DAIKIN
Installation manual
Daikin room air conditioner
Model: FTXF50F5V1B
1 About the documentation
1.1 About this document
INFORMATION: Make sure that the user has the printed documentation and ask him/her to keep it for future reference.
Target audience: Authorised installers
INFORMATION: This appliance is intended to be used by expert or trained users in shops, in light industry, and on farms, or for commercial and household use by lay persons.
Documentation set: This document is part of a documentation set. The complete set consists of:
- General safety precautions: Safety instructions that you MUST read before installing. Format: Paper (in the box of the indoor unit).
- Indoor unit installation manual: Installation instructions. Format: Paper (in the box of the indoor unit).
- Installer reference guide: Preparation of the installation, good practices, reference data, etc. Format: Digital files on https://www.daikin.eu. Use the search function to find your model.
The latest revision of the supplied documentation is published on the regional Daikin website and is available via your dealer. The original instructions are written in English. All other languages are translations of the original instructions.
Technical engineering data: A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of the latest technical data is available on the Daikin Business Portal (authentication required).
2 Specific installer safety instructions
Always observe the following safety instructions and regulations.
Unit installation (see "5 Unit installation" [5])
WARNING: Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard.
Installation site (see "5.1 Preparing the installation site" [5])
CAUTION:
- Check if the installation location can support the unit's weight. Poor installation is hazardous. It can also cause vibrations or unusual operating noise.
- Provide sufficient service space.
- Do NOT install the unit so that it is in contact with a ceiling or a wall, as this may cause vibrations.
WARNING: The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
Connecting the refrigerant piping (see "6.2 Connecting the refrigerant piping" [9])
CAUTION:
- No brazing or welding on site for units with R32 refrigerant charge during shipment.
- During installation of the refrigeration system, joining of parts with at least one part charged shall be performed taking into account the following requirements: inside occupied spaces non-permanent joints are NOT allowed for R32 refrigerant except for site made joints directly connecting the indoor unit to piping. Site made joints directly connecting piping to indoor units shall be of non-permanent type.
NOTICE:
- Use the flare nut fixed to the unit.
- To prevent gas leakage, apply refrigeration oil ONLY to the inside of the flare. Use refrigeration oil for R32 (FW68DA).
- Do NOT reuse joints.
NOTICE:
- Do NOT use mineral oil on flared part.
- Do NOT reuse piping from previous installations.
- NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material may dissolve and damage the system.
WARNING: Connect the refrigerant piping securely before running the compressor. If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run, air will be sucked in. This will cause abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
CAUTION:
- Incomplete flaring may cause refrigerant gas leakage.
- Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
- Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage.
CAUTION: Do NOT open the valves before flaring is complete. This would cause refrigerant gas leakage.
DANGER: RISK OF EXPLOSION: Do NOT open the stop valves before the vacuum drying is finished.
Charging refrigerant (see Charging refrigerant)
WARNING: The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the refrigerant leaks in the room and comes in contact with fire from a burner, a heater, or a cooker, this may result in fire, or the formation of a harmful gas. Turn OFF any combustible heating devices, ventilate the room, and contact the dealer where you purchased the unit. Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.
WARNING: Only use R32 as refrigerant. Other substances may cause explosions and accidents. R32 contains fluorinated greenhouse gases. Its global warming potential (GWP) value is 675. Do NOT vent these gases into the atmosphere. When charging refrigerant, ALWAYS use protective gloves and safety glasses.
NOTICE: To avoid compressor breakdown, do NOT charge more than the specified amount of refrigerant.
WARNING: NEVER directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
Electrical installation (see "7 Electrical installation" [10])
WARNING: The appliance MUST be installed in accordance with national wiring regulations.
WARNING: All wiring MUST be performed by an authorised electrician and MUST comply with the national wiring regulation. Make electrical connections to the fixed wiring. All components procured on-site and all electrical construction MUST comply with the applicable legislation.
WARNING: If the power supply has a missing or wrong N-phase, equipment might break down. Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shocks. Install the required fuses or circuit breakers. Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side. Do NOT use taped wires, extension cords, or connections from a star system. They can cause overheating, electrical shocks or fire. Do NOT install a phase advancing capacitor, because this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING: ALWAYS use multicore cable for power supply cables.
