PR Electronics 5332 2-Wire Programmable RTD Transmitter
Product Overview
The PR electronics 5332 is a 2-wire programmable RTD transmitter designed for industrial and factory automation. It offers high signal integrity and is suitable for demanding environments, backed by a 5-year warranty.
6 Product Pillars
PR electronics focuses on six key product areas to meet diverse industrial needs:
- Temperature: Transmitters and sensors providing high signal integrity for process temperature measurements, with features like automatic self-calibration and sensor error detection.
- I.S. Interface: Intrinsically safe isolation barriers with SIL 2 Full Assessment, offering multifunctional inputs and outputs for safe and cost-effective solutions.
- Communication: Easy-to-use, future-ready interfaces for accessing PR products, featuring built-in displays and configuration via push-buttons. Supports Modbus and Bluetooth, with remote access via the PR Process Supervisor (PPS) application.
- Multifunction: Versatile single devices adaptable to a broad range of applications, simplifying installation, training, and spare parts management. Designed for long-term accuracy and low power consumption.
- Isolation: Compact, high-quality 6 mm isolators based on microprocessor technology, providing exceptional performance and EMC immunity with low total cost of ownership. Can be stacked vertically or horizontally.
- Display: Flexible and stable devices for process signal readout, featuring universal input and power supply capabilities for real-time process value measurement.
Key Features
- RTD or Ohm input
- Accuracy: Better than 0.05% of selected range
- Programmable sensor error value
- DIN form B sensor head mounting
Applications
- Linearized temperature measurement with Pt100, Pt1000, Ni100, or Ni1000 sensors.
- Conversion of linear resistance variation to a standard analog current signal for valves or Ohmic level sensors.
Technical Characteristics
- Programmable for various temperature ranges.
- Dedicated programmable non-isolated 4-wire RTD transmitter.
- RTD and resistance inputs support 2-, 3-, and 4-wire connections with cable compensation.
- Continuous check of stored data for safety.
Mounting / Installation
For DIN form B sensor head mounting. In non-hazardous areas, the 5332 can be mounted on a DIN rail using the PR fitting type 8421.
Electrical Specifications
- Environmental Conditions: Operating temperature: -40°C to +85°C; Calibration temperature: 20...28°C; Relative humidity: < 95% RH (non-cond.).
- Protection Degree: IP68/IP00.
- Mechanical Specifications: Dimensions: Ø 44 x 20.2 mm; Weight: 50 g; Max. wire size: 1 x1.5 mm² stranded wire; Screw terminal torque: 0.4 Nm.
- Common Specifications: Supply voltage: 7.2...35 VDC; Internal power dissipation: 25 mW...0.8 W; Voltage drop: 7.2 VDC; Warm-up time: 5 min.
- Programming: Loop Link interface.
- Signal/noise ratio: Min. 60 dB.
- Response time: 1...60 s (programmable).
- EEprom error check: < 3.5 s.
- Signal dynamics: Input: 20 bit; Output: 16 bit.
- Effect of supply voltage variation: < 0.005% of span / VDC.
Accuracy
General Values
Input type | Absolute accuracy | Temperature coefficient |
---|---|---|
All | ≤ ±0.05% of span | ≤ ±0.01% of span / °C |
Basic Values
Input type | Basic accuracy | Temperature coefficient |
---|---|---|
RTD | ≤ ±0.2°C | ≤ ±0.01°C/°C |
Lin. R | ≤ ±0.1 Ω | ≤ ±10 mΩ / °C |
Input Specifications
RTD and linear resistance input
Type | Min. value | Max. value | Min. span | Standard |
---|---|---|---|---|
Pt100...Pt1000 | -200°C | +850°C | 25°C | IEC 60751 |
Ni100...Ni1000 | -60°C | +250°C | 25°C | DIN 43760 |
Linear resistance | 0 Ω | 5000 Ω | 30 Ω | --- |
- Max. offset: 50% of selec. max. value.
- Cable resistance per wire (max.): 5 Ω.
- Sensor current: Nom. 0.2 mA.
- Effect of sensor cable resistance (3-/4-wire): < 0.002 Ω/Ω.
- Sensor error detection: Yes.
