PR electronics 5332 2-Wire Programmable RTD Transmitter

Model: 5332

Document Type: Product Manual

Manufacturer: PR electronics

Introduction

With innovative, patented technologies, PR electronics makes signal processing smarter and simpler. Our product range covers six product areas, offering a wide spectrum of analog and digital devices suitable for over a thousand applications in industrial and factory automation. All our products meet or exceed the strictest industry standards, ensuring reliability even in the toughest environments. All products come with a 5-year warranty.

6 Product Pillars Meeting Your Needs

Outstanding individually, unbeatable in combination.

Temperature Measurement

Our range of temperature converters and sensors provides the highest possible signal integrity from the measurement point to your control system. You can convert industrial process temperature signals to analog, bus-based, or digital communication with a highly reliable point-to-point solution featuring fast response time, automatic self-calibration, sensor error detection, low deviation, and excellent EMC performance in all environments.

I.S. Interface (Intrinsically Safe)

We deliver the safest signal converters by validating our products against the most demanding safety standards. Through our pursuit of innovation, we have achieved groundbreaking success in developing Ex interfaces with full SIL 2 approval, which are both effective and cost-saving. Our comprehensive range of analog and digital isolators with built-in safety features offer multifunctional inputs and outputs, making PR an easily implemented standard for facilities. Our backplanes further simplify installations and enable seamless integration with DCS standard systems.

Communication Interface

We offer affordable, easy-to-use, future-proof communication interfaces that can communicate with your installed PR product base. All interfaces are detachable, feature a built-in display for viewing process values and diagnostics, and can be configured using pushbuttons. Product-specific functionality includes communication via Modbus and Bluetooth, and remote access using our PPS application (PR Process Supervisor), available for iOS and Android.

Multifunctionality

Our unique range of single units that cover multiple applications can easily be installed as a facility standard. By providing a single variant that works with a large number of applications, we reduce installation and training time, and significantly simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low power consumption, immunity to electrical interference, and easy programming.

Isolation

Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology for exceptional performance and EMC immunity for dedicated applications with very low total cost of ownership. They can be stacked vertically or horizontally without air gaps between units.

Display

Our display range is characterized by flexibility and stability. The units meet almost all requirements for displaying process signals and feature universal input and power supply. They enable real-time measurement of process values across a wide range of areas and are designed to provide user-friendly and reliable information, even in demanding environments.

2-Wire Programmable RTD Transmitter 5332 Features

Applications

Linearized temperature measurement of Pt100...Pt1000 or Ni100...Ni1000 sensors. Conversion of linear resistance variation to a standard analog current signal, e.g., from valves or ohmic level sensors.

Technical Specifications

Environmental Conditions

Operating temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-condensing)
Degree of protection, housing / terminals IP68 / IP00

Mechanical Specifications

Dimensions Ø 44 x 20.2 mm
Weight 50 g
Max. wire cross-section 1 x 1.5 mm² twisted pair
Screw terminals, max. tightening torque 0.4 Nm

General Specifications

Supply voltage, DC (5332N and 5332A) 7.2...35 VDC
Supply voltage, DC (5332D) 7.2...30 VDC
Power loss (5332N and 5332A) 25 mW...0.8 W
Power loss (5332D) 25 mW...0.7 W
Voltage drop 7.2 VDC
Warm-up time 5 min.
Startup to stable output 4.5 s
Programming Loop Link
Signal-to-noise ratio > 60 dB
Response time (programmable) 1...60 s
EEPROM error check < 3.5 s
Signal dynamics, input 20 bit
Signal dynamics, output 16 bit
Effect of supply voltage variation < 0.005% of span / VDC

Accuracy

The greatest value of the general and basic values:

General Values

Input Type Absolute Accuracy Temperature Coefficient
All ≤ ±0.05% of range ≤ ±0.01% of range/°C

Basic Values

Input Type Basic Accuracy Temperature Coefficient
RTD ≤ ±0.2°C ≤ ±0.01°C/°C
Lin. R ≤ ±0.1 Ω ≤ ±10 mΩ / °C

EMC Immunity

EMC immunity < ±0.5% of range
Extended EMC immunity: NAMUR NE 21, criterion A, burst < ±1% of range

