Reliable and Precise Monitoring of Electrical Power Systems
Introducing the SENTRON PAC3200, a powerful and compact power monitoring device designed for industrial, government, and commercial applications.
Key Features and Applications
The SENTRON PAC3200 is suitable for basic metering and energy monitoring. It can be used as a standalone device monitoring over 50 parameters or as part of a larger industrial control, building automation, or global power monitoring system. Applications range from replacing simple analog volt and amp meters to implementing standalone sub-billing or cost allocation systems with multiple tariffs. It also supports LEED certification and provides energy metering data for government energy reduction programs.
The SENTRON PAC3200 offers open communications via Modbus RTU/TCP and PROFIBUS-DP protocols, enabling easy integration into local or remote monitoring systems. Configuration is straightforward, accessible directly from the front display or via the PC-based SENTRON powerconfig setup software.
Device Dimensions: 96 mm x 96 mm (3.78 in. x 3.78 in.).
Display: Features a full graphic LCD display that indicates display title, measurements, phase, measured value, unit, and function key labels. The display is gradually adjustable for optimum visibility in various lighting conditions.
Operating Menu: Texts can be displayed in multiple languages, selectable directly on the device. The menu includes options such as SETTINGS, DEVICE INFORMATION, LANGUAGE/REGIONAL, BASIC PARAMETERS, POWER DEMAND, and ENERGY COUNTER.
Connectivity: Modbus TCP is integrated as standard. Expansion modules for PROFIBUS DP and MODBUS RTU are available for remote data transmission. Terminal blocks are provided for voltage and current measuring, control power, and digital input/output.
Image Description: A front view of the SENTRON PAC3200 meter, a compact, front-panel mounted power monitoring device with a digital display and four function buttons.
Image Description: An illustration of the SENTRON PAC3200 operating menu on its LCD screen, showcasing various system settings and data points.
Image Description: A diagram illustrating the SENTRON PAC3200's connectivity, including integrated Modbus TCP, optional PROFIBUS DP and MODBUS RTU expansion modules, and terminal blocks for electrical connections.
Making Consumption Apparent
To achieve sustainable power cost reduction, analyzing electrical system consumption and power flows is essential. The SENTRON PAC3200 power meter provides precise and reliable information to guide power cost reduction efforts.
Application Summary
- Replace Multiple Analog Meters: An ideal replacement for analog meters in custom panels, switchboards, switchgear, gensets, motor control centers, UPS systems, PDUs, RPPs, and more.
- Basic Metering: Offers high-accuracy power, energy, and demand measurements. These revenue-accurate values are useful for bill verification, monitoring backup power on critical systems, and implementing cost-effective energy solutions.
- Cost Allocation / Energy Monitoring: Facilitates monitoring down to the tool level, helping to track cost centers, identify demand control opportunities, and analyze energy consumption patterns.
- Automation Integration: Enables monitoring of critical equipment processes and direct integration with Siemens PLCs and automation networks.
- Sub-metering: Provides a low-cost, high-accuracy solution for measuring energy consumption in commercial and residential tenant spaces, integrating with existing energy management systems and RTUs to reduce energy consumption by eliminating uncontrolled expenses.