Output Specifications
- Current output: Signal range: 4...20 mA; Min. signal range: 16 mA; Updating time: 440 ms.
- Load resistance: ≤ (Vsupply - 7.2) / 0.023 [Ω].
- Load stability: < ±0.01% of span / 100 Ω.
- Sensor error detection: Programmable, NAMUR NE43 Upscale: 3.5...23 mA, NAMUR NE43 Downscale: 23 mA, 3.5 mA.
Observed Authority Requirements
- EMC: 2014/30/EU
- RoHS: 2011/65/EU
- ATEX: 2014/34/EU
- EAC: TR-CU 020/2011
- EAC Ex: TR-CU 012/2011
Ex / I.S. Approvals
- 5332A: ATEX: KEMA 10ATEX0002 X
- 5332D: ATEX: KEMA 06ATEX0062 X; FM: FM17US0013X
- 5332A & 5332D: IECEX: DEK 13.0035 X; CSA: 1125003; INMETRO: DEKRA 16.0013 X; EAC Ex: RU C-DK.HA65.B.00355/19
Connections
Input:
- RTD, 2-wire: Terminals 3, 4
- RTD, 3-wire: Terminals 3, 4, 5
- RTD, 4-wire: Terminals 3, 4, 5, 6
- Resistance, 2-wire: Terminals 3, 4
- Resistance, 3-wire: Terminals 3, 4, 5
- Resistance, 4-wire: Terminals 3, 4, 5, 6
Output:
- 2-wire installation: Terminals 1 (+), 2 (-)
Block Diagram
The block diagram illustrates the signal path from the RTD input through the CPU, A/D converter, and D/A converter to the 4-20 mA output, powered by a 7.2-35 VDC supply.
Programming
Programming is done using the Loop Link communication interface and the PReset software. Loop Link is not approved for communication in hazardous (Ex) areas.
Order: Loop Link
The diagram shows the Loop Link connection to the 5332 transmitter via USB, with connections for Red, Black, Yellow, and Green wires.
Mechanical Specifications
Dimensions: Ø 6 mm, 33 mm, Ø 44 mm, 20.2 mm.
Mounting of Sensor Wires
Wires must be mounted between the metal plates.
ATEX Installation Drawing (5332A)
Address: LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
ATEX Certificate: KEMA 10ATEX 0002X
Marking: II 3 G Ex nA [ic] IIC T4 ... T6 Gc; II 3 G Ex ic IIC T4...T6 Gc; II 3 D Ex ic IIIC Dc
Standards: EN 60079-0: 2012, EN 60079-11: 2012, EN 60079-15: 2010
Temperature Ratings: T4: -40 ≤ Ta ≤ 85°C; T6: -40 ≤ Ta ≤ 60°C
Terminal Details:
- Terminal: 3,4,5,6 (Ex nA [ic]): Uo: 9.6 V; Io: 25 mA; Po: 60 mW; Lo: 33 mH; Co: 2.4 µF
- Terminal: 1,2 (Ex nA): Umax ≤ 35 VDC; Ui = 35 VDC; li = 110 mA; Li = 10 μH; Ci = 1.0 nF
- Terminal: 1,2 (Ex ic): Ui = 35 VDC; li = 110 mA; Li = 10 μH; Ci = 1.0 nF
Special conditions for safe use: For Ex nA protection, mount in a metal enclosure with IP54 (EN60529). For combustible dust, use IP6X enclosure. For ambient temperature ≥ 60°C, use heat-resistant cables rated for 20 K above ambient.
