CONTROL BOX Control Box description - www.engocontrols.com

output 1 l2 sl1 l2 sl1 output 2 l2 sl2 l2 sl2 output 3 l2 sl3 l2 sl3 output 4 l2 sl4 l2 sl4 output 5 l2 sl5 l2 sl5 output 6 l2 sl6 l2 sl6 output 7 l2 sl7 l2 sl7


File Info : application/pdf, 2 Pages, 1.04MB

PDF preview unavailable. Download the PDF instead.

ECB8-24 QG A3 ENG-v1.0
CONTROL BOX
ECB8-24 | Wired Control Box for Underfloor Heating System, 24V

Control Box description
1. Cartridge fuse 5 x 20 mm T10A 2. Power supply (AC 24V) 3. Pump control output (volt free)

4. Boiler control output (volt free) 5. Thermostats input connections 6. Actuators output connections (AC 24V)
5

7. LED diodes indicators for the operation status of the pump, boiler and control box power supply connection
8. LEDs 1 to 8 informing about the operation of zones 1-8

Quick Guide
Ver. 1.0 Release date: VII 2024
Soft: v1.3
Producer: Engo Controls sp z o.o. sp. k.
Rolna 4 St. 43-262 Kobielice
Polska
www.engocontrols.com

L2 L1 SL1 L2 L1 SL2 L2 L1 SL3 L2 L1 SL4 L2 L1 SL5 L2 L1 SL6 L2 L1 SL7 L2 L1 SL8 INPUT_1 INPUT_2 INPUT_3 INPUT_4 INPUT_5 INPUT_6 INPUT_7 INPUT_8

THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT

8

LED

LED

LED

LED

LED

LED

LED

LED

ACTUATOR

ACTUATOR

ACTUATOR

ACTUATOR

ACTUATOR

ACTUATOR

ACTUATOR

ACTUATOR

LED

LED

LED

24V AC IN

OUTPUT_1 OUTPUT_2 OUTPUT_3 OUTPUT_4 OUTPUT_5 OUTPUT_6 OUTPUT_7 OUTPUT_8 FUSE 10A
L2 SL1 L2 SL1 L2 SL2 L2 SL2 L2 SL3 L2 SL3 L2 SL4 L2 SL4 L2 SL5 L2 SL5 L2 SL6 L2 SL6 L2 SL7 L2 SL7 L2 SL8 L2 SL8

POWER SUPPLY
L2 L1

6

1

2

7
Pump status Boiler status Power supply

LED

LED

LED

VOLT FREE VOLT FREE

PUMP OUTPUT BOILER OUTPUT
NO COM NO COM NC

3

4

Introduction
ECB8-24 control box is the main element of the underfloor heating control system. It has a built-in modules that controls the heat sources and pump (by volt-free relay). The control box allows to control 8 different zones. It is equipped with 24V AC voltage outputs actuators. Pluggable terminal blocks provide quick and convenient wiring connections. The control box is designed to work with NC (normally-closed) type actuators.
Product compliance
This product complies with the essential requirements and other relevant provisions of the following EU Directives: EMC 2014/30/EU, Low Voltage Directive LVD 2014/35/EU, RoHS directive 2011/65/EU.

Safety information
Use in accordance with national and EU regulations. Device is intended for indoor use only in dry conditions. Product for indoor use only. Installation must be carried out by a qualified person in accordance to national and EU regulations. Before attempting to setup and install, make sure that control box is not connected to any power source. Installation must be carried out by a qualified person. Incorrect installation may cause damage to the wiring centre. The control box should not be installed in areas where it may be exposed to water or damp conditions. PLEASE NOTE: For the entire installation, there may be additional protection requirements, which the installer is responsible for maintaining.

Technical Information

Power Supply Fuse (Total Load Max) Pump Load Max Boiler Load Max Outputs
Dimensions [mm]

24 V AC 50 Hz 10 A 6A 6A
Boiler control (NO/COM/NC) Pump control (NO/COM) Terminals for actuators (24V AC)
327 x 110 x 36

Power supply

LED

LED

LED

24V AC IN

FUSE 10A

POWER SUPPLY L2 L1

VOLT FREE VOLT FREE
PUMP OUTPUT BOILER OUTPUT NO COM NO COM NC

230V AC L

TR* 230V / 24V

N

The red LED indicates that the wiring centre is connected to the power supply.

Power supply for wiring centre is 24 V~, 50Hz. TR*- Power transformer230/24V AC

Please note: Recommended transformer power for 12 actuators is 30VA. Recommended transformer is T24-30W.

Fuse
Please note: Replacement of the fuse to be carried out only when the control box is disconnected from power supply (24 V ~).
Main fuse is located under the housing cover next to power supply terminals and secures the control box and the devices connected to it. Use ceramic tube slow blow 250 V ROHS fuses (5x20 mm) with nominal max current 10A. To replace fuse remove the fuse holder with a flat screwdriver and pull out the fuse.

