AIKO PV Module Installation Manual - Double Glass Module

AIKO reserves the right to change this Manual without prior notice. Please check the latest version of the Installation Manual on the official website of AIKO: www.aikosolar.com. This manual is version 2.0, updated August 2023.

Applicable module models include: AIKO-Axxx-MAH54Dw, AIKO-Axxx-MAH54Db, AIKO-Axxx-MAH72Dw, AIKO-Axxx-MAH72Db. Module structure: Double Glass.

Important safety instructions: This Installation Manual provides information regarding the installation and safe use of PV power modules (hereinafter referred to as "modules") produced by AIKO Digital Energy Technology Co., Ltd. (hereinafter referred to as "AIKO"). Installation and day-to-day maintenance of modules shall be in accordance with all safety precautions specified in this Manual and local laws. Installation of module systems requires specialized skills and knowledge, and modules shall be installed and maintained by qualified persons. Installers shall be familiar with mechanical and electrical requirements of the system. Please keep this Manual for future maintenance or treatment.

01 Overview

Thank you for choosing AIKO Digital Energy Technology Co., Ltd. products. This Installation Manual contains important information regarding electrical and mechanical installation that you must know before installing modules. It also contains other safety information you must be familiar with. This manual is not intended as a warranty, expressed or implied, nor does it include any indemnification plan against loss, module damage, or other expenses arising from installation, operation, use, or maintenance. Failure to install modules according to this manual will invalidate the limited product warranty. Recommendations are provided to improve installation safety and are based on tests and practical experience. Please provide this Manual to end customers and inform them of all safety, operation, and maintenance requirements.

02 Laws and acts

Mechanical and electrical installations of PV modules shall be executed by referring to applicable laws and acts, including electrical and building acts, and electrical connection requirements. These requirements vary by location and may differ for rooftop installations or onboard applications, and also by mounting system voltage and current properties (DC or AC). Please contact your local authority for further details.

03 General information

Structural diagram of double glass modules and component description

The diagram shows a double glass module with the following components:

  • 1. Aluminum alloy frame
  • 2. Front glass
  • 3. EVA (Ethylene Vinyl Acetate)
  • 4. ABC cell (All Black Cell)
  • 5. Back glass
  • 6. Silicone
  • 7. Junction Box
  • 8. Nameplate
  • 9. Cable
  • 10. Connector
  • 11. Mounting hole
  • 12. Grounding hole
  • 13. Leak hole
  • 14. Barcode

3.1 Module identification

AIKO modules have two visual labels:

  • Nameplate: Displays product type, rated power, rated current, rated voltage, open circuit voltage (Voc), short circuit current (Isc) under Standard Test Conditions (STC), maximum system voltage, and certification marks.
  • Serial number: Each module has a unique serial number printed on a barcode and embedded before lamination, making it permanent. The serial number is also found on the module frame and back.

Barcode labeling is also present on the module.

Packing List

The packing list includes module type, product serial number, package weight, package dimension, and cell color classification to ensure system color consistency. An example includes:

ItemDetails
Pallet No.A123224013
Product No.63000161
Module Power450 W
Qty31 PCS
Color CodeS1
Bin Code12345678912345
Module TypeAIKO-A450-MAH54Dw
Product Description450/A/12BB/1722*1134*35mm/FT50xy,25A,FMK5040D, RHC2xyzu,350mm/A123224013
N.W.756.0KG
G.W.801.0KG
Package Size1770*1140*1275mm
S/N:2DQC PASS 01
RemarkMade in China

Serial numbers are listed in a table format for individual modules.

3.2 Wiring method

AIKO modules have the junction box in the middle. Series connections are made as follows, depending on the mounting type:

  • Mounting on the long side, single row: Horizontally adjacent modules are connected directly or via secondary beams.
  • Mounting on the long side, double rows: Connections between adjacent rows are designed with opposite polarity on the same side. Adjacent modules can be connected via a duct. For vertical installation, connections between vertically adjacent modules are designed with opposite polarities and extension lines can be placed into the secondary beam.
  • Mounting on the short side, single row: Similar connection logic applies.
  • Mounting on the short side, multiple rows: Vertically adjacent modules are connected directly. Adjacent columns are designed with opposite polarity on the same side.

