EasyIO FG Series FAQ

EasyIO FG Series FAQ

Version 1.3

Document Change Log

  • 16th May 2014: Document created.
  • 28th Dec 2014: Bacnet limitation added.
  • 28th Dec 2014: Edit doc.
  • 26th Oct 2015: Details update for FG+ model.

Disclaimer

EasyIO 30P is a product by EasyIO Holdings Pte Ltd. The EasyIO 30P was built on the Sedona Framework®.

EasyIO FG-32 is a product by EasyIO Holdings Pte Ltd. The EasyIO FG-32 was built on the Sedona Framework®.

Sedona Framework is a trademark of Tridium, Inc.

CPT Tool is by Online Tools Inc.

Introduction

This document is a quick reference to all most commonly asked questions.

Frequently Asked Questions

1) Default IP address.

Below applies to both FG and FG+.

Default IP address: 192.168.10.11

Default Subnet: 255.255.255.0

Default Gateway: 192.168.10.1

The above IP address is the IP address if a restore to factory setting carried out at the controller.

2) Commonly used login credentials for EasyIO FG Series

Below applies to both FG and FG+.

Function Username Password Remarks
Sedona (sox) admin (Leave it blank) Login to the Sedona sox protocol
Controller Web scripts (via file transfer client, FTP) webuser 123456 Login to the webuser folder that contains web server default files system.
CPT graphics deployment webuser 123456 Credentials for CPT graphics deployment
CPT graphics login via web browser admin hellocpt Credentials for CPT web server
Micro SD card (if a micro SD card is insert) sdcard 123456 Login to the SD Card file system where it contain the CPT deployed files.
SQL Lite browser administrative page - 123456 Login to the SQL Lite Administrative Web Page. Link: http://192.168.10.11/sdcard/phpliteadmin.php

3) Default IP Ports for EasyIO FG Series

Below applies to both FG and FG+.

Protocol Port Type Remarks
Sedona (sox) 1876 UDP Sox connection
File Transfer Client (FTP) 21 TCP Graphics Deploy, File Transfer via FTP Client
Modbus TCP 502 TCP Modbus TCP Port
BACnet IP 47808 UDP BACnet IP Port
Web Server 80 TCP Build In Web Server port
Tcom 5021 UDP Tcom Niagara Driver port

4) How do I upgrade the firmware for EasyIO FG Series controllers?

FG Series: There are two types of flashing files which are explained below. Both types will erase the Sedona apps in the controller, therefore please ensure a controller back up is performed before the flashing procedure otherwise the controller App will be lost.

The process will take approximately 5 minutes. The RED LED will light constantly for 5 minutes. This is normal.

If the RED LED continues to light up for more than 8 minutes, the firmware file transferred into the SD card is corrupted.

Type Functions Remarks
Factory Default Firmware upgrade
Restore back to factory default
Sedona apps will be erase
IP address will restore back to default IP address (IP address: 192.168.10.11)
Maintain IP address Firmware upgrade
Remain the last IP address
Sedona apps will be erase
IP address will remain the last valid IP address set.

Get the required files from EasyIO technical support at support@easyio.com. Depending on version, quantity of files may differ. See below.

For V2.1.2.0.01 and below: Requires 2 files.

For V2.1.2.0.02 and above: Requires only 1 file.

The firmware file, typically fg320.tar.gz, needs to be copied into the fg320 folder using a file transfer client or a memory card reader. You can copy files over to the SD card by dragging the file into the fg320 folder if a file transfer client program is used.

Note: You might need 2 files or 1 file depending on the current firmware version of the controller. Important: Please check the file size and compare with the source file to ensure correctness.

3 Important Tech Tips if using file transfer client program:

  1. Files need to be transferred/copied into the "fg320" folder.
  2. Files cannot be in the root directory of the SD card; they need to be copied into the "fg320" folder.
  3. If the "fg320" folder is not seen, refer to Step 3 above.

Login to the Sedona controller via Sedona workbench or the CPT tool and reboot the device.

Tech Tip: The watchdog jumper must be in the "ON" position for the controller to automatically reboot. By default, the controller is shipped with the watchdog jumper in the ON position.

For detailed explanation, please refer to "04 EasyIO FG Series Firmware Upgrade.pdf".

For FG+ series: There are 4 files required.

Note: You need 4 files for FG+ controller. Important: Please check the file size and compare with the source file to ensure correctness.

5) Restore to factory default.

Below apply to both FG and FG+.

The new firmware release dated 1st August 2013 comes with "Restore Factory Settings". This function is done by pressing the “Service” button while the controller is booting up.

A restore to factory settings will do the following:

  1. Restore the IP address to the default, which is 192.168.10.11.
  2. Clear the Sedona application in the Sedona VM back to default (default app is an empty app).
  3. A default Sedona apps default login is admin, with no password.

Below is a simple explanation. For detail explanation, please refer to "03 EasyIO FG Series User Reference.pdf".

Step 1: Make sure you backup the Sedona apps if you have connection to the EasyIO FG32.

Step 2: Cycle power and within 5 seconds, press and HOLD down the service button until the Error LED starts to flash approximately 2 Hz. This process will take approximately 15 seconds before the error LED starts to blink.

