KeepRite Refrigeration

Roundell Unit Coolers

High Temperature Applications (35 °F and Higher) Air Defrost

Electrical Power: 115/1/60, 208-230/1/60

Bulletin K30-R-PDI-13

Key Features:

Nomenclature Example: R 375 A

Description: KeepRite Roundell Unit Cooler

BTUH Capacity @ 1 °F TD (60Hz): e.g., 450 = 4500 @ 10 °F TD

Electrical Designation: A = 115/1/60, W = 208-230/1/60

Website: www.keepriterefrigeration.com

Contents

  • Nomenclature: Cover
  • Capacity Data: 2
  • Electrical Data: 2
  • Typical Field Wiring: 2
  • Dimensional & Physical Data: 3
  • Thermostatic Expansion Valve: 4
  • Installation Instructions: 5
  • Service Parts List: 6
  • Service Log: 6
  • Warranty: 7
  • Project Information: 7
  • "As Built" Service Parts: Back

Specifications

Capacity Data

MODEL No.10°F TDCAPACITY (BTUH) 12°F BTU/HR15°F BTU/HRAIR FLOW CFMREFR'G CHARGE R22* Lbs.
R 3753730448056007701.25
R 4854880586073207701.77
R 59560507260908012802.10
R 775790094801185013003.02
R 9058900106801335013803.28
R 102510200122401530020253.77
R 130512800153601920020004.81
R 205020400244803060040507.50

* R-22 at 30 °F S.S.T. with coil 30% full

Electrical Data

115/1/60 (Shaded Pole Motor)

MODELQTY.H.P.RPMTOTAL F.L.A.M.C.A.M.O.P.
R37511/2015501.6215
R48511/2015501.6215
R59511/2015501.6215
R77511/1510502.12.6315
R90511/1510502.12.6315
R102511/1510502.12.6315
R130511/1510502.12.6315
R205021/1510504.24.7315

115/1/60 (Optional P.S.C. Motor)

MODELQTY.H.P.RPMTOTAL F.L.A.M.C.A.M.O.P.
R37511/2016000.60.7515
R48511/2016000.60.7515
R59511/2016000.60.7515
R77511/1510601.321.6515
R90511/1510601.321.6515
R102511/1510601.321.6515
R130511/1510601.321.6515
R205021/1510602.642.9715

208-230/1/60 (Optional P.S.C. Motor)

MODELQTY.H.P.RPMTOTAL F.L.A.M.C.A.M.O.P.
R37511/2016000.290.3615
R48511/2016000.290.3615
R59511/2016000.290.3615
R77511/1510600.540.6815
R90511/1510600.540.6815
R102511/1510600.540.6815
R130511/1510600.540.6815
R205021/1510601.081.2215

M.C.A. = Minimum Circuit Ampacity

M.O.P. = Maximum Overcurrent Protection

Typical Field Wiring

Diagram Description: A simplified wiring diagram showing supply voltage connected to two EVAP fans. A ground connection is also shown. The R2050 model includes a second fan motor.

Dimensional and Physical Data

Diagram Description: Illustrates the dimensions for single-fan (Models R375 to R1305) and double-fan (Model R2050) unit coolers. Shows air flow direction, suction, external equalizer connection (1/4" O.D.), and drain connection (5/8" O.D.). Notes a 7/16" diameter hole for mounting and a 7/16" E-slot.

MODELA (in)B (in)C (in)D (in)E (in)F (in)G (in)Suct. Conn. O.D. (in/mm)Shipping Weight (Lbs./Kg.)
R 3758 1/833 1/420 3/4216 3/434 3/44 3/45/8 / 15.972 / 32.7
R 485(206.4)(844.6)(527.0)(50.8)(425.5)(882.7)(120.7)
R 59511 1/839 1/423 3/42 1/419 3/840 3/45 1/85/8 / 15.976 / 34.5
R 775(282.6)(997.0)(603.3)(57.2)(492.1)(1035.0)(130.2)
R 90511 1/842 1/425 1/42 1/220 3/843 3/45 5/87/8 / 22.2104 / 47.2
(282.6)(1073.1)(641.4)(63.5)(417.5)(1111.3)(142.9)
R 102512 5/842 1/425 1/42 1/220 3/843 3/45 5/87/8 / 22.2108 / 49
(320.7)(1073.1)(641.4)(63.5)(417.5)(1111.3)(142.9)
R 130512 5/87425 1/42 1/220 3/875 1/25 5/87/8 / 22.2114 / 51.2
(320.7)(1879.6)(641.4)(63.5)(417.5)(1917.5)(142.9)
R 205012 5/87425 1/42 1/220 3/875 1/25 5/81 1/8 / 28.6187 / 84.8
(320.7)(1879.6)(641.4)(63.5)(417.5)(1917.5)(142.9)