ATEX Installation Drawing (5332D)
Address: LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
ATEX Certificate: KEMA 06ATEX 0062 X
Marking: II 1 G Ex ia IIC T4...T6 Ga; II 1 D Ex ia IIIC Da; I 1 M Ex ia I Ma
Standards: EN 60079-0: 2012, EN 60079-11: 2012, EN 60079-26: 2007, EN 60079-15:2010
Hazardous Area: Zone 0, 1, 2, 20, 21, 22
Temperature Ratings: T4: -40 ≤ Ta ≤ 85°C; T6: -40 ≤ Ta ≤ 60°C
Terminal Details:
- Terminal: 3,4,5,6: Uo: 9.6 VDC; Io: 25 mA; Po: 60 mW; Lo: 33 mH; Co: 2.4µF
- Terminal: 1,2: Ui: 30 VDC; li: 120 mA; Pi: 0.84 W; Li: 10μΗ; Ci: 1.0nF
Installation notes: For explosive gas atmospheres, mount in a metal enclosure (IP20 minimum, IP54 for Ex nA). For aluminum enclosures in explosive atmospheres, ensure no impact/friction sparks. For non-metallic enclosures, avoid electrostatic charging. For explosive dust atmospheres, use a metal enclosure form B (IP6X) and ensure correct cable entries. For ambient temperature ≥ 60°C, use heat-resistant cables (20 K above ambient). Surface temperature is ambient + 20 K for dust layers up to 5 mm.
IECEx Installation Drawing (5332A)
Address: LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Certificate: IECEX DEK 13.0035X
Marking: Ex nA [ic] IIC T4..T6 Gc; Ex ic IIC T4..T6 Gc; Ex ic IIIC Dc
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011, IEC 60079-15: 2010
Temperature Ratings: T4: -40 ≤ Ta ≤ 85°C; T6: -40 ≤ Ta ≤ 60°C
Terminal Details:
- Terminal: 3,4,5,6: Uo: 9.6 V; Io: 25 mA; Po: 60 mW; Lo: 33 mH; Co: 2.4 µF
- Terminal: 1,2 (Ex nA): Umax =35 VDC; Ui = 35 VDC; li = 110mA; Li = 10 μH; Ci = 1.0 nF
- Terminal: 1,2 (Ex ic): Ui = 35 VDC; li = 110mA; Li = 10 μH; Ci = 1.0 nF
Installation note: For gas atmospheres, use metal enclosure (IP54 for Ex nA, IP20 for Ex ic). For dust atmospheres, use metal enclosure form B (IP6X). Heat-resistant cables for ≥ 60°C ambient. Surface temperature is ambient + 20 K for dust layers.
IECEx Installation Drawing (5332D)
Address: LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Certificate: IECEX DEK 13.0035X
Marking: Ex ia IIC T4...T6 Ga; Ex ia IIIC Da; Ex ia I Ma
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011, IEC 60079-26:2006
Hazardous Area: Zone 0, 1, 2, 20, 21, 22, M1
Temperature Ratings: T4: -40 ≤ Ta ≤ 85°C; T5: -40 ≤ a ≤ 60°C; T6: -40 ≤ Ta ≤ 45°C
Terminal Details:
- Terminal 3,4,5,6: Uo: 9.6 VDC; lo: 25 mA; Po: 60 mW; Lo: 33 mH; Co: 2.4µF
- Terminal 1,2: Ui: 30 VDC; li: 120 mA; Pi: 0.84 W; Li: 10μΗ; Ci: 1.0nF
Installation notes: For gas atmospheres, use metal enclosure (IP20 minimum). For aluminum enclosures in explosive atmospheres, ensure no impact/friction sparks. For non-metallic enclosures, avoid electrostatic charging. For dust atmospheres, use metal enclosure form B (IP6X). Heat-resistant cables for ≥ 60°C ambient. Surface temperature is ambient + 20 K for dust layers.
FM Installation Drawing (Models 5331D, 5332D, 5333D, 5343B)
Hazardous (Classified) Location: Class I, Division 1, Groups A,B,C,D T4..T6; Class I, Zone 0, AEx ia IIC T4..T6
Ambient temperature limits: T4: -40 to + 85 deg. Celcius; T6: -40 to + 60 deg. Celcius
Terminal 1,2 Parameters: Vmax or Ui: 30 V; Imax or li: 120 mA; Pmax or Pi: 0.84 W; Ci: 1 nF; Li:10 uH
Terminal 3,4,5,6 Parameters: Vt or Uo: 9.6 V; It or lo: 28 mA; Pt or Po: 67.2 mW; Ca or Co: 3.5 uF; La or Lo: 35 mH
Non Hazardous Location: Associated Apparatus or Barrier with entity Parameters (UM < 250V, Voc or Uo, Isc or lo, Po < Pi, Vmax or Ui, Imax or li, Ca or Co > Ci + Ccable, La or Lo > Li + Lcable). This device must not be connected to any associated apparatus which uses or generates more than 250 VRMS.