3 About the box
WARNING: Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III.
WARNING: If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING: Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING:
- Do NOT use locally purchased electrical parts inside the product.
- Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire.
WARNING: Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.
DANGER: RISK OF ELECTROCUTION: All electrical parts (including thermistors) are powered by the power supply. Do NOT touch them with bare hands.
DANGER: RISK OF ELECTROCUTION: Disconnect the power supply for more than 10 minutes, and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Finishing indoor unit installation (see Finishing the outdoor unit installation)
DANGER: RISK OF ELECTROCUTION:
- Make sure that the system is earthed properly.
- Turn OFF the power supply before servicing.
- Install the switch box cover before turning ON the power supply.
Commissioning (see "10 Commissioning" [12])
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
CAUTION:
- Do NOT perform the test operation while working on the indoor unit(s).
- When performing the test operation, NOT ONLY the outdoor unit, but the connected indoor unit will operate as well. Working on an indoor unit while performing a test operation is dangerous.
CAUTION: Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.
WARNING: MILDLY FLAMMABLE MATERIAL: The refrigerant inside this unit is mildly flammable.
3.1 Indoor unit
INFORMATION: The following figures are examples and may NOT completely match your system layout.
3.1.1 To remove the accessories from the indoor unit
1. Remove:
- The accessory bag located at the bottom of the package.
- The mounting plate attached to the back of the indoor unit.
- The spare SSID sticker located on the front grille.
Diagram showing accessories: a. Installation manual, b. Operation manual, c. General safety precautions, d. Spare SSID sticker, e. Indoor unit fixing screw (M4×12L), f. Dry battery AAA.LR03 (alkaline) for user interface, g. Holder for wireless remote control, h. Wireless remote control, i. Mounting plate.
2. Spare SSID sticker: Do NOT throw away the spare sticker. Keep it in a safe place in case it is needed in future (e.g. in case the front grille was replaced, attach it to the new front grille).
4 About the unit
WARNING: MILDLY FLAMMABLE MATERIAL: The refrigerant inside this unit is mildly flammable.
4.1 System layout
INFORMATION: The following figures are examples and may NOT completely match your system layout.
Diagram showing system layout components: a. Indoor unit, b. Service lid, c. Air filter, d. Titanium apatite deodorizing and silver particle filter, e. Refrigerant piping, drain hose and interconnection cable, f. Insulation tape.
4.2 Operation range
Use the system in the following temperature and humidity ranges for safe and effective operation.
4.3 About the wireless LAN
For detailed specifications, installation instructions, setting methods, FAQ, declaration of conformity and the latest version of this manual, visit app.daikineurope.com.
INFORMATION: Declaration of conformity
Daikin Europe N. V. declares that the radio equipment type inside of this unit is in compliance with Directive 2014/53/EU and S.I. 2017/1206: Radio Equipment Regulations 2017. This unit is considered as combined equipment according to the definition of Directive 2014/53/EU and S.I. 2017/1206: Radio Equipment Regulations 2017.
4.3.1 Precautions when using the wireless LAN
Do NOT use near:
- Medical equipment (e.g., persons using cardiac pacemakers or defibrillators). This product may cause electromagnetic interference.
- Auto-control equipment (e.g., automatic doors or fire alarm equipment). This product may cause faulty behaviour of the equipment.
- Microwave ovens. It may affect wireless LAN communications.
4.3.2 Basic parameters
What | Value |
---|---|
Frequency range | 2400 MHz~2483.5 MHz |
Radio protocol | IEEE 802.11b/g/n |
Radio frequency channel | 1~13 |
Output power | 13 dBm |
Effective radiated power | 15 dBm (11b) / 14 dBm (11g) / 14 dBm (11n) |
Power supply | DC 14 V / 100 mA |
5 Unit installation
5.1 Preparing the installation site
WARNING: The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
WARNING: The appliance using R32 refrigerant shall be stored so as to prevent mechanical damage and in a well-ventilated room without continuously operating ignition sources (e.g. open flames, an operating gas appliance, or an operating electric heater). The room size shall be as specified in the General safety precaution.
