EasyIO FG Series Controller
BACnet Protocol Implementation Conformance Statement
Your Choice for Automation
Version 1.01 February 2016
Document Information
Date: February 25, 2016
Vendor Name: EasyIO Holdings Pte. Ltd.
Product Name: EasyIO FG+ Controller
Product Model Number: FG-32+, FG-20+
Applications Software Version: 1.17
Firmware Revision: 0.8.2
BACnet Protocol Revision: 1.09
© EasyIO Holdings Pte Ltd 2011-2016
Product Description
The EasyIO FG+ Controller is a dual ARM processor based controller comprising up to 32 input/output (I/O) channels, an Ethernet port, and 2 RS-485 ports. The controller supports multiple concurrent protocols and services, including BACnet, Modbus, TCOM, and Web Services. It features universal inputs (digital, resistance, voltage, current, pulse count), relay outputs, and universal outputs (voltage, current, digital). Graphics content is stored on the built-in micro SD Card slot (up to 16GB).
BACnet Standardized Device Profile (Annex L)
- BACnet Operator Workstation (B-OWS)
- BACnet Building Controller (B-BC)
- BACnet Advanced Application Controller (B-AAC)
- BACnet Application Specific Controller (B-ASC)
- BACnet Smart Sensor (B-SS)
- BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K)
Supported BIBBs | BIBB Name |
---|---|
DS-RP-B | Data Sharing – ReadProperty – B |
DS-RPM-B | Data Sharing – ReadPropertyMultiple – B |
DS-WP-B | Data Sharing – WriteProperty – B |
DS-WPM-B | Data Sharing – WritePropertyMultiple – B |
DM-DDB-B | Device Management – Dynamic Device Binding – B |
DM-DOB-B | Device Management – Dynamic Object Binding – B |
DM-DCC-B | Device Management – DeviceCommunicationControl – B |
Standard Object Types Supported
COV: Supports change of value (COV) reporting
DC: Dynamically creatable
DD: Dynamically deletable
There are no specific property range restrictions. Standard object types are supported as listed:
Object Type | COV | DC/DD | Optional Properties | Writable Properties |
---|---|---|---|---|
Analog Value | □ | □ | Description Priority_Array Relinquish_Default | Object_Name Present_Value Units Relinquish_Default |
Binary Value | □ | □ | Description Priority_Array Relinquish_Default | Object_Name Present_Value Relinquish_Default |
Device | □ | □ | Max Master Max_Info_Frames Description | Object_Identifier Object_Name APDU_Timeout Number_Of_APDU_Retries |
Data Link Layer Options
- ■ BACnet IP, (Annex J)
- □ BACnet IP, (Annex J), Foreign Device
- □ ISO 8802-3, Ethernet (Clause 7)
- □ ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
- □ ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s): [Specify]
- ■ MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400
- □ MS/TP slave (Clause 9), baud rate(s): [Specify]
- □ Point-To-Point, EIA 232 (Clause 10), baud rate(s): [Specify]
- □ Point-To-Point, modem, (Clause 10), baud rate(s): [Specify]
- □ LonTalk, (Clause 11), medium: [Specify]
- □ Other: [Specify]
Device Address Binding
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)
■ Yes □ No
Networking Options
- □ Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
- □ Annex H, BACnet Tunneling Router over IP
- □ BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? □ Yes ■ No
Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
- ■ ANSI X3.4
- □ ISO 10646 (UCS-2)
- □ IBM™/Microsoft® DBCS
- □ ISO 8859-1
- □ ISO 10646 (UCS-4)
- □ JIS C 6226