FM Installation Drawing (Models 5335D, 5337D)
Hazardous (Classified) Location: Class I, Division 1, Groups A,B,C,D T4..T6; Class I, Zone 0, AEx ia IIC T4..T6
Ambient temperature limits: T4: -40 to + 85 deg. Celcius; T6: -40 to + 60 deg. Celcius
Terminal 1, 2 Parameters: Vmax or Ui: 30 V; Imax or li: 120 mA; Pmax or Pi: 0.84 W; Ci: 1 nF; Li:10 uH
Terminal 3,4,5,6 Parameters: Vt or Uo: 9.6 V; It or lo: 28 mA; Pt or Po: 67.2 mW; Ca or Co: 3.5 uF; La or Lo: 35 mH
Non Hazardous Location: Associated Apparatus or Barrier with entity Parameters (UM < 250V, Voc or Uo < Vmax or Ui, Isc or lo Imax or li, Po ≤ Pi, Ca or Co > Ci + Ccable, La or Lo > Li + Lcable). This device must not be connected to any associated apparatus which uses or generates more than 250 VRMS.
Entity concept: Transmitter must be installed per National Electrical Code (ANSI-NFPA 70). FM-approved equipment can be connected to barriers based on the ENTITY CONCEPT, provided agency criteria are met. Intrinsically safe devices must not be a power source. Ui/li/Pi must be greater than or equal to Uo/Io/Po of the barrier. Capacitance and inductance of intrinsically safe devices and wiring must be less than the barrier's allowance.
NI Field Circuit Parameters (Models 5331D, 5332D, 5333D, 5335D, 5337D and 5343B): Hazardous Location: Class I, Division 2, Groups A,B,C,D T4..T6; Class I, Zone 2, IIC T4..T6. Ambient temperature limits: T4: -40 to + 85 deg. Celcius; T6: -40 to + 60 deg. Celcius. Terminal 1, 2 Parameters: Vmax: 35 V; Ci: 1.0 nF; Li:10 uH.
CSA Installation Drawing (5331QC02)
Marking: Class I, Division 2, Group A,B,C,D T4..T6; Class I Zone 2 Ex/AEx nA[ic] IIC T4..T6; Class I Zone 2 Ex/AEx nA IIC T4..T6; NIFW Class I Division 2, Group A,B,C,D
Hazardous Area: CL I, Div 2, GP ABCD; CL I, Zone 2, IIC. T4: -40°C to 85 °C; T6: -40°C to 60 °C
Terminal Details:
- Terminal: 3,4,5,6: Uo: 9.6 VDC; lo: 25 mA; Po: 60 mW; Lo: 33 mH; Co: 2.4µF
- Terminal: 1-2: Functional Ratings: U nominal ≤ 35 VDC; I nominal ≤ 3.5 - 23 mA
NI Installation instructions: Install in an enclosure with at least IP54 protection (IEC60529). Avoid electrostatic charging on non-metallic/painted enclosures. Use supply wires rated 5 K above ambient. Supply from Class 2 Power Supply with transient protection. WARNING: Component substitution may impair Class I, Division 2 suitability. Do not disconnect equipment unless power is off or area is safe.
Non Incendive field wiring installation: Allows interconnection of Nonincendive Field wiring Apparatus with Associated Nonincendive Field Wiring Apparatus or Associated Intrinsically Safe Apparatus or Associated Apparatus using wiring methods permitted for unclassified locations. Voc < Vmax, Ca ≥ Ci + Ccable, La ≥ Li + Lcable.
CSA Installation Drawing (5332QC01)
Hazardous area: T4: -40 ≤ Ta ≤ 85°C; T6: -40 ≤ Ta ≤ 60°C
Terminal: 3,4,5,6: Connect only to passive, or non-energy storing devices such as RTD's.
