FOGATTI Rooftop Air Conditioner
Installation and Operation Manual
Models: FA135, FA150
WARNING
This manual must be carefully read and understood before installation, adjustment, repair or maintenance. The equipment must be installed by qualified technicians. Transformation of this product is an extremely dangerous operation, which may lead to personal injury or property loss. Important: please keep this manual with the product.
Table of Contents
- 1. Safety Information
- 2. General Information
- 3. Installation Instructions
- 4. Installing ADB
- 5. Maintenance of Air Conditioner
- 6. Troubleshooting
- 7. Circuit Diagram
1 Safety Information
1.1 Safety Definitions
- DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
- WARNING: Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
- CAUTION: Indicates a hazardous situation which, if not avoided, could result in property damage and minor or moderate injury.
- NOTICE: This symbol indicates important information where there is no risk to people or property.
1.2 Information Introduction
This air conditioner (hereinafter referred to as "unit" or "product") is designed and intended for installation on the roof of a Recreational Vehicle (hereinafter referred to as Marine rooftop Air conditioner) during or after the time it is manufactured.
This unit can be installed by one person with brief help from additional personnel. Use these instructions to ensure a properly installed, and properly functioning product.
FOGATTI reserves the right to modify appearances and specifications without notice.
This manual has safety information and instructions to help you eliminate or reduce the risk of accidents and injuries.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
1.3 Supplemental Directives
Read and follow all safety information and instructions to avoid possible injury or death.
Read and understand these instructions before installing, using, servicing, or performing maintenance on this product.
Incorrect installation, operation, servicing, or maintaining of this product can lead to serious injury. Follow all instructions. The installation MUST comply with all applicable local and national codes, including the latest edition of the following standards:
U.S.A.
- ANSI/NFPA70, National Electrical Code (NEC)
- ANSI/NFPA1192, Recreational Vehicles Code
Canada
- CSA C22.1, Parts I & II, Canadian Electrical Code
- CSA Z240 Marine rooftop Air conditioner Series, Recreational Vehicles
1.4 General Safety Messages
Failure to obey the following warnings could result in death or serious injury:
- This product MUST be installed / serviced by a qualified service technician.
- Do NOT modify this product in any way. Modification can be extremely hazardous.
- Do NOT add any devices or accessories to this product except those specifically authorized in writing by FOGATTI.
WARNING
During the use of this product, due to the great change of air temperature in the vehicle, when the temperature drops rapidly, part of condensate will adhere to the surface of objects near the air outlet, which is a normal phenomenon. After the air conditioner works normally for a certain period, it will be automatically dried and detached from the surface of objects. Therefore, when the air conditioner works, please close the doors and windows as much as possible to reduce the coagulation of water vapor on the surface of objects inside the vehicle.
The appliance shall be installed in accordance with national wiring regulations.
2 General Information
2.1 Table - Unit Data
- For wire length over 24 ft., consult the National Electrical Code for proper sizing.
- FOGATTI gives GENERAL guidelines for generator requirements. These guidelines come from experiences people have had in actual applications. When sizing the generator, the total power usage of your Marine rooftop Air conditioner must be considered. Keep in mind generators lose power at high altitudes and from lack of maintenance.
- CIRCUIT PROTECTION: Time Delay Fuse or Circuit Breaker Required.
2.2 Roof Requirements
- A 14-1/4" x 14-1/4" (±1/8") square opening (hereinafter referred to as "roof opening") is required for installing this unit. This opening is part of the return air system of the unit and MUST be finished in accordance with NFPA1192.
- Roof construction with rafters/joists support frames on a minimum of 16 inch centers.
- Minimum of 1.5 inches and maximum of 6 inches distance between roof to ceiling of Marine rooftop Air conditioner.
2.3 Introduction of Air Conditioner
The design and installation of this machine is suitable for RV to improve its internal temperature and provide a comfortable environment.