5.1.1 Installation site requirements of the indoor unit
INFORMATION:
- The sound pressure level is less than 70 dBA.
- Air flow: Make sure nothing blocks the air flow.
- Drainage: Make sure condensation water can be evacuated properly.
- Wall insulation: When conditions in the wall exceed 30°C and a relative humidity of 80%, or when fresh air is inducted into the wall, then additional insulation is required (minimum 10 mm thickness, polyethylene foam).
- Wall strength: Check whether the wall or the floor is strong enough to support the weight of the unit. If there is a risk, reinforce the wall or the floor before installing the unit.
- Spacing: Install the unit at least 1.8 m from the floor and keep the following requirements in mind for distances from the walls and the ceiling: 30 mm (side), 50 mm (back), 50 mm (top).
5.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up. In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is NOT affected by the snow. If necessary, install a snow cover or shed and a pedestal.
5.2 Opening the indoor unit
5.2.1 To remove the front panel
1. Hold the front panel by the panel tabs on both sides and open it.
2. Remove the front panel by sliding it to the left or the right and pulling it toward you. Result: The front panel shaft on 1 side will be disconnected.
3. Disconnect the front panel shaft on the other side in the same manner.
5.2.2 To re-install the front panel
1. Attach the front panel. Align the shafts with the slots and push them all the way in.
2. Close the front panel slowly; press at both sides and at the centre.
5.2.3 To remove the front grille
CAUTION: Wear adequate personal protective equipment (protective gloves, safety glasses,...) when installing, maintaining or servicing the system.
1. Remove the front panel to remove the air filter.
2. Remove 2 screws (class 20~35) or 3 screws (class 50~71) from the front grille.
3. Push down the 3 upper hooks marked with a symbol with 3 circles.
4. We recommend opening the flap before removing the front grille.
5. Place both hands under the centre of the front grille, push it up and then toward you.
5.2.4 To re-install the front grille
1. Install the front grille and firmly engage the 3 upper hooks.
2. Install 2 screws back on the front grille.
3. Install the air filter and then mount the front panel.
5.2.5 To remove the electrical wiring box cover
Prerequisite: Remove the front grille.
1. Remove 1 screw from the electrical wiring box.
2. Open the electrical wiring box cover by pulling the protruding part on the top of the cover.
3. Unhook the tab on the bottom and remove the electrical wiring box cover.
5.2.6 To open the service cover
1. Remove 1 screw from the service cover.
2. Pull out the service cover horizontally away from the unit.
5.3 Mounting the indoor unit
5.3.1 To install the mounting plate
1. Install the mounting plate temporarily.
2. Level the mounting plate.
3. Mark the centres of the drilling points on the wall using a tape measure. Position the end of tape measure at symbol ">
4. Finish the installation by securing the mounting plate on the wall using M4×25L screws (field supply).
INFORMATION: The removed pipe port cover can be kept in the mounting plate pocket.
5.3.2 To drill a wall hole
Diagram showing mounting plate dimensions and hole positions: Overall width 770 mm, height 286 mm. Piping hole centers at 160 mm left and 170 mm right. Hole for embedded piping Ø65 mm.
CAUTION: For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
NOTICE: Be sure to seal the gaps around the pipes with sealing material (field supply), in order to prevent water leakage.
1. Bore a 65 mm large feed-through hole in the wall with a downward slope towards the outside.
2. Insert a wall embedded pipe into the hole.
3. Insert a wall cover into the wall pipe.
4. After completing wiring, refrigerant piping and drain piping, do NOT forget to seal the gap with putty.
5.3.3 To remove the pipe port cover
INFORMATION: To connect the piping on right-side, right-bottom, left-side or left-bottom, the pipe port cover MUST be removed.
1. Cut off the pipe port cover from inside the front grille using a coping saw.
2. Remove any burrs along the cut section using a half round needle file.
NOTICE: Do NOT use nippers to remove the pipe port cover, as this would damage the front grille.