Terminal: 1,2: Ui: 30 VDC; li: 120 mA; Pi: 0.84 W; Li: 10μΗ; Ci: 1.0nF
CLASS 2258 04 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous Locations: Class I, Division 1, Groups A, B, C and D; Ex ia IIC, Ga
CLASS 2258 84 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous Locations - Certified to US Standards: Class I, Division 1, Groups A, B, C and D; Class I, Zone 0, AEx ia IIC, Ga
Warning: Substitution of components may impair intrinsic safety. Install in a suitable enclosure per Canadian Electrical Code (CEC) or National Electrical Code (NEC).
Desenho de Instalação INMETRO (5332A)
Certificado: DEKRA 16.0013 X
Marcas: Ex nA [ic] IIC T4..T6 Gc; Ex ic IIC T4..T6 Gc; Ex ic IIIC Dc
Normas: ABNT NBR IEC 60079-0: 2013; ABNT NBR IEC 60079-11: 2013; ABNT NBR IEC60079-15: 2012
Temperature Ratings: T4: -40 ≤ Ta ≤ 85°C; T6: -40 ≤ Ta ≤ 60°C
Terminal Details:
- Terminais: 3,4,5,6: Uo: 9,6 V; lo: 25 mA; Po: 60 mW; Lo: 33 mH; Co: 2,4 μF
- Terminais: 1,2 (Ex nA): U ≤35 VDC; Ui = 35 VDC; li = 110 mA; Li = 10 μH; Ci = 1,0 nF
- Terminais: 1,2 (Ex ic): Ui = 35 VDC; li = 110 mA; Li = 10 μH; Ci = 1,0 nF
Notas para instalação: For gas atmospheres, mount in metal enclosure (IP54 minimum per ABNT NBR IEC60529). For Ex ic, IP20 minimum. For aluminum enclosures in explosive atmospheres, ensure no impact/friction sparks. For non-metallic enclosures, avoid electrostatic charging. For dust atmospheres, use metal enclosure form B (IP6X per ABNT NBR IEC60529). Heat-resistant cables for ≥ 60°C ambient. Surface temperature is ambient + 20 K for dust layers up to 5 mm.
Desenho de Instalação INMETRO (5332D)
Certificado: DEKRA 16.0013 X
Marcas: Ex ia IIC T6...T4 Ga; Ex ia IIIC Da; Ex ia I Ma
Normas: ABNT NBR IEC 60079-0: 2013; ABNT NBR IEC 60079-11: 2013
Áreas classificadas: Zona 0, 1, 2, 20, 21, 22. T4: -40 ≤ Ta ≤ 85°C; T5: -40 ≤ a ≤ 60°C; T6: -40 ≤ Ta ≤ 45°C
Terminal Details:
- Terminais 3,4,5,6: Uo: 9,6 VDC; lo: 25 mA; Po: 60 mW; Lo: 33 mH; Co: 2,4µF
- Terminais: 1,2: Ui: 30 VDC; li: 120 mA; Pi: 0,84 W; Li: 10μΗ; Ci: 1,0nF
Notas de instalação: For gas atmospheres, mount in enclosure (IP20 minimum per ABNT NBR IEC60529). For aluminum enclosures in explosive atmospheres, ensure no impact/friction sparks. For non-metallic enclosures, avoid electrostatic charging. For dust atmospheres, use metal enclosure form B (IP6X per ABNT NBR IEC60529). Heat-resistant cables for ≥ 60°C ambient. Surface temperature is ambient + 20 K for dust layers.
Document History
- Rev. ID 100, Date 1845: Initial release of the product.
- Rev. ID 101, Date 2007: EAC, EAC Ex and INMETRO approvals added. CSA installation drawing for 5332A added.
Global Presence
PR electronics has offices and authorized partners worldwide, providing local market knowledge and global reach. They are committed to customer satisfaction and offer PERFORMANCE MADE SMARTER solutions.
About PR electronics
PR electronics is a leading technology company specializing in industrial process control, focusing on high-precision technology with low power consumption. Founded in 1974, the company is driven by customer needs and principles of simplicity, focus, courage, and excellence.
Related Documents
![]() |
PR electronics 5335 2-Wire Transmitter with HART Protocol Product Manual Comprehensive product manual for the PR electronics 5335 2-wire transmitter with HART protocol, detailing its features, applications, technical specifications, and installation guidelines. |