2.4 User Guide
The performance of air conditioner is related to the heating condition of insulation box of RV itself. Users can take some preventive measures to reduce heat entry, so as to improve the refrigeration performance of air conditioning equipment.
When outdoor temperature is high, the following methods can be adopted to reduce the heat entry of RV and improve work efficiency:
- Park the RV in a cool place.
- Strengthen thermal insulation of the compartment, remove or block the opening in the vehicle.
- Block the window with shade curtains (shutters or hanging curtains).
- Close doors and windows or avoid frequent opening and closing of them.
- Avoid using heating devices inside the vehicle.
Turn on the air conditioner in advance to achieve better effect. When indoor or outdoor temperature is high, set the air conditioner in cooling mode and turn on high wind speed will bring the performance of air conditioner into full play.
WARNING
The manufacturer will not be responsible for any damage arising from condensation on the ceiling or the surface of other objects caused by the condensate of this product.
2.5 Tools and Materials
Included Parts | Quantity |
---|---|
Wall mounted control user's guide | 1 |
Rooftop air conditioner installation and operation manual | 1 |
Air conditioning panel | 1 |
Long screw (5.5*203.5mm) | 4 |
Aluminum foil tape (40*10mm) | 1 |
Screw (4.2*30mm) | 8 |
Recommended Tools
- Angle Grinder
- Cutting Disc for Metal
- Extension Cord
- Drill
- Phillips Screwdriver
- Side Cutters
- Automotive Staple Remover
- Impact Gun
- Screwdriver Bit Set
- Hole Saw Set
- Self Tapping Screws
- Flat Head Screwdriver
- Pliers
2.6 Dimensions
NOTICE
The images used in this document are for reference purposes only. Measurements may vary ±0.38 in. (10 mm).
Rooftop Air Conditioner
A: 29.5 in (750 mm)
B: 14.2 in (360 mm)
C: 27.6 in (700 mm)
Air conditioning panel (ADB)
A: 21.1 in (535 mm)
B: 22.8 in (580 mm)
2.7 Main Parameters
MODEL | FA135 | FA150 | FA150 |
---|---|---|---|
Part No. | / FAA135WA FAA135BA | FAA150WA FAA150BA | FAA150WD FAA150BD |
Nominal capacity | 13,500 BTU/hr | 15,000 BTU/hr | 15,000 BTU/hr |
Power Supply | 115/60 VAC/Hz | 115/60 VAC/Hz | 115/60 VAC/Hz |
Rated current for cooling | 13.6 A | 15.5 A | 15.5 A |
Rated current for heating | / | / | 15.7 A |
Input needed for cooling | 1510 W | 1600 W | 1600 W |
Input of customized heat | / | / | 1800 W |
Air volume (high speed) | 28251 ft³/h | 28251 ft³/h | 28251 ft³/h |
Maximum design pressure | 450 PSIG | 450 PSIG | 450 PSIG |
Minimum design pressure | 236 PSIG | 236 PSIG | 236 PSIG |
Refrigerant charged | R-410A | R-410A | R-410A |
Refrigerant charged | 16 oz | 16 oz | 16 oz |
Minimum Wire Size* 12 AWG Copper Up to 24' | / | 12AWG copper wire, length not exceeding 8m. | 12AWG copper wire, length not exceeding 8m. |
AC Circuit Protection *** | Installer Supplied | 20A fuse or fuse | 20A fuse or fuse |
WARNING
Please use the connecting wires complying with the national regulations. During sizing of the generator, the total power usage of RV must be considered.
NOTICE
Tip: the generator will lose power due to high altitude and lack of maintenance. Circuit protection: please use Time Delay Fuse or Circuit Breaker.
3 Installation Instructions
3.1 Choosing Proper Location For Unit
This unit is specifically designed for installation on the roof of an Marine rooftop Air conditioner. When determining your cooling requirements, the following should be considered:
- Size of Marine rooftop Air conditioner;
- Window area (increases heat gain);
- Amount of insulation in walls and roof;
- Geographical location where the Marine rooftop Air conditioner will be used;
- Personal comfort level required.