Input Specifications

RTD and Linear Resistance Input

RTD Type Min. Value Max. Value Min. Span Standard
Pt100...Pt1000 -200°C +850°C 25°C IEC 60751
Ni100...Ni1000 -60°C +250°C 25°C DIN 43760
Linear Resistance 0 Ω 5000 Ω 30 Ω -
Max. offset 50% of selected max. value
Cable resistance per wire (max.) 5 Ω
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/ 4-wire) < 0.002 Ω/Ω
Sensor error detection Yes

Output Specifications

Current Output

Signal range 4...20 mA
Min. signal range 16 mA
Update time 440 ms
Load resistance ≤ (Vsupply - 7.2) / 0.023 [Ω]
Load stability < ±0.01% of span / 100 Ω

Sensor Error Detection

Programmable 3.5...23 mA
NAMUR NE43 Upscale 23 mA
NAMUR NE43 Downscale 3.5 mA

Span = Selected range

Compliant Standards

Connections and Diagrams

Input Connections

Diagrams illustrate various RTD and Resistance input wiring configurations (2, 3, and 4-wire).

Output Connection

Diagram shows a 2-wire installation for the 4-20 mA output signal, with terminals 1 (+) and 2 (-).

Block Diagram

The block diagram illustrates the internal components of the 5332 transmitter, including input signal conditioning (MUX, PGA, A/D converter), CPU, EEPROM for configuration storage, Digital-to-Analog (D/A) converter for the output signal, communication interface, and power supply input (7.2-35 VDC). The output is a 4-20 mA signal.

Programming

Loop Link is a communication interface required for programming the 5332. Refer to the description below and the help functions in PReset for programming details. Loop Link is not approved for communication with modules installed in hazardous (Ex) areas.

Ordering: Loop Link

Diagram shows Loop Link USB interface connecting to the 5332 transmitter for online programming, with wire color indications (Red, Black, Yellow, Green).

Installation Drawings and Certifications

ATEX Installation Drawings

ATEX Installation Drawing 5332A (QA02-V2R0)

For safe installation of 5332A, follow these guidelines. Installation must be performed by qualified personnel familiar with national and international laws, directives, and standards. The year of manufacture can be determined from the first two digits of the serial number.

ATEX Certificate: DEKRA 20ATEX0096 X

Marking: II 3 G Ex nA [ic] IIC T6...T4 Gc, II 3 G Ex ec [ic] IIC T6...T4 Gc, II 3 G Ex ic IIC T6...T4 Gc, II 3 D Ex ic IIIC Dc

Standards: EN 60079-0: 2018, EN 60079-11: 2012, EN 60079-15: 2010, EN 60079-7:2015 +A1: 2018

Terminal 3,4,5,6 (Ex ic IIC, Ex ic IIIC): Uo: 9.6 V, Io: 25 mA, Po: 60 mW, Lo: 33 mH, Co: 2.4 µF

Terminal 1,2 (Ex ic IIC, Ex ic IIIC): Ui = 35 V, Ii = 110 mA, Ci = 1 nF, Li = 10 µH

Terminal 1,2 (Ex ic IIC, Ex ic IIIC): Ui = 24 V, Ii = 260 mA, Ci = 1 nF, Li = 10 µH

Terminal 1,2 (Ex nA, Ex ec): Umax ≤ 35 VDC or Umax ≤ 24 VDC

Ambient Temperature Range (Ex ic IIC, Ex ic IIIC):

Temperature ClassUi=35 VUi=24 V
T6-40°C to +54°C-40°C to +63°C
T5-40°C to +69°C-40°C to +78°C
T4-40°C to +85°C-40°C to +85°C

Ambient Temperature Range (Ex ec, Ex nA):

Temperature ClassVmax=35 VVmax=24 V
T6-40°C to +43°C-40°C to +55°C
T5-40°C to +85°C-40°C to +85°C
T4-40°C to +85°C-40°C to +85°C

ATEX Installation Drawing 5332D (QA01-V2R0)

For safe installation of 5332D, follow these guidelines. Installation must be performed by qualified personnel familiar with national and international laws, directives, and standards. The year of manufacture can be determined from the first two digits of the serial number.