Functional Features
Instantaneous Values
Parameter | Specification | |
---|---|---|
Voltage | Phase-phase / phase-neutral | ✔️ |
Currents | Per phase | ✔️ |
Apparent, active and reactive power | Per phase and total | ✔️ |
Power factor | Per phase and total | ✔️ |
Frequency | 45...64 Hz | ✔️ |
THD for voltage and current | Per phase | ✔️ |
Min. / max. values | Voltage - phase-phase, phase-neutral; Current / Power / Power factor / THD per phase; Frequency | ✔️ |
Average values | Three phase average voltage and current; Voltage phase-phase, phase-neutral; Voltage min. / max. for phase-phase-phase-neutral; Current; Current min. / max. | ✔️ |
Energy Measurement
Parameter | Specification | |
---|---|---|
Active energy | Import / export; high / low tariff | ✔️ |
Reactive energy | Positive / negative; high / low tariff | ✔️ |
Apparent energy | High / low tariff | ✔️ |
Energy demand per measuring period | Three phase average rating for active and reactive power | 1 to 60 min. |
Min. / max. rating values within the measuring period | ✔️ | |
Meter running counter | Uptime in hours | ✔️ |
Universal counter | Pulse counting of external devices like water, gas, etc. | ✔️ |
Measurement Accuracy
Parameter | Accuracy |
---|---|
Voltages | ±0.3 |
Currents | ±0.2 |
Power factor and power | ±0.5% |
Active energy | Class 0.5S in acc. with IEC 62053-22 / ANSI 12.20 class 0.5 |
Reactive energy | Class 2 in acc. with IEC 62053-23 |
Monitoring Functions
Function | Specification |
---|---|
Set point monitoring | V, I, power, VAR, VA, Freq., THD, PF |
Simple logic functions for alarming | Alarm via digital output or software |
Phase unbalance | Voltage and/or current |
Communication
Interface | Specification | Supported Baud Rates |
---|---|---|
Ethernet | Integrated 10 Base-T (10 Mbit/sec) | |
Modbus TCP | Integrated RJ45 port 10 Base-T (10 Mbit/sec) | |
PROFIBUS DP expansion module | Optional; Parameterization via device front or SENTRON powerconfig software; Transition of data via GSD file | Support of all baud rates from 9600 BPS to 12 MBPS (9.6 Kbit/sec to 12 Mbit/sec) |
Modbus RTU expansion module | Optional; Parameterization via device front or SENTRON powerconfig software; Transition of data via MODBUS register based points | Support of all baud rates of 4800, 9600, 19.2K and 38.4K BPS (4.8/9.6 / 19.2 and 38.4 kB/sec) |
Technical Specifications
Standard Inputs / Outputs
Feature | Specification |
---|---|
Integrated digital input | 24 Vdc / 7 mA |
Integrated digital output | 30 Vdc max. / 10-27 mA; 100 mA max. |
General Password protection | 1, dry contact, requires external power ✔️ |
Technical Data
Parameter | Specification |
---|---|
Measurement type | Two-quadrant (import) / four-quadrant (import and export) measuring |
Applicable for network type | 1 ph, 2 ph or 3 ph; TN, TT, IT |
Sampling rate | 64 samples / cycle at 60Hz |
Measured voltage | Direct connection up to max. delta/wye without transformer |
Current inputs | Settable on device |
Power supply | AC/DC; DC only |
Dimensions | L x W x D in mm: 96 x 96; Installation depth without module: 51 mm / 2.0 in.; Installation depth with module: 73 mm / 2.875 in. |
Degree of protection | Front: IP65 (for UL IP54); Rear: IP20, NEMA 1A |
Operating temperature | -5...+55 °C / +23...+131 °F |
Display | Type: Background-illuminated graphic LCD; Resolution: 128 x 96 pixels; Text displays: Multilingual |
Optional ports | One port is available for optional modules |
Certifications
- UL61010-1, 2nd Ed. Safety of Electrical Equipment for Measurement, Control and Laboratory Use Part 1: General Requirements
- CAN/CSA-C22.2 NO. 61010-1-04, 2nd Ed. Safety for Electrical Equipment for Measurement, Control and Laboratory Use
- CE IEC 61010-1 2nd Ed. Safety for Electrical Equipment for Measurement, Control and Laboratory Use Part 1: General Requirements
Order Information
Product | Order No. |
---|---|
SENTRON PAC3200 compression terminals not suitable for use with ring tongue terminals, AC/DC | 7KM2112-0BA00-3AA0 |
SENTRON PAC3200 compression terminals not suitable for use with ring tongue terminals, DC only | 7KM2111-1BA00-3AA0 |
SENTRON PAC PROFIBUS DP expansion module | 7KM9300-0AB00-0AA0 |
SENTRON PAC MODBUS RTU expansion module | 7KM9300-0AM00-0AA0 |
Connector block suitable for use with ring tongue terminals | Consult Siemens Sales |
SENTRON Adapter Plate for 4700/4720 meter cutout | 93-47ADAPTER |
SITOP Power Supply AC 99-264VAC, 24 VDC, 0.5A | 6EP1331-2BA10 |
SENTRON PAC3200/4200 Meter DIN Rail adapter - Meter display will not be seen | 7KM9900-0YA00-0AA0 |
Note: Omit dashes from part numbers when ordering except on 93-47ADAPTER.