Diagrams illustrate these connection types.

03 General information (continued)

3.3 General safety

  • AIKO modules comply with IEC standards IEC-61215 and IEC-61730, with safety class II and fire class rating C.
  • Read and understand this Installation Manual before handling or installing. Contact AIKO (aikosolar.com) for explanations.
  • Use appropriate protections: insulated tools, safety helmets ⛑️, insulating gloves ?, safety belts, and safety shoes ?. Use appropriate electrical safety tools.
  • PV modules generate DC electrical energy when exposed to sunlight ☀️ or other light sources. Improper contact with live parts (connectors) can result in burns ?, sparks, and lethal shock ⚡.
  • Observe local laws and regulations for module installation and obtain necessary qualifications.
  • Modules must be installed by qualified persons with specialized skills and knowledge of the system's mechanical and electrical requirements. Identify potential risks like electrical shock in advance.
  • Rooftop systems require roofs that have passed structural analysis.
  • Observe safety regulations for all mounting components, wires, cables, connectors, inverters, and batteries.
  • Artificial concentrated sunlight should not be directed onto the module.

3.4 Electrical safety

  • Follow electrical safety precautions strictly to avoid accidents. Modules can generate DC voltage >30V and current >10A (STC). Avoid direct contact. Wear protective helmets ⛑️, insulating gloves ?, and rubber shoes ?. Do not install components without security precautions.
  • Do not drill holes in the frame, as this risks module insulation failure.
  • Make electrical connections only via connectors.
  • Replace broken modules immediately due to risk of electric shock and fire ⚡.
  • Install modules only when electrically safe.
  • Avoid touching modules as surfaces and frames can be hot, risking burns ?. The series voltage must not exceed the maximum withstand voltage.
  • Do not connect or disconnect modules during current leakage or when external current is present. Disconnect faulty modules with safety protection.
  • Do not connect the positive and negative anode cables of the same PV module together.
  • Do not open the packing box before modules arrive; keep in a ventilated, dry environment.
  • Refer to Section 4.0 for Storage and Transportation instructions. Improper handling and storage can cause breakage or loss of electrical property.
  • When installing, do not lift modules by the junction box or cable. At least two operators must hold the module edges with both hands.
  • Do not attempt to dismantle the module or remove nameplates/components.
  • Do not apply paint or other adhesives to the module's top surface.
  • Do not damage or scratch the glass on the front or back side.
  • Do not drill holes in the frame, as this reduces frame loading capacity, can cause corrosion, and may invalidate the warranty.
  • Do not scratch the anodized coating of the aluminum alloy frame, except for grounding connections, as this may lead to corrosion and reduce reliability.
  • Do not repair or modify the module yourself.

04 Storage and transportation instructions

4.1 Considerations for module turnover and handling

  • Upon arrival, check the packaging for good condition and verify module type and quantity against the delivery order. Contact AIKO logistics if there are any issues.
  • Crane unloading: Use specialized tooling for the weight and size of the pallet. Adjust sling position for stability. Use wooden sticks or boards on the upper part of the box to prevent the sling from squeezing and damaging the modules. Operate the spreader at a constant speed. Place the box gently on relatively flat ground. Do not unload modules in wind conditions exceeding Beaufort scale 6 ?.
  • Forklift unloading: The loading dock should be at the same height as the carrier's underside. Maintain straight line speed within 5 km/h and turning speed within 3 km/h. Avoid sudden stops and rapid starts. If the packing box obstructs the driver's sight, drive in reverse and ensure special supervision to prevent collisions.

4.2 Considerations for module turnover and transportation

  • When using a forklift, ensure fork length meets requirements to avoid module tilting.
  • When opening the packing box, place modules to be unpacked at a distance of 20-30cm from the wall or other modules. Remove the torr (stack). After removing cable ties, slowly lean modules against the wall or torr to prevent falling.
  • Handle modules gently during transportation. Do not lift by the junction box or cables. Two or more people must hold the module edges with both hands.