5.3.4 To provide drainage
Make sure condensation water can be evacuated properly. This involves:
- General guidelines
- Connecting the drain piping to the indoor unit
- Checking for water leaks
General guidelines:
- Pipe length: Keep drain piping as short as possible.
- Pipe size: If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.
NOTICE:
- Install the drain hose with a downward slope.
- Traps are NOT permitted.
- Do NOT put the end of the hose in water.
Drain hose extension: To extend the drain hose, use a field supplied hose with inner Ø16 mm. Do NOT forget to use a heat insulation tube on the indoor section of the extension hose.
Rigid polyvinyl chloride pipe: When connecting a rigid polyvinyl chloride pipe (nominal Ø13 mm) directly to the drain hose as with embedded piping work, use a field supplied drain socket (nominal Ø13 mm).
Condensation: Take measures against condensation. Insulate the complete drain piping in the building.
1. Insert the drain hose in the drain pipe as shown in the following figure, so it will NOT be pulled out of the drain pipe.
To connect the piping on right side, right-back, or right-bottom
INFORMATION: The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side.
1. Attach the drain hose with adhesive vinyl tape to the bottom of the refrigerant pipes.
2. Wrap the drain hose and the refrigerant pipes together using insulation tape.
Diagram showing piping connection sides: A. Right-side piping, B. Right-bottom piping, C. Right-back piping. Labels indicate where to remove the pipe port cover.
To connect the piping on left side, left-back, or left-bottom
INFORMATION: The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side.
1. Remove the insulation fixing screw on the right side and remove the drain hose.
2. Remove the drain plug on the left side and attach it to the right side.
NOTICE: Do NOT apply lubricating oil (refrigerant oil) to the drain plug when inserting it. The drain plug may deteriorate and cause drain leakage from the plug.
3. Insert the drain hose on the left side and do not forget to tighten it with the fixing screw; otherwise water leakage may occur.
4. Attach the drain hose to the refrigerant piping bottom side using adhesive vinyl tape.
Diagram showing piping connection sides: A. Left-side piping, B. Left-back piping, C. Left-bottom piping. Labels indicate where to remove the pipe port cover.
To check for water leaks:
1. Remove the air filters.
2. Gradually pour approximately 1 l of water in the drain pan, and check for water leaks.
6 Piping installation
6.1 Preparing refrigerant piping
6.1.1 Refrigerant piping requirements
NOTICE: The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant piping. Foreign materials inside pipes (including oils for fabrication) must be ≤30 mg/10 m.
Refrigerant piping diameter: Use the same diameters as the connections on the outdoor units:
- Liquid piping: Ø6.4 mm (1/4")
- Gas piping: Ø12.7 mm (1/2")
Refrigerant piping material: Phosphoric acid deoxidised seamless copper
Flare connections: Only use annealed material.
Piping temper grade and thickness:
- Outer diameter (Ø): 6.4 mm (1/4")
- Temper grade: Annealed (O)
- Thickness (t)(a): ≥0.8 mm
(a) Depending on the applicable legislation and the maximum working pressure of the unit (see "PS High" on the unit name plate), larger piping thickness might be required.
6.1.2 Refrigerant piping insulation
Use polyethylene foam as insulation material:
- With a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and 0.045 kcal/mh°C).
- With a heat resistance of at least 120°C.
Insulation thickness:
- Pipe outer diameter (Øp): 6.4 mm (1/4")
- Insulation inner diameter (Øi): 8~10 mm
- Insulation thickness (t): ≥10 mm
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.
6.2 Connecting the refrigerant piping
DANGER: RISK OF BURNING/SCALDING
6.2.1 Guidelines when connecting the refrigerant piping
Take the following guidelines into account when connecting pipes:
- Coat the flare inner surface with ether oil or ester oil when connecting a flare nut. Tighten 3 or 4 turns by hand, before tightening firmly.
- ALWAYS use 2 wrenches together when loosening a flare nut.
- ALWAYS use a spanner and torque wrench together to tighten the flare nut when connecting the piping. This to prevent nut cracking and leaks.
Diagram showing tools: a. Torque wrench, b. Spanner, c. Piping union, d. Flare nut.