Pump output (volt free)
The PUMP OUTPUT is a potential-free output (COM/NO) controlling a circulating pump in the heating system, with a maximum load of 6A. The output is short-circuited (the pump starts) always after 3 minutes from the receipt of the heating signal from any controller connected to this control box. The output is switched off (the pump stops) when none of the controllers sends the heating signal.

PUMP OUTPUT
NO COM
max 6A
L AC 230V N PE

NO COM PUMP OUTPUT

When the Pump/Valve control output is activated, the pump status LED shows
a constant green light.

Boiler control output (volt free)
The boiler control output is supported by a relay with voltage-free contacts (NO / COM / NC output). The boiler must be connected to the COM-NO or COM-NC contacts. It is a typical two-state relay. In most cases, the NC terminal is not used. If the thermostats connected to the wiring centre send a signal for heating, the BOILER output contacts activate the relay with a 3-minute delay, allowing the boiler to be turned on. The boiler is turned off immediately, when none of the zones sends a signal for heating.
VOLT FREE

BOILER OUTPUT
NO COM NC

NO COM NC BOILER OUTPUT

Boiler ON/OFF contacts (according to the boiler's manual)

BOILER

When the BOILER control output is activated, the boiler status LED shows
a constant green light.

Thermostats input connections
a - 24V thermostat connection (with COM / NO voltage-free contacts) b - Connecting a battery ON / OFF thermostat (with COM / NO voltage-free contacts)

a 24V AC THERMOSTAT
COM NO L2 L1

b BATTERY
THERMOSTAT
COM NO

INSTALLATION
1
Remove the top cover of the control box.

L2 L1 SL1 L2 L1 SL2 L2 L1 SL3 L2 L1 SL4 L2 L1 SL5 L2 L1 SL6 L2 L1 SL7 L2 L1 SL8 INPUT_1 INPUT_2 INPUT_3 INPUT_4 INPUT_5 INPUT_6 INPUT_7 INPUT_8

THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED

LED

LED

24V AC IN

OUTPUT_1 OUTPUT_2 OUTPUT_3 OUTPUT_4 OUTPUT_5 OUTPUT_6 OUTPUT_7 OUTPUT_8 FUSE 10A
L2 SL1 L2 SL1 L2 SL2 L2 SL2 L2 SL3 L2 SL3 L2 SL4 L2 SL4 L2 SL5 L2 SL5 L2 SL6 L2 SL6 L2 SL7 L2 SL7 L2 SL8 L2 SL8

POWER SUPPLY
L2 L1

L1, L2 24 V AC Power supply SL1 ... SL8 24V AC Control signal

VOLT FREE VOLT FREE
PUMP OUTPUT BOILER OUTPUT
NO COM NO COM NC

Actuators output connections (AC 24V)
Actuators wires should be plugged into the pluggable terminal blocks of the respective zones. Maximum current load for each zone is designed to handle up to 6 actuators with a power of 2W each. With more actuators in one zone, an additional relay should be used to make sure that actuators output will be not overloaded.

L2 L1 SL1 L2 L1 SL2 L2 L1 SL3 L2 L1 SL4 L2 L1 SL5 L2 L1 SL6 L2 L1 SL7 L2 L1 SL8 INPUT_1 INPUT_2 INPUT_3 INPUT_4 INPUT_5 INPUT_6 INPUT_7 INPUT_8

THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT THERMOSTAT

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED
ACTUATOR

LED

LED

LED

24V AC IN

OUTPUT_1 OUTPUT_2 OUTPUT_3 OUTPUT_4 OUTPUT_5 OUTPUT_6 OUTPUT_7 OUTPUT_8 FUSE 10A
L2 SL1 L2 SL1 L2 SL2 L2 SL2 L2 SL3 L2 SL3 L2 SL4 L2 SL4 L2 SL5 L2 SL5 L2 SL6 L2 SL6 L2 SL7 L2 SL7 L2 SL8 L2 SL8

POWER SUPPLY
L2 L1

VOLT FREE VOLT FREE
PUMP OUTPUT BOILER OUTPUT
NO COM NO COM NC

3
Connect the wires in accordance with the connection description. Refer to the sticker under the top cover.

2
Remove the appropriate piece of insulation from the wires.

5 mm Wires for boiler and battery thermostats: min. 2 x 0,5 mm2 max. 2 x 1,0 mm2

40 mm 5 mm

Wires for 24V thermostats: min. 3 x 0,5 mm2 max. 3 x 1,0 mm2

40 mm

Power supply for the tranformer (wiring
centre) and pump: min. 3 x 0,75 mm2 230 V max. 3 x 1,5 mm2 230 V

4
After making sure all wires are properly connected, mount the top cover and turn the wiring centre to the 24 V power supply -
the red "Power" diode will light up.

When the actuator has After applying 24V no power, it is closed. voltage, the actuator
will open.
Example based on E30NC-24 E30NC-24.



References

Adobe PDF Library 17.0 Adobe InDesign 19.5 (Windows)