4.3 Considerations for module storage and placement

  • Store modules in a clean, dry place with relative humidity below 85% ?. Storage temperature should be between -20°C and 50°C.
  • Do not stack two boxes of modules on top of each other for long-term storage.
  • Keep the junction box and cables clean and dry.
  • Store in a ventilated, rainproof, dry place. If stored outdoors, fully cover modules and pallets with rain protection and take moisture-proof measures to prevent collapse and moisture ingress.
  • For scattered modules, stack vertically with the glass side up for the first module, followed by modules with the glass side down. Maximum stack: 22 pieces for 54 types, 16 pieces for 72 types.
  • For long-term storage, keep the original package. It is recommended to store modules in a standard warehouse and conduct regular inspections. Address any abnormal tilt immediately.

05 Installation conditions

5.1 Location and working environment

  • Install modules in an environment between -20°C and 50°C (extreme working temperature -40°C to 85°C) with humidity less than 85%RH ?.
  • Modules are designed to operate up to 2000 m above sea level.
  • Do not install in locations at risk of flooding, near open flames ?, or flammable materials.
  • Install modules at least 50m away from the seashore. For installations between 50m and 500m, frames and components need anti-corrosion treatment.
  • For rooftop installations, ensure a safe working area between the roof edge and the PV module array. Check roof loads and create a construction organization plan.
  • Position modules to receive adequate sunlight ☀️ and avoid shading from trees or buildings.
  • Ensure modules are installed in a well-ventilated position for adequate air circulation on the back and sides to dissipate heat. Poor heat dissipation reduces output power.
  • For areas with high wind ? or snow ❄️ pressure, design supports and fixings according to local standards to withstand external loads.
  • In areas prone to salt fog, sulfide, or ammonia gas (coastal, factories, volcanic, farmlands), use anticorrosive materials for module-to-racking connections and ground connections.
  • After installation, ensure modules are protected against lightning strikes ⚡ via grounding.

5.2 Tilt angle selection

The tilt angle is the angle between the PV module and the horizontal ground. Different projects require different installation angles based on local conditions. All modules in the same array should have the same orientation and angle to avoid output mismatch and ensure system efficiency. For maximum annual energy generation, select the optimal orientation and inclination. When the module surface is perpendicular to sunlight ☀️, output power is maximized. AIKO recommends a tilt angle of not less than 10 degrees. The optimal tilt angle should consider multi-year mean irradiance, direct/scattering irradiance, wind speed, snow load, and water/dust collection. Consult a reliable local solar system installation company for details.

06 Mechanical installation

6.1 General requirements

  • Ensure modules are properly installed and the mounting structure is adequately fastened. Use anticorrosive, UV-resistant materials.
  • Installation bracket systems should be tested by a third party according to local or international standards.
  • In regions with heavy snowfall ❄️, adjust mounting system height so the module's lower edge is not covered by snow and is not in the shadow of plants/trees.
  • For rooftop installations, maintain a minimum gap of 10cm between the module frame and the roof for air circulation.
  • The minimum mounting distance between adjacent modules is 10 mm.
  • Ensure the module's backside does not contact piercing structures, especially under pressure.
  • Modules can be installed horizontally or vertically. Be cautious not to block drain holes.
  • Module loads described are test values. According to IEC 61215-2016, a safety factor of 1.5 is required for maximum design load calculations, complying with local laws. Project design loads must be based on location, climate, mounting structure, and standards. Consult mounting suppliers and structural engineers.

6.2 Mechanical installation of double glass modules

AIKO double glass modules can be mounted using pressure clamps and bolts. Follow recommendations below. Other configurations require AIKO Energy's prior written consent, otherwise the warranty will be invalidated.

6.2.1 Mounting pressure clamps

Specialized pressure clamps are used for mounting. Diagrams show side clamps and middle clamps, detailing bolt, gasket, nut, module frame, and racking. Ensure clamps do not touch the glass or deform the frame, and avoid shadowing. Clamps must not fail due to deformation or corrosion. Recommended clamp length is >50 mm and thickness >3 mm. The overlapped distance (D) between the clamp and the module frame should be at least 7 mm but no more than 10 mm. Use at least four clamps per module. For high wind/snow loads, at least six clamps may be required. Consult AIKO technical personnel for details. Applied torque should refer to mechanical design standards (e.g., M8 bolts: 16-20 N•m).