Notes:

  • 5/8" (15.9 mm) O.D. Drain connection on all models.
  • 1/2" (12.7 mm) Flare TX valve connection on all models R375 thru T775.
  • 1/2" (12.7 mm) Sweat TX Valve connection on models R905 thru R2050.

Thermostatic Expansion Valve Selection Chart

Chart for +35°F Rooms and Up, Air Defrost

MODELTD °FCAPACITY BTUHSPORLAN VALVE MODELALCO VALVE MODEL
REFRIGERANT R22REFRIGERANT R502/404A/507REFRIGERANT R12/R134aREFRIGERANT R22REFRIGERANT R502/404A/507REFRIGERANT R134a
R375103,730EGVE-1/3-CEGSE-1/4-SEEGJE-1/6-JCHFES-1/4-HCHFES-1/4-SCHFES-1/2-MC
124,480EGVE-1/3-CEGSE-1/2-SEEGJE-1/4-JCHFES-1/2-HCHFES-1/4-SCHFES-1/2-MC
155,600EGVE-1/2-VCEGSE-1/2-SEEGJE-1/2-JCHFES-1/2-HCHFES-1/4-SCHFES-1/2-MC
R485104,880EGVE-1/2-VCEGSE-1/2-SEEGJE-1/2-JCHFES-1/2-HCHFES-1/4-SCHFES-1/2-MC
125.860EGVE-1/2-VCEGSE-1/2-SEEGJE-1/2-JCHFES-1/2-HCHFES-1/2-SCHFES-3/4-MC
157,320EGVE-3/4-VCEGSE-1/2-SEEGJE-1/2-JCHFES-1/2-HCHFES-1/2-SCHFES-3/4-MC
R595106,050EGVE-1/2-VCEGSE-1/2-SEEGJE-1/2-JCHFES-1/2-HCHFES-1/2-SCHFES-3/4-MC
127,260EGVE-3/4-VCEGSE-1/2-SEEGJE-1/2-JCHFES-1/2-HCHFES-1/2-SCHFES-3/4-MC
159,080EGVE-3/4-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1/2-SCHFES-3/4-MC
R775107,900EGVE 3/4-VCEGSE-1/2-SEEGJE-1/2-JCHFES-1/2-HCHFES-1/2-SCHFES-3/4-MC
129480EGVE 3/4-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1-SCHFES-1-MC
1511,850EGVE-1-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1-SCHFES-1-MC
R905108,900EGVE-3/4-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1-SCHFES-3/4-MC
1210,680EGVE-1-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1-SCHFES-1-MC
1513,350EGVE-1-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1-SCHFES-1-MC
R10251010,200EGVE-3/4-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1-SCHFES-1-MC
1212,240EGVE-1-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1-SCHFES-1-MC
1515,300EGVE-1 1/2-VCEGSE-1-SEEGJE-1-JCHFES-1 1/2-HCHFES-1 1/4-SCHFES-1 1/2-MC
R13051012,800EGVE-1-VCEGSE-1-SEEGJE-1-JCHFES-1-HCHFES-1 1/4-SCHFES-1-MC
1215,360EGVE-1 1/2-VCEGSE-1-SEEGJE-1-JCHFES-1 1/2-HCHFES-1 1/4-SCHFES-1 1/2-MC
1519,200EGVE-1 1/2-VCEGSE-1 1/2-SEEGJE-1 1/2-JCHFES-1 1/2-HCHFES-1 1/2-SCHFES-1 3/4-MC
R20501020,400EGVE-1 1/2-VCEGSE-1 1/2-SEEGJE-1 1/2-JCHFES-1 1/2-HCHFES-1 1/2-SCHFES-1 3/4-MC
1224,480EGVE-2-VCEGSE-2-SEEGJE-1 1/2-JCHFES-2-HCHFES-2-SCHFES-2 1/2-MC
1530,600EGVE-3-VCEGSE-3-SEEGJE-2-JCHFES-2 1/2-HCHFES-2-SCHFES-2 1/2-MC