Flare connection dimensions:
Piping size (mm) | Tightening torque (Nm) | Flare dimensions (A) (mm) | Flare shape (mm) |
---|---|---|---|
Ø6.4 | 15~17 | 8.7~9.1 | 90°±2 |
Ø12.7 | 50~60 | 16.2~16.6 | 45°±2 |
Diagram showing flare shape R=0.4~0.8.
6.2.2 To connect the refrigerant piping to the indoor unit
WARNING: MILDLY FLAMMABLE MATERIAL: The refrigerant inside this unit is mildly flammable.
Pipe length: Keep refrigerant piping as short as possible.
1. Connect refrigerant piping to the unit using flare connections.
7 Electrical installation
Diagram showing insulation of piping, cable, and hose.
NOTICE: Make sure to insulate all refrigerant piping. Any exposed piping might cause condensation.
6.3 Checking the refrigerant piping
6.3.1 To check for leaks
NOTICE: Do NOT exceed the unit's maximum working pressure (see "PS High" on the unit name plate).
NOTICE: ALWAYS use a recommended bubble test solution from your wholesaler. NEVER use soap water:
- Soap water may cause cracking of components, such as flare nuts or stop valve caps.
- Soap water may contain salt, which absorbs moisture that will freeze when the piping gets cold.
- Soap water contains ammonia which may lead to corrosion of flared joints (between the brass flare nut and the copper flare).
1. Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa (2 bar). It is recommended to pressurize to 3000 kPa (30 bar) or higher (depending on local legislation) to detect small leaks.
2. Check for leaks by applying the bubble test solution to all connections.
3. Discharge all nitrogen gas.
6.3.2 To perform vacuum drying
1. Vacuum the system until the pressure on the manifold indicates -0.1 MPa (-1 bar).
2. Leave as is for 4-5 minutes and check the pressure:
- If the pressure does not change: There is no moisture in the system. This procedure is finished.
- If the pressure increases: There is moisture in the system. Go to the next step.
3. Vacuum the system for at least 2 hours to a manifold pressure of -0.1 MPa (-1 bar).
4. After turning the pump OFF, check the pressure for at least 1 hour.
5. If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour, do the following:
- Check for leaks again.
- Perform vacuum drying again.
DANGER: RISK OF ELECTROCUTION
WARNING: ALWAYS use multicore cable for power supply cables.
WARNING: Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III.
WARNING: If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING: Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING:
- Do NOT use locally purchased electrical parts inside the product.
- Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire.
WARNING: Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.
7.1 Specifications of standard wiring components
NOTICE: We recommend using solid wires. If stranded wires are used, slightly twist the strands to consolidate the end of the conductor for either direct use in the terminal clamp or insertion in a round crimp-style terminal. Details are described in "Guidelines when connecting the electrical wiring" in the installer reference guide.
Specifications | Value |
---|---|
Voltage | 220~240 V |
Phase | 1~ |
Frequency | 50 Hz |
Interconnection cable | Only use harmonised wire providing double insulation and suitable for the applicable voltage. 4-core cable Minimum 1.5 mm² |
7.2 To connect the electrical wiring to the indoor unit
WARNING: Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
NOTICE:
- Keep power supply wiring and interconnection wiring apart from each other. Interconnection wiring and power supply wiring may cross, but may NOT run parallel.
- In order to avoid any electrical interference, the distance between both wirings should ALWAYS be at least 50 mm.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice.
1. Set the indoor unit on the mounting plate hooks. Use the " " marks as a guide.
2. Open the front panel, and then the service cover. Refer to "5.2 Opening the indoor unit" [5].
3. Pass the interconnection cable from the outdoor unit through the feed-through wall hole, through the back of the indoor unit and through the front side. Note: In case the interconnection cable was stripped in advance, cover the ends with insulating tape.
4. Bend the end of the cable up.
5. Strip the wire ends approximately 15 mm.
6. Match wire colours with terminal numbers on the indoor unit terminal blocks and firmly screw the wires to the corresponding terminals.