ATEX Certificate: DEKRA 20ATEX0095 X

Marking: II 1 G Ex ia IIC T6...T4 Ga, II 2 D Ex ia IIIC Db, I M1 Ex ia I Ma

Standards: EN 60079-0: 2018, EN 60079-11: 2012

Hazardous Area: Zone 0, 1, 2, 21, 22

Terminal: 3,4,5,6: Uo: 9.6 VDC, Io: 25 mA, Po: 60 mW, Lo: 33 mH, Co: 2.4 µF

Terminal: 1,2: Ui: 30 VDC, Ii: 120 mA, Pi: 0.84 W or 0.75 W, Li: 10 µH, Ci: 1.0 nF

Diagram shows connection between Hazardous Area (Terminals 3,4,5,6) and Non Hazardous Area (Terminal 1,2) via a Barrier.

Ambient Temperature Range:

Temperature ClassPi: 0.84 WPi: 0.75 W
T6-40°C to +47°C-40°C to +50°C
T5-40°C to +62°C-40°C to +65°C
T4-40°C to +85°C-40°C to +85°C

IECEx Installation Drawings

IECEx Installation Drawing 5332A

For safe installation of 5332A, the following must be observed. The module shall only be installed by qualified personnel familiar with national and international laws, directives, and standards. Year of manufacture from the first two digits of the serial number.

Certificate: IECEx DEK 20.0059X

Marking: Ex nA [ic] IIC T6 ... T4 Gc, Ex ec [ic] IIC T6 ... T4 Gc, Ex ic IIC T6 ... T4 Gc, Ex ic IIIC Dc

Standards: IEC 60079-0: 2017, IEC 60079-11: 2011, IEC 60079-15: 2010, IEC 60079-7:2017

Terminal 3,4,5,6 (Ex ic IIC, Ex ic IIIC): Uo: 9.6 V, Io: 25 mA, Po: 60 mW, Lo: 33 mH, Co: 2.4 µF

Terminal 1,2 (Ex ic IIC, Ex ic IIIC): Ui = 35 V, Ii = 110 mA, Ci = 1 nF, Li = 10 µH

Terminal 1,2 (Ex ic IIC, Ex ic IIIC): Ui = 24 V, Ii = 260 mA, Ci = 1 nF, Li = 10 µH

Terminal 1,2 (Ex nA, Ex ec): Umax ≤ 35 VDC or Umax ≤ 24 VDC

Ambient Temperature Range (Ex ic IIC, Ex ic IIIC):

Temperature ClassUi=35 VUi=24 V
T6-40°C to +54°C-40°C to +63°C
T5-40°C to +69°C-40°C to +78°C
T4-40°C to +85°C-40°C to +85°C

Ambient Temperature Range (Ex ec, Ex nA):

Temperature ClassVmax=35 VVmax=24 V
T6-40°C to +43°C-40°C to +55°C
T5-40°C to +85°C-40°C to +85°C
T4-40°C to +85°C-40°C to +85°C

IECEx Installation Drawing 5332D

For safe installation of 5332D, the following must be observed. The module shall only be installed by qualified personnel familiar with national and international laws, directives, and standards. Year of manufacture from the first two digits of the serial number.

Certificate: IECEx DEK 20.0059X

Marking: Ex ia IIC T6...T4 Ga, Ex ia IIIC Db, Ex ia I Ma

Standards: IEC 60079-0: 2017, IEC 60079-11: 2011

Hazardous Area: Zone 0, 1, 2, 21, 22

Terminal: 3,4,5,6: Uo: 9.6 VDC, Io: 25 mA, Po: 60 mW, Lo: 33 mH, Co: 2.4 µF

Terminal: 1,2: Ui: 30 VDC, Ii: 120 mA, Pi: 0.84 W or 0.75 W, Li: 10 µH, Ci: 1.0 nF

FM Installation Drawings

Model 5331D, 5332D, 5333D and 5343B

Hazardous (Classified) Location: Class I, Division 1, Groups A,B,C,D T4..T6; Class I, Zone 0, AEx ia IIC T4..T6

Ambient temperature limits: T4: -40 to +85 deg. Celcius; T6: -40 to +60 deg. Celcius

Terminal 1, 2: Vmax or Ui: 30 V, Imax or Ii: 120 mA, Pmax or Pi: 0.84 W, Ci: 1 nF, Li:10 uH

Diagram shows connection between Hazardous Location and Non Hazardous Location via an Associated Apparatus or Barrier with entity parameters (UM < 250V, Voc or Uo < Vmax or Ui, etc.).