Selections based on 100° Liquid

Application

High Temp Unit Coolers are designed for use with R12, R22, R134a, R404A, R407A/B/C, R507 or R502 refrigerants.

At room temperatures above 34°F and evaporating temperatures no lower than 27°F, the air flowing through the coil will accomplish defrost. Temperatures of 34°F and below (to -40°F) require positive defrosting (either Electric or Hot Gas).

The coil must not be exposed to any abnormal atmospheric or acidic environments, which may cause corrosion or coil failure. Consult manufacturer for optional baked-on phenolic protective coatings.

Installation

Installation and start-up should only be performed by qualified refrigeration mechanics, in accordance with all applicable codes, ordinances, and local by-laws.

Inspection

Inspect all equipment before unpacking for visible signs of damage or loss. Check shipping list against material received to ensure shipment is complete.

Important: Consignees must make any necessary claims against the transportation company for shipping damage or missing parts. Claims for concealed damage should also be filed with the carrier.

Verify electrical characteristics match order and available power.

Save all shipping papers, tags, and instruction sheets.

Location

Select unit location for uniform air distribution. Ensure air is not blown directly out through opened doors and that product does not obstruct air circulation.

Note: Units draw air through the fan and discharge air from the coil side.

Provide minimum 2" (50mm) clearance adjacent to walls for hinged drain pan servicing. Channel type hangers are provided; rear hangers are slotted for installation.

Mounting

Mounting brackets with 7/16" dia. holes are provided for flush ceiling mounting. Ensure the ceiling is level for proper drain pan slope during defrost.

Drain Line

Run drain line from connection, sloping at least 4" per foot. A trap outside the room prevents warm air entry. Connect to proper drainage facilities complying with local regulations.

Ensure drain pan has sufficient slope for proper drainage and to prevent ice build-up/blockage.

Piping

Refrigerant line sizes are important and may differ from coil connections. Consult "Recommended refrigerant line sizes" charts or engineering manuals if unsure.

Wiring

Wire system according to governing standards and local codes. Refer to page 2 for wiring diagrams. Electrical wiring must be sized according to minimum ampacity rating.

System Check

Before Start-Up:

  • Verify all wiring complies with local codes.
  • Ensure refrigerant lines are properly sized.
  • Off-cycle defrost systems should include a liquid line solenoid valve.
  • Confirm thorough evacuation and dehydration have been performed.
  • Ensure suction, discharge, and receiver service valves are open.
  • System should include a liquid line drier moisture indicator and suction filter.
  • Pour water into the drain pan to check drainage and seal the trap.

After Start-Up:

  • Check compressor oil level for correct charge.
  • Verify expansion valve is set correctly for superheat.
  • Note that heavy moisture loads are common during initial system start-up.
  • Check evaporator fan blade rotation.

Maintenance

Periodically inspect the unit for dirt or build-up on the fin surface. Clean with a soft whisk or brush if necessary.

Service Parts List

MODEL115V S.P.115V P.S.C.208-230 P.S.C.FAN BLADEFAN GUARD
R37517062110625331062534282711043043
R48517062110625331062534282711043043
R5951706211062533106253428270170512-003
R7751706201062541106254228272170512-003
R9051706201062541106254228269170512-003
R10251706201062541106254228269170512-003
R13051706201062541106254228269170512-003
R20501706201062541106254228269170512-003

Service Log

Placeholder for service records.

Warranty

Finished Goods Warranty

Terms and conditions for products manufactured by National Refrigeration.