6.2.2 Double glass modules clamp mounting diagram and corresponding loads

Diagrams (A), (B), and (C) illustrate clamp mounting on the long frame, short frame, and short & long frame respectively. Tables provide module model, size, and load capacities [Pa] for different installation areas (30mm frame, 35/40mm frame). These loads are based on static load requirements of IEC61215 standard.

Table 3: Double glass modules clamp mounting diagram and corresponding loads, long frame (A)
Module modelModule size [mm]Load [Pa] (30mm frame)Load [Pa] (35/40mm frame)
Min DMax DMin DMax D
AIKO-A***-MAH54Dw
AIKO-A***-MAH54Db
1722*1134310350≤D≤450310350≤D≤450
AIKO-A***-MAH72Dw
AIKO-A***-MAH72Db
2278*1134430≤D≤530450≤D≤550430≤D≤530450≤D≤550
Table 4: Double glass modules clamp mounting diagram and corresponding loads, short frame (B)
Module modelModule size [mm]Load [Pa] (30mm frame)Load [Pa] (35/40mm frame)
D=W/4-100D=W/4-50
AIKO-A***-MAH54Dw
AIKO-A***-MAH54Db
1722*1134+1600/-1600D=W/4-100D=W/4-50
AIKO-A***-MAH72Dw
AIKO-A***-MAH72Db
2278*1134///
Table 5: Double glass modules clamp mounting diagram and corresponding loads, short & long frame (C)
Module modelModule size [mm]Load [Pa] (30mm frame)Load [Pa] (35/40mm frame)
D1D2D1D2
AIKO-A***-MAH54Dw
AIKO-A***-MAH54Db
1722*1134D1=W/4-100
D2=100
+1600/-1600D1=W/4-50
D2=120
+1600/-1600
AIKO-A***-MAH72Dw
AIKO-A***-MAH72Db
2278*1134////

06 Mechanical installation (continued)

6.2.3 Bolts Mounting

Modules can be secured using bolts through mounting holes on the back of the frame. Modules come standard with 4 or 8 mounting holes, matching M8 bolts. A diagram illustrates the bolt, washer, spring washer, nut, aluminum frame, and bracket. A table lists accessories: Bolt (M8*1.25, S35C), Spring washer (13.5*2.1, Mn65), Washer (16*1.7, Fe), Bracket (Q235), Nuts (M8*1.25, S35C). It is important that bolts do not fail due to deformation or corrosion. AIKO recommends washer thickness ≥1.7mm and M8 nuts/bolts, with a tightening torque of 16-20 N•m.

6.2.4 Double glass modules bolt mounting diagram and corresponding loads

Diagrams show bolt mounting configurations: outer four-hole bolt mounting (beam perpendicular to long frame, beam perpendicular to short frame) and inner four-hole bolt mounting (beam perpendicular to long frame, beam perpendicular to short frame). These are for transversal mounting.

6.2.5 Single-axis tracking system installation

AIKO 72 type modules have four M8 outer mounting holes and four M6 inner mounting holes for tracking systems. A diagram shows the module with M8 and M6 mounting hole locations.

Table 6: Double glass modules bolt mounting diagram and corresponding loads, transversal (D)
Module modelModule size [mm]Frame thickness [mm]Load [Pa] (4 inner mounting holes)Load [Pa] (4 outer mounting holes)
AIKO-A***-MAH54Dw
AIKO-A***-MAH54Db
1722*113430/35/40+5400/-2400+2400/-2400
AIKO-A***-MAH72Dw
AIKO-A***-MAH72Db
2278*113430/35/40/+5400/-2400
Table 7: Double glass modules bolt mounting diagram and corresponding loads, longitudinal (E)
Module modelModule size [mm]Frame thickness [mm]Load [Pa] (4 inner mounting holes)Load [Pa] (4 outer mounting holes)
AIKO-A***-MAH54Dw
AIKO-A***-MAH54Db
1722*113430/35/40+5400/-2400+2400/-2400
AIKO-A***-MAH72Dw
AIKO-A***-MAH72Db
2278*113430/35/40/+5400/-2400

Note: The above data is based on the static load requirements of IEC61215 standard.