Model 5335D, 5337D

Hazardous (Classified) Location: Class I, Division 1, Groups A,B,C,D T4..T6; Class I, Zone 0, AEx ia IIC T4..T6

Ambient temperature limits: T4: -40 to +85 deg. Celcius; T6: -40 to +60 deg. Celcius

Terminal 1, 2: Vmax or Ui: 30 V, Imax or Ii: 120 mA, Pmax or Pi: 0.84 W, Ci: 1 nF, Li:10 uH

Terminal 3,4,5,6: Vt or Uo: 9.6 V, It or Io: 28 mA, Pt or Po: 67.2 mW, Ca or Co: 3.5 uF, La or Lo: 35 mH

Diagram shows connection between Hazardous Location and Non Hazardous Location via an Associated Apparatus or Barrier with entity parameters.

Entity Concept & NI Field Circuit Parameters

The Transmitter must be installed according to National Electrical Code (ANSI-NFPA 70). Equipment approved for intrinsic safety may be connected to barriers based on the ENTITY CONCEPT. The intrinsically safe devices must not be a source of power. The maximum voltage, current, and power the device can receive must be equal to or greater than what the barrier delivers. Capacitance (Ci) and inductance (Li) of the device plus wiring must be less than the barrier's capacitance (Ca) and inductance (La).

NI Field Circuit Parameters (Models 5331D, 5332D, 5333D, 5335D, 5337D and 5343B):

Hazardous (Classified) Location: Class I, Division 2, Groups A,B,C,D T4..T6; Class I, Zone 2, IIC T4..T6

Ambient temperature limits: T4: -40 to +85 deg. Celcius; T6: -40 to +60 deg. Celcius

Terminal 1,2: Vmax: 35 V, Ci: 1.0 nF, Li:10 uH

Diagram shows connection between Hazardous Location and Non Hazardous Location via an Associated Apparatus or Barrier.

CSA Installation Drawings

CSA Installation Drawing 5331A and 5332A (5331QC02)

For safe installation of 5331A and 5332A, follow these guidelines. Installation must be performed by qualified personnel familiar with national and international laws, directives, and standards.

Marking: Class I, Division 2, Group A,B,C,D T6...T4; Ex nA[ic] IIC T6...T4; Class I Zone 2 AEx nA[ic] IIC T6...T4

Hazardous Area: CL I, Div 2, GP ABCD; CL I, Zone 2, IIC

Temperature Limits: T4: -40°C to 85 °C; T6: -40°C to 60 °C

Terminal: 3,4,5,6: Uo: 9.6 VDC, Io: 25 mA, Po: 60 mW, Lo: 33 mH, Co: 2.4µF

Terminal: 1-2: Functional Ratings: U nominal ≤ 35 VDC; I nominal ≤ 3.5 - 23 mA

Diagram shows connection to Supply.

NI Installation Instructions: Transmitter must be installed in an enclosure providing IP54 protection (IEC60529). Avoid electrostatic charging. Use supply wires rated at least 5 K above ambient temperature. Supply from Class 2 Power Supply.

Warning: Substitution of components may impair suitability for Class I, Division 2.

Warning: Do not disconnect equipment unless power is switched off or area is known to be safe.

Non Incendive Field Wiring Installation: Concept allows interconnection of Nonincendive Field wiring Apparatus with Associated Apparatus using wiring methods permitted for unclassified locations (Voc < Vmax, Ca ≥ Ci + Ccable, La ≥ Li + Lcable).

CSA Installation Drawing 5332QC01

Hazardous area: T4: -40 ≤ Ta ≤ 85°C; T6: -40 ≤ Ta ≤ 60°C

Terminal: 3,4,5,6: Connect only to passive, or non-energy storing devices such as RTD's.

Terminal: 1,2: Ui: 30 VDC, Ii: 120 mA, Pi: 0.84 W, Li: 10 µH, Ci: 1.0 nF

Diagram shows connection to a Barrier.

Certifications: CLASS 2258 04, CLASS 2258 84 (Intrinsically Safe Entity)

Standards: Class I, Division 1, Groups A, B, C and D T6...T4; Ex ia IIC T6...T4 Ga; Class I, Zone 0, AEx ia IIC Ga

Warning: Substitution of components may impair intrinsic safety.

Transmitters must be installed in a suitable enclosure to meet installation codes (CEC or NEC).

INMETRO Installation Drawings (Portuguese)

Note: The following sections are in Portuguese. Key technical parameters are transcribed below.