7. Connect the earth wire to the corresponding terminal.
8. Firmly fix the wires with the terminal screws.
9. Pull the wires to make sure that they are securely attached, then retain the wires with the wire retainer.
10. Shape the wires so that the service cover fits securely, then close the service cover.
8 Finishing the indoor unit installation
8.1 To insulate the drain piping, refrigerant piping and interconnection cable
1. After the drain piping, refrigerant piping and the electrical wiring are finished, wrap refrigerant piping, interconnection cable and drain hose together using insulation tape. Overlap at least half the width of the tape with each turn.
Diagram showing components to be insulated: a. Drain hose, b. Interconnection cable, c. Mounting plate, d. Refrigerant piping, e. Indoor unit fixing screw, f. Bottom frame.
8.2 To pass the pipes through the wall hole
1. Shape the refrigerant pipes along the pipe path marking on the mounting plate.
Diagram showing drain hose and putty for sealing the wall hole.
NOTICE:
- Do NOT bend refrigerant pipes.
- Do NOT push the refrigerant pipes onto the bottom frame or the front grille.
8.3 To fix the unit on the mounting plate
1. Set the indoor unit on the mounting plate hooks. Use the " " marks as a guide.
2. Press the bottom frame of the unit with both hands to set it on the bottom hooks of the mounting plate. Make sure that the wires do NOT get squeezed anywhere. Note: Take care that the interconnection cable does NOT get caught in the indoor unit.
3. Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks.
4. Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4×12L (accessory).
5. Pass the drain hose and refrigerant piping through the wall hole and seal the gap with a putty.
9 Configuration
9.1 To set a different channel of the indoor unit infrared signal receiver
In case 2 indoor units are installed in 1 room, you can change the channel for the infrared signal receiver on the indoor unit to avoid the wireless remote control signal confusion.
Prerequisite: Perform the following setting for only 1 of the units:
1. Remove the batteries from the user interface.
2. Cut the address jumper.
3. Turn the power supply on.
Result: The flap of the indoor unit will open and close to set the reference position.
INFORMATION: In case you could NOT complete the setting in time, turn the power supply off and wait at least 1 minute before turning the power supply back on.
4. Press simultaneously: Model FTXF and ATXF Buttons: , , and .
5. Press: Model FTXF and ATXF Buttons: .
6. Select: Model FTXF and ATXF Symbol: R.
7. Press: Model FTXF and ATXF Button: ON/OFF.
8. Press the indoor unit ON/OFF switch while the operation lamp is blinking.
Jumper Address:
- Factory setting: 1
- After cutting with nippers: 2
INFORMATION: If the setting could NOT be completed while the operation lamp was blinking, repeat the setting process from the beginning.
9. When the setting is complete, press: Model FTXF and ATXF Button: Keep pressed for about 5 seconds.
Result: The user interface will return to the previous screen.
10 Commissioning
NOTICE: ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT, burning of the compressor might be the result.
10.1 Checklist before commissioning
1. After the installation of the unit, check the items listed below.
2. Close the unit.
3. Power up the unit.
- You read the complete installation instructions, as described in the installer reference guide.
- The indoor units are properly mounted.
- The outdoor unit is properly mounted.
- Air inlet/outlet: Check that the air inlet and outlet of the unit is NOT obstructed by paper sheets, cardboard, or any other material.
- There are NO missing phases or reversed phases.
- The refrigerant pipes (gas and liquid) are thermally insulated.
- Drainage: Make sure drainage flows smoothly. Possible consequence: Condensate water might drip.
- The system is properly earthed and the earth terminals are tightened.
- The fuses or locally installed protection devices are installed according to this document, and have NOT been bypassed.
- The power supply voltage matches the voltage on the identification label of the unit.
- The specified wires are used for the interconnection cable.
- The indoor unit receives the signals of the user interface.
- There are NO loose connections or damaged electrical components in the switch box.
- The insulation resistance of the compressor is OK.
- There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units.
- There are NO refrigerant leaks.
- The correct pipe size is installed and the pipes are properly insulated.
- The stop valves (gas and liquid) on the outdoor unit are fully open.
10.2 To perform a test run
Prerequisite: The power supply MUST be in the specified range.
Prerequisite: Test run may be performed in cooling or heating mode.