Normal locations-The unit is designed to fit over an existing roof vent opening. Other locations-When no roof vent is available or another location is desired, the following is recommended:
- For one unit installation: The unit should be mounted slightly forward of center (front to back) and centered from side to side.
- For two unit installations: Install one unit 1/3 and one unit 2/3's from front of Marine rooftop Air conditioner and centered from side to side. It is preferred that the unit be installed on a relatively flat and level roof section measured with the Marine rooftop Air conditioner parked on a level surface. The maximum inclination Angle is 8°.
3. Maintain structural integrity. Otherwise damage to product and/or Marine rooftop Air conditioner could occur. The roof must be designed to support 130 pounds when Marine rooftop Air conditioner is in motion. Normally a 200 lb. static load design will meet this requirement.
4. Check inside the Marine rooftop Air conditioner for air distribution box (hereinafter referred to as "ADB") obstructions (i.e. door openings, room dividers, curtains, ceiling fixtures, etc.).
Diagram showing roof opening considerations:
- Do Not Cut Roof Structure Or Rafters
- Good-rafters Supported By Cross Beams
- Good Location Between Roof Rafters
Dimensions for roof opening:
- 1: 12 in. (305 mm)
- 2: 4 in. (102 mm)
- 3: 4 in. (102mm)
- 4: Keep these air flow areas free of obstructions
- 5: Roof opening
- 6: Center line of unit
Frame opening so it won't collapse when bolting down unit.
Leave Access For Power Supply Wiring.
Diagram showing ADB opening:
- 1/4" Min.
- 15" Min at front of opening
3.2 Roof Preparation
WARNING: FIRE OR ELECTRICAL SHOCK HAZARD. Make sure there are no obstacles (wires, pipes, etc.) inside Marine rooftop Air conditioner's roof/floor/walls. Shut OFF gas supply, disconnect 120 Vac power from Marine rooftop Air conditioner, and disconnect positive (+) 12 Vdc terminal from supply battery BEFORE drilling or cutting into Marine rooftop Air conditioner. Failure to obey these warnings could result in death or serious injury.
Opening Requirements - Before preparing the ceiling opening, read all of the following instructions before beginning the installation.
3.2.1 Creating a New Roof Opening
If an existing roof vent opening will NOT be used a roof opening MUST be cut through the roof and ceiling of the Marine rooftop Air conditioner. This opening MUST be located between the roof reinforcing members. See "2.2 Roof Requirements".
Diagram showing roof opening and sealant:
- 1: Roof Vent
- 2: Opening
- 3: Residual Sealant
If the opening is less than 14-1/8" x 14-1/8", it must be enlarged. See "2.2 Roof Requirements".
- Carefully mark and cut the required roof opening. See "2.2 Roof Requirements".
- Maintain structural integrity. Otherwise damage to product and/or Marine rooftop Air conditioner could occur.
Diagram showing measurements for new opening:
- 1: Roof Opening
- 2: 13.75 in. (349 mm)
- 3: 13.75 in. (349 mm)
CAUTION
NEVER create a low spot on Marine rooftop Air conditioner roof. Otherwise, water will pool and could cause a leak.
Using the roof opening as a guide, cut the matching hole in the ceiling. The opening created must be framed to provide adequate support and prevent air from being drawn from the roof cavity. Framing stock 3/4" or more in thickness must be used. Remember to provide an entrance hole for power supplies at the front of the opening.
3.2.2 Using an Existing Roof Opening
- Unscrew and remove the roof vent.
- Remove all caulking compound around opening.
- Seal all screw holes and seams where the roof gasket will be located. Use a good grade of all weather sealant.
3.3 Wiring Requirements
Route a copper, with ground, 120 Vac supply wire from the time delay fuse or circuit breaker box to the roof opening. Use a listed/certified non metallic - sheathed single strand cable.