Desenho de Instalação INMETRO (5332A)

For safe installation of 5332A, observe the following. Installation by qualified personnel familiar with national and international laws, directives, and standards. Year of manufacture from first two digits of serial number.

Certificate: DEKRA 23.0009 X

Markings: Ex ec [ic] IIC T4..T6 Gc, Ex ic IIC T4..T6 Gc, Ex ic IIIC Dc

Standards: ABNT NBR IEC 60079-0:2020, ABNT NBR IEC 60079-7:2018, ABNT NBR IEC 60079-11:2013

Terminals 3,4,5,6 (Ex ic IIC, Ex ic IIIC): Uo: 9.6 V, Io: 25 mA, Po: 60 mW, Lo: 33 mH, Co: 2.4 µF

Terminals 1,2 (Ex ic IIC, Ex ic IIIC): Ui = 35 V, Ii = 110 mA, Ci = 1 nF, Li = 10 µH

Terminals 1,2 (Ex ic IIC, Ex ic IIIC): Ui = 24 V, Ii = 260 mA, Ci = 1 nF, Li = 10 µH

Terminals 1,2 (Ex ec): Umax ≤ 35 Vdc or Umax ≤ 24 Vdc

Ambient Temperature Range (Ex ic IIC, Ex ic IIIC):

Temperature ClassUi=35VUi=24V
T6-40 °C to +54 °C-40 °C to +63 °C
T5-40 °C to +69 °C-40 °C to +78 °C
T4-40 °C to +85 °C-40 °C to +85 °C

Ambient Temperature Range (Ex ec):

Temperature ClassUmax=35VUmax=24V
T6-40 °C to +43 °C-40 °C to +55 °C
T5-40 °C to +85 °C-40 °C to +85 °C
T4-40 °C to +85 °C-40 °C to +85 °C

Notas de Instalação (Portuguese)

Avoid electrostatic charges on non-metallic enclosures. For explosive atmospheres requiring Gc protection level (Ex ic type), mount in an enclosure with at least IP20 (ABNT NBR IEC 60529). For Dc protection level, use a separately certified enclosure with at least IP5X (ABNT NBR IEC 60079-0). Surface temperature is +20 K above ambient. Ambient temp range: -40°C to +85°C. For Gc protection level (Ex ec type), use a separately certified enclosure with at least IP54 (ABNT NBR IEC 60079-0). Use only in areas with pollution degree not exceeding 2 (IEC 60664-1).

Desenho de Instalação INMETRO (5332D)

For safe installation of 5332D, observe the following. Installation by qualified personnel familiar with national and international laws, directives, and standards. Year of manufacture from first two digits of serial number.

Certificate: DEKRA 23.0009 X

Markings: Ex ia IIC T6...T4 Ga, Ex ia IIIC Db, Ex ia I Ma

Standards: ABNT NBR IEC 60079-0:2020, ABNT NBR IEC 60079-11:2013

Classified Areas: Zone 0, 1, 2, 21, 22

Terminals 3,4,5,6: Uo: 9.6 VDC, Io: 25 mA, Po: 60 mW, Lo: 33 mH, Co: 2.4µF

Terminals: 1,2: Ui: 30 VDC, Ii: 120 mA, Pi: 0.84 W or 0.75W, Li: 10µH, Ci: 1.0nF

Diagram shows connection to a Barrier.

Ambient Temperature Range:

Temperature ClassPi: 0.84WPi: 0.75W
T6-40 °C to +47 °C-40 °C to +50 °C
T5-40 °C to +62 °C-40 °C to +65 °C
T4-40 °C to +85 °C-40 °C to +85 °C

Notas de instalação (Portuguese)

Avoid electrostatic charges on non-metallic enclosures. For explosive atmospheres requiring Ga protection level, mount in an enclosure with at least IP20 (ABNT NBR IEC 60529). If enclosure is aluminum, exclude ignition sources from impact/friction. For Db protection level, use a separately certified enclosure with at least IP5X (ABNT NBR IEC 60079-0). Surface temp +20 K above ambient. Ambient temp range: -40°C to +85°C. For Ma protection level, mount in an enclosure with at least IP54 (ABNT NBR IEC 60529). Use suitable cable entries/blanking elements. For ambient temp ≥ 60°C, use heat-resistant cables rated at least 20 K above ambient.

General Installation Notes

If the enclosure is made of non-metallic plastic materials, electrostatic charges on the transmitter enclosure shall be avoided.