Step 3: Once the Red LED flashes, a momentary press of the service button will restore the FG Series controller back to factory default state.

6) Micro SD Card

Each EasyIO FG Series comes with a micro SD memory card slot.

Specifications Remark
Brand tested recommended Transend, Kingston
Capacity tested 2GB, 4GB, 8GB, 16GB
Class Class 4
Class 10

Please note that the Micro SD card in the EasyIO FG Series is optional and the controller does not come with the SD Micro Card as standard. The SD Micro card can be purchased separately that have the following specifications.

Make sure the controller is power off before inserting the micro SD Card.

For detail explanation, please refer to "01 EasyIO FG32 Installation.pdf".

7) EasyIO FG Series Modbus Master Driver limitation

Modbus RTU Master

Modbus only can run at Port 2.

Max. No. of MODBUS Serial Networks (per FG device) 1
Max. No. of MODBUS Serial Devices per Network 31
Max. No. of Points per MODBUS Serial Device 32

Modbus TCP Master

Max. No. of MODBUS TCP Networks (per FG device) 1
Max. No. of MODBUS TCP Devices per Network 31
Max. No. of Points per MODBUS TCP Device 32

Modbus TCP Gateway

Max. No. of TCP Gateway Networks (per FG device) 1
Max. No. of MODBUS Gateway Devices allowed 31
Max. No. of Points per MODBUS Gateway Device 32

For detail explanation, please refer to "10 EasyIO FG Series Modbus Master.pdf".

8) EasyIO FG Series Modbus Slave Driver limitation

Modbus RTU Slave/ Modbus TCP Slave

Modbus only run at Port 2.

Max Network allowed 1 (of both drivers)
Max Discrete Point allowed 200 register address (total)
Max Coil Output allowed 200 register address(total)
Max Input Register allowed 200 register address, depending to data type.
Max Holding Register allowed Integer data type occupy 1 register address
Float data type occupy 2 register address
Long data type occupy 2 register address
200 register address, depending to data type.
Integer data type occupy 1 register address
Float data type occupy 2 registers address
Long data type occupy 2 registers address

For detail explanation, please refer to "EasyIO 11 EasyIO FG Series Modbus Slave.pdf".

9) EasyIO FG BACnet Server Limitation

BACnet IP Server

(Information is correct at the time of document)

Bacnet MS/TP only run at Port 1.

Objects supported
Analog Value , Read Only or Read Write
Binary Value , Read Only or Read Write
Priority Array Supported Yes
Writable Property Present Value Only
Total Analog Value (AV) 128
Total Binary Value (BV) 128

For detail explanation, please refer to "12 EasyIO FG Series Bacnet.pdf".

10) EasyIO FG BACnet Client Limitation

(Information is correct at the time of document)

Multistate objects need firmware b38 or higher and easyioBacnet kit 1.0.45.38.4 or higher.

Bacnet MS/TP only run at Port 1.

Max devices 32 devices (combination of both IP and MSTP devices)
Max registers per device 31 BACnet objects (combination of all the supported BACnet objects below)
Objects supported Analog Input
Analog Output
Analog Value , Read Only or Read Write
Binary Input
Binary Output
Binary Value , Read Only or Read Write
Multistate Input
Multistate Output
Multistate Value, Read Only or Read Write

Priority Array Supported: Yes

Writable Property: Present Value Only

Total Analog Value (AV): 32

Total Binary Value (BV): 32

For detail explanation, please refer to "EasyIO 12 EasyIO FG Series Bacnet.pdf".

11) EasyIO FG Series History storage

There is no metric for calculating memory size for a history data table. Table below displays an estimation of memory size used. Results are by EasyIO bench testing.

Number of Table Number of Column (Values) Total records Size on Disk
1 1 1000 40 KB
1 10 1000 132 KB
1 1 100,000 5,100 KB
1 32 100,000 27,000 KB

For detail explanation, please refer to "14 EasyIO FG Series SQL Lite.pdf".

Technical Support

For technical support issues, please contact the technical support person as below:

Email: support@easyio.com

PDF preview unavailable. Download the PDF instead.

FAQ EASYIO-FG Microsoft Office Word 2007 Microsoft Office Word 2007

Related Documents

Preview EasyIO FG Series Controller BACnet Protocol Implementation Conformance Statement
This document provides the BACnet Protocol Implementation Conformance Statement (PICS) for the EasyIO FG+ Controller, detailing its supported features, device profiles, interoperability building blocks, object types, and data link layer options.
Preview EasyIO-30P-SF45-V2: High-Performance Network Controller with Sedona Framework
Discover the EasyIO-30P-SF45-V2, a robust network-centric controller featuring Sedona Framework, BACnet IP, Modbus, and a web server for seamless configuration and management of building automation systems.
Preview EasyIO 30P Frequently Asked Questions: HVAC Control and Automation
A comprehensive FAQ guide for the EasyIO-30P controller, covering installation, configuration, Sedona framework, BACnet, Modbus, and troubleshooting for HVAC and building automation systems.
Preview EasyIO FW-08 V3 Instruction Manual and Installation Guide
Comprehensive instruction and installation guide for the EasyIO FW-08 V3 building automation and IoT controller, detailing mounting, wiring, electrical ratings, communication, wireless specifications, and regulatory compliance.