General Warranty Policy

Company warrants Products and Service Parts against defects in material or workmanship for one (1) year from installation or eighteen (18) months from shipment, whichever occurs first.

Replacement parts are warranted for the balance of the original warranty. Proof of installation date is required.

Labor, material, refrigerant, transportation, and other charges are the owner's responsibility.

Warranty may be transferred to a subsequent owner.

This Warranty Does Not Cover

  • Damages from accident, abuse, negligence, misuse, riot, fire, flood, Acts of God.
  • Operation in corrosive atmosphere.
  • Unauthorized alteration or repair affecting reliability or performance.
  • Improper matching or application of product or components.
  • Failure to provide routine and proper maintenance or service.
  • Expenses for erecting, disconnecting, or dismantling.
  • Parts used in normal maintenance (filters, belts).
  • Products no longer at the original installation site.
  • Products installed or operated not in accordance with printed instructions, local codes, or good trade practices.
  • Products lost or stolen.

No one is authorized to change this warranty or create other obligations. Company is not liable for incidental, consequential, or special damages.

Additional warranty provisions are in addition to statutory warranties and rights.

Project Information

SystemModel NumberDate of Start-Up
RefrigerantService ContractorPhone
Electrical SupplyFax

"As Built" Service Parts List

Placeholder for "As Built" service parts label to be attached here.

PDF preview unavailable. Download the PDF instead.

Keeprite K Product Data Acrobat PDFWriter 4.0 for Windows

Related Documents

Preview KeepRite KCL Air Cooled Condensers Product Data and Installation Manual
Comprehensive product data and installation guide for KeepRite KCL Air Cooled Condensers. This manual covers features, options, capacity data, electrical specifications, and general specifications for various models and refrigerants.
Preview KeepRite Roto Line Refrigerated Display Cases | MGRTW-130L-1, MGRTW-160L-2
Discover the KeepRite Roto Line of refrigerated display cases, including models MGRTW-130L-1 and MGRTW-160L-2. This document provides specifications and details about METALGAS, S.R.L., the distributor.
Preview KeepRite N4A4S Series Single-Stage Air Conditioner Product Specifications
Comprehensive product specifications for the KeepRite N4A4S series single-stage air conditioners, featuring R-410A refrigerant. Includes detailed information on features, benefits, standard features, model nomenclature, physical data, refrigerant piping limitations, charging adjustments, long line applications, vapor line sizing, accessories, electrical data, sound power levels, cooling capacities, dimensions, clearances, and guide specifications.
Preview KeepRite Vineras de Mesa: Modelos MGJC38A, MGJC38B, MGJC38C | METALGAS S.R.L.
Descubra las vineras de mesa KeepRite de METALGAS S.R.L., incluyendo los modelos MGJC38A, MGJC38B y MGJC38C. Conozca sus especificaciones de capacidad, dimensiones y voltaje para su negocio.
Preview KeepRite Evaporator Coils: Energy-Efficient HVAC Solutions
Explore KeepRite's advanced aluminum evaporator coils, featuring R-454B refrigerant, V-shaped coil design, and durable construction for enhanced HVAC performance and efficiency. Learn about benefits, models, and limited warranty.
Preview KeepRite KPCOROLLA Series Juice Dispensers - Product Overview
Discover the KeepRite KPCOROLLA series of juice dispensers, featuring durable polycarbonate containers, quiet hermetic compressors, digital controls, and stainless steel fronts. Ideal for commercial use.
Preview KeepRite "C" Generation Condensing Units - Price List and Specifications
This document provides the price list and specifications for KeepRite's "C" Generation of Indoor and Outdoor Air Cooled Condensing Units, including KEH, KEZ, and KES lines. It details model nomenclature, standard features, available options, and pricing for various configurations.
Preview KeepRite TSTAT0101SC Thermostat: More Than Just a Thermostat
Discover the advanced features of the KeepRite TSTAT0101SC wall control unit, offering 12 ways more functionality than a standard thermostat. Learn about its easy installation, enhanced serviceability, and user-friendly interface for both consumers and contractors.