If the transmitter is installed in an explosive atmosphere requiring equipment protection level Gc and applied in type of protection Ex ic, it shall be mounted in an enclosure providing a degree of protection of at least IP20 according to IEC 60529, and that is suitable for the application and correctly installed.

If the transmitter is installed in an explosive atmosphere requiring equipment protection level Dc, it shall be mounted in a separately certified enclosure that provides a degree of protection of at least IP5X according to IEC 60079-0, and that is suitable for the application and correctly installed. The surface temperature of the outer enclosure is +20 K above the ambient temperature, determined without a dust layer. Ambient temperature range: -40°C to +85°C.

If the transmitter is installed in an explosive atmosphere requiring equipment protection level Gc and applied in type of protection Ex nA or Ex ec, it shall be mounted in a separately certified enclosure that provides a degree of protection of at least IP54 according to IEC 60079-0, and that is suitable for the application and correctly installed.

If the transmitter is installed in an explosive atmosphere requiring equipment protection level Gc and applied in type of protection Ex nA or Ex ec, the equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC 60664-1.

Document History

Rev. IDDateNotes
1001845First version of the product.
1012007EAC, EAC Ex and INMETRO approvals added.
1022145CSA installation drawing for 5332A added.
1032202ATEX and IECEx approvals updated - Ex na changed to Ex ec.
1042245CSA installation drawings updated.
1052411UKCA added.
1052411INMETRO approval updated - Ex na changed to Ex ec.

PR electronics - Global Presence

PR electronics is the leading technology company for safer, more reliable, and more efficient industrial process control. Since 1974, we have focused on perfecting our core competence: innovative high-precision technology with low energy consumption. Through this competence, we continue to set new standards for products that communicate, monitor, and connect our customers' process measurement points with their process control systems.

Our innovative, patented technology stems from our extensive research and development resources and our deep insight into our customers' needs and processes. We are guided by principles of simplicity, focus, courage, and skill, and we help some of the world's foremost companies achieve SMARTER PERFORMANCE.

We are close to you around the world. Our trusted red boxes are supported wherever you are. All our units are backed by expert service and a five-year warranty. With every product you purchase, you receive personal technical support and guidance, ongoing deliveries, repair free of charge during the warranty period, and easily accessible documentation.

We have our headquarters in Denmark and offices and authorized partners worldwide. We are a local company with global reach. This means we are always close by and have a thorough understanding of the local market. We want you to be satisfied and therefore offer SMARTER PERFORMANCE worldwide. For more information about our warranty program or to meet a salesperson in your region, visit prelectronics.se.

www.prelectronics.se

Models: 5332V105-SE, 5332V105-SE 2 Wire Programmable RTD Temperature Transmitter, 5332V105-SE, 2 Wire Programmable RTD Temperature Transmitter, Programmable RTD Temperature Transmitter, RTD Temperature Transmitter, Temperature Transmitter, Transmitter

PDF preview unavailable. Download the PDF instead.

5332v105 se Adobe PDF Library 17.0 Adobe InDesign 19.4 (Windows)

Related Documents

Preview PR Electronics 5332 2-Wire Programmable RTD Transmitter Product Manual
This product manual provides detailed information on the PR Electronics 5332 2-wire programmable RTD transmitter, covering its applications, technical specifications, installation, and safety guidelines for various hazardous environments.
Preview PR electronics 5335 2-Wire Transmitter with HART Protocol Product Manual
Comprehensive product manual for the PR electronics 5335 2-wire transmitter with HART protocol, detailing its features, applications, technical specifications, and installation guidelines.
Preview PR electronics 5337 2-Wire Transmitter with HART Protocol - Product Manual
Comprehensive product manual for the PR electronics 5337, a 2-wire transmitter with HART protocol. Details technical specifications, applications, installation guidelines, programming options, and safety certifications including ATEX, IECEx, CSA, FM, and INMETRO.
Preview PR electronics 5114 Programmable Transmitter - Technical Specifications and Manual
Detailed technical specifications, features, application, and installation guide for the PR electronics 5114 Programmable Transmitter. Includes electrical data, safety information, and ordering details.
Preview Manuale PR electronics 4179B: Amplificatore di Soglia Universale
Manuale completo per l'amplificatore di soglia universale PR electronics 4179B. Copre caratteristiche, installazione, programmazione, diagnostica e risoluzione problemi per applicazioni industriali.