Prerequisite: Refer to the operation manual of the indoor unit for setting temperature, operation mode....
1. In cooling mode, select the lowest programmable temperature. In heating mode, select the highest programmable temperature. The test run can be disabled if necessary.
2. When the test run is finished, set the temperature to a normal level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
3. Make sure that all functions and parts are working properly.
4. The system stops operating 3 minutes after the unit is turned OFF.
10.2.1 To perform a test run in winter season
When operating the air conditioner in Cooling mode in winter, set it to test run operation using the following method.
1. Press TEMP , COOL , and OFF simultaneously.
2. Press TEMP .
3. Select .
4. Press FAN .
5. Press COOL to switch the system on.
Result: Test run operation will stop automatically after about 30 minutes.
6. To stop operation, press OFF .
INFORMATION: Some of the functions CANNOT be used in the test run operation mode.
If a power failure occurs during operation, the system automatically restarts immediately after power is restored.
11 Disposal
NOTICE: Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
12 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible).
The full set of the latest technical data is available on the Daikin Business Portal (authentication required).
12.1 Wiring diagram
The wiring diagram is delivered with the unit, located inside of the outdoor unit (bottom side of the top plate).
12.1.1 Unified wiring diagram legend
For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by "*" in the part code.
Symbols and Meanings:
- Circuit breaker: Circuit breaker
- Protective earth: Protective earth
- Noiseless earth: Noiseless earth
- Connection: Connection
- Connector: Connector
- Earth: Earth
- Field wiring: Field wiring
- Fuse: Fuse
- Indoor unit: Indoor unit
- Outdoor unit: Outdoor unit
- Residual current device: Residual current device
- Protective earth (screw): Protective earth (screw)
- Rectifier: Rectifier
- Relay connector: Relay connector
- Short-circuit connector: Short-circuit connector
- Terminal: Terminal
- Terminal strip: Terminal strip
- Wire clamp: Wire clamp
- Heater: Heater
- FG*: Connector (frame ground)
- H*: Harness
- H*P, LED*, V*L: Pilot lamp, light emitting diode
- HAP: Light emitting diode (service monitor green)
- HIGH VOLTAGE: High voltage
- IES: Intelligent eye sensor
- IPM*: Intelligent power module
- K*R, KCR, KFR, KHUR, K*M: Magnetic relay
- L: Live
- L*: Coil
- L*R: Reactor
- M*: Stepper motor
- M*C: Compressor motor
- M*F: Fan motor
- M*P: Drain pump motor
- MR*, MRCW*, MRM*, MRN*: Magnetic relay
- N: Neutral
- n=*, N=*: Number of passes through ferrite core
- PAM: Pulse-amplitude modulation
- PCB*: Printed circuit board
- PM*: Power module
- PS: Switching power supply
- PTC*: PTC thermistor
- Q*: Insulated gate bipolar transistor (IGBT)
- Q*C: Circuit breaker
- Q*DI, KLM: Earth leak circuit breaker
- Q*L: Overload protector
- Q*M: Thermo switch
- Q*R: Residual current device
- R*: Resistor
- R*T: Thermistor
- RC: Receiver
- S*C: Limit switch
- S*L: Float switch
- S*NG: Refrigerant leak detector
- S*NPH: Pressure sensor (high)
- S*NPL: Pressure sensor (low)
- S*PH, HPS*: Pressure switch (high)
- S*PL: Pressure switch (low)
- S*T: Thermostat
- S*RH: Humidity sensor
- S*W, SW*: Operation switch
- SA*, F1S: Surge arrester
- SR*, WLU: Signal receiver
- SS*: Selector switch
- SHEET METAL: Terminal strip fixed plate
- T*R: Transformer
- TC, TRC: Transmitter
- V*, R*V: Varistor
- V*R: Diode bridge, Insulated-gate bipolar transistor (IGBT) power module
- WRC: Wireless remote controller
- X*: Terminal
- X*M: Terminal strip (block)
- Y*E: Electronic expansion valve coil
- Y*R, Y*S: Reversing solenoid valve coil
- Z*C: Ferrite core
- ZF, Z*F: Noise filter