07 Electrical installation

7.1 Electrical performance

Electrical performance parameters are detailed in the product specification. Standard Test Conditions (STC) for PV modules: irradiance 1,000 W/m², cell temperature 25°C, AM1.5. The maximum system voltage of AIKO modules is 1,500 V.

In series connection, the string voltage is the sum of individual module voltages. In parallel connection, the current is the sum of individual module currents. Modules in the same string must have the same product code and nominal power.

Diagrams illustrate series connection and parallel after series connection. Symbols for Overcurrent protective device, Diode, and Connector are shown.

If a module is passed through by a reverse current greater than its maximum fuse current, it shall be protected with an overcurrent protector. If more than two strings are connected in parallel, each string requires an overcurrent protector. The string voltage must not exceed the maximum system voltage. The open circuit voltage of the array shall be calculated at the minimum expected ambient temperature using the formula: Maximum system voltage > N×Voc×[1+ β *(Tmin-25)], where N is the number of modules in series, Voc is the open circuit voltage, β is the thermal coefficient of open circuit voltage, and Tmin is the lowest ambient temperature.

7.2 Cables and Connections

PV module junction boxes have IP68 protection and include connected cables and IP68 connectors. Modules have positive and negative PV wires and a plug-and-play connector. Series connection is made by connecting the positive connector of one module to the negative connector of the adjacent module. Use specialized solar cables (4 mm², UV resistant) and appropriate connectors according to local standards. AIKO recommends copper cables rated for 90°C and UV resistance. The minimum bending radius of the cable is 43mm. Cables should be run in conduits and sited away from water collection areas.

7.3 Connector

Keep connectors dry and clean. Tighten connector nuts before making connections. Do not connect when connectors are wet or abnormal. Connectors provide IP68 protection only when fully mated. Connect modules as soon as possible after installation or take steps to prevent water vapor and dust ingress. Avoid exposing connectors to direct sunlight, water, or the ground surface. Ensure all electrical connections are secure to prevent arcing and shocks ⚡. Do not mate different models of connectors.

08 Grounding

Module frames are made of anodized anticorrosive aluminum alloy and must be grounded for safety, lightning ⚡, and electrostatic protection. Grounding must ensure full contact with the interior of the aluminum alloy frame, penetrating the oxide film. Grounding devices include grounding screws, flat washers, puncture gaskets, and grounding wires (stainless steel except for wires, which are copper). Connect to the ground through an appropriate grounding electrode. Third-party grounding devices meeting local electrical installation standards may be used. Install grounding devices according to the manufacturer's manual.

Recommended grounding method: Use the grounding holes (Ø 4.2 mm) on surface C of the module frame. Connect the aluminum alloy frame to the ground using a separate grounding wire and accessories. AIKO recommends M4×12 mm grounding bolts with M4 nuts, star washers, and flat washers. Torque grounding bolts to 3~7 N•m and use 4 mm² copper wires. Unused module mounting holes can also be used for grounding. The connection sequence is: star washer, flat washer, ground wire, screw, tightened.

A diagram illustrates the grounding components and method.

09 Maintenance of PV modules

Modules shall be inspected and maintained regularly, especially within the warranty period. Report any damage or visible abnormalities to AIKO Energy customer service. Any damage or abnormalities of the module shall be reported to AIKO Energy customer service upon discovery.

9.1 Cleaning

Module power output ☀️ can be reduced by dust collection or shading. Clean dirt immediately. Cleaning frequency depends on dirt accumulation. Modules installed at an adequate tilt angle allow rainwater to clean the surfaces, reducing cleaning frequency.

Cleaning recommendations: Use a clear water-netted sponge. Do not use detergents containing acid or alkali, hair brushes, or rough surface tools. Clean in the early morning or late afternoon when light is weak and module temperature is lower.

  • Method A: High pressure water cleaning
    • Water quality: pH 6-8, calcium carbonate concentration <600mg/L. Soft water recommended. Maximum water pressure: 4MPa (40bar).
  • Method B: Compressed air cleaning
    • Recommended for cleaning soft stains like dust.
  • Method C: Wet test cleaning
    • For heavy stains, use an insulating brush, sponge, or other soft cleaning tool. Ensure tools are insulating to minimize electric shock risk and prevent scratching the glass or frame. For oil stains, use an environmentally friendly cleaner.
  • Method D: Robot cleaning
    • If using a cleaning robot for dry cleaning, the brush material must be soft plastic to avoid scratching the glass surface and aluminum alloy frame.

9.2 Visual checks of the modules

Visually check for defects such as:

  • Broken module glass.
  • Cracked or abnormal back cover.
  • Damaged junction box or broken cable.
  • Shading from foreign matter or shadows.
  • Loose or corroded bolts fixing the module to the racking (adjust or replace if necessary).
  • Module grounding status.

9.3 Checks of connectors and cables

Perform preventive examinations every six months:

  • Check if connectors are properly sealed and cables are properly fastened.
  • Check if the sealant of the junction box is cracked.

9.4 AIKO Technical Support

To request Technical Support:

  • Collect evidence of the issue (photos and measurements).
  • Be prepared to show the purchase invoice and module serial number.
  • Contact your Installer.
Models: AIKO-A445-MAH54Db Black Hole Dual Glass, AIKO-A445-MAH54Db, Black Hole Dual Glass, Hole Dual Glass, Dual Glass, Glass

PDF preview unavailable. Download the PDF instead.

Installatiehandleiding-Aiko-Energy-Double-glass Adobe PDF library 16.03 Adobe Illustrator 26.0 (Windows)

Related Documents

Preview AIKO PV Modules Installation Manual - Comprehensive Guide
Detailed installation manual for AIKO PV modules, covering electrical and mechanical installation, safety guidelines, storage, handling, and maintenance. Includes product specifications and best practices for solar panel installation.
Preview AIKO PV Module Installation Manual - Dual Glass Module
This manual provides comprehensive information on the installation and safe use of AIKO Dual Glass PV modules. It covers general information, safety precautions, storage and transportation, mechanical and electrical installation, grounding, and maintenance procedures.
Preview AIKO Neostar 2P+ 455W-475W High-Efficiency Double Glass Solar Module Datasheet
Detailed technical specifications, features, and performance guarantees for the AIKO Neostar 2P+ series of high-efficiency double glass solar modules, available in power outputs from 455W to 475W.
Preview AIKO Neostar 2P Mono-Glass Module: High-Efficiency Solar Power
Explore the AIKO Neostar 2P, a high-performance mono-glass solar module available in 450W-485W. Discover its technical features, including partial shading optimization, superior temperature coefficient, and enhanced durability for reliable solar energy generation.
Preview AIKO Neostar 2S Mono-Glass Module Datasheet (440W-470W)
Technical datasheet for AIKO Neostar 2S Mono-Glass solar modules, featuring N-Type ABC technology, power outputs from 440W to 470W, high efficiency, and a 30-year linear performance warranty.
Preview AIKO Neostar 2S Mono-Glass Module 500W-515W Datasheet
Technical specifications and performance data for the AIKO Neostar 2S mono-glass solar module, available in 500W to 515W power outputs. Features include partial shading optimization, better temperature coefficient, high temperature restriction, micro-crack resistance, higher power, lower BOS, and more aesthetic values. Includes detailed electrical characteristics, product specifications, and temperature ratings.
Preview AIKO Nebular 2P Mono-Facial Solar Module 430W-460W Datasheet
Technical datasheet for AIKO's Nebular 2P mono-facial solar modules, featuring power outputs from 430W to 460W. Details electrical characteristics, mechanical specifications, and temperature ratings.
Preview AIKO Neostar 3S54 Mono-Glass Module: 460W-490W Technical Specifications
Detailed technical specifications and features for the AIKO Neostar 3S54 Mono-Glass Module, including performance data, electrical characteristics, product specifications, and installation guidelines. Covers models from 460W to 490W.