If vent fan was removed, the existing wire may be used provided it is of proper type, size, location, and correctly fused.
- This supply wire must be located in the front portion of the roof opening.
- The power MUST be on an appropriately sized separate time delay fuse or circuit breaker. See "2.1".
- Make sure that at least 15" of supply wire extends into the roof opening. This ensures an easy connection at the junction box.
- Protect the wire where it passes into the opening with approved method.
3.4 Placing Unit On Roof
- Remove the unit from the carton and discard carton.
- LIFTING HAZARD. Use proper lifting technique and control when lifting product. Failure to obey this caution could result in injury. Place unit on the roof.
- Do NOT slide unit. Otherwise, damage to gasket (on bottom of unit) may occur, and could cause a leak. Lift and place the unit over the prepared opening using the gasket on the unit as a guide.
- Place the ADB kit inside the Marine rooftop Air conditioner. This box contains mounting hardware for the unit and will be used inside the Marine rooftop Air conditioner.
This completes the outside work. Minor adjustments can be done from inside the Marine rooftop Air conditioner if required.
3.5 Installation Preparation
Check gasket alignment of the unit over the roof opening and adjust if necessary. Unit may be moved from below by slightly lifting.
Diagram showing unit placement and gasket alignment:
- Center unit from below
- 1: Roof gasket
4 Installing ADB
- Install the wall control panel and route the cable into the interlayer of the air conditioner mounting port. (Mechanical air conditioners can skip this step)
Diagram of ADB installation components:
- 1: Mounting Bolt *4
- 2: Duct Divide
- 3: Control Box
- 4: ADB
- 5: Ceiling Template
Diagram showing front and rear views of ADB components:
- 1: Base pan
- 2: Duct divider
- 3: Black side to front
- 4: 5-5/8" From back of roof opening
- Determine the height of partition board.
- Measure ceiling thickness.
- Carefully install the duct divider in the roof opening 5-5/8" from back of roof opening.
Diagram showing electrical connections:
- 1: Electrical cord
- 2: Control panel cable
Remove Rows Starting Here
- Fix the electric control box on the top template and align it with the return air end of the host. Fix the top template on the ceiling with the fixing screws.
- Wiring: Connect the main cable and wall control cable to the corresponding terminals of the electric control box then arrange the excess cable.
- Install ADB panel. Cover the top template with ADB, align the air inlet with the host air return port, and fix the screws in sequence.
Diagram showing air inlet and screws:
- 1: Air inlet
- 2: Screw *6
- Place filter in return air vent grille. It may already be installed on some units.
Diagram showing filter and return air vent grille:
- 1: Filter
- 2: Return air vent grille
8. Mechanical ADB also requires two temperature control knobs.
Diagram showing air outlet baffles:
- Air outlet baffle
- Air outlet baffle
- Air outlet baffle
- Air outlet baffle
CAUTION
Please open the air outlet when the air conditioner is running, and the air volume can be adjusted by adjusting the angle of the air outlet baffle.
5 Maintenance of Air Conditioner
5.1 Cleaning of Air filter
Remove the filter screen behind the interior panel (press the left and right buttons of the decorative panel, and the decorative panel can be removed), clean with water, and then re install after drying.
Diagram showing filter removal:
- Return Air vent grille
- Filter
WARNING
It is forbidden to operate the air conditioner without the air filter, otherwise, the evaporator coil will be defiled and the service life of air conditioner will be affected.
5.2 Panel Surface Cleaning
Clean the outer surface of the panel with soft cloth dipped in neutral detergent. Do not use polishing or cleaning powder.
5.3 Fan Motor
The fan motor has been lubricated during production procedure and does not need special maintenance.
6 Troubleshooting
If the air conditioning equipment cannot work normally, please carry out inspection as follows to remove the faults:
- Check whether the fuse of air conditioning equipment or leakage circuit breaker of the RV is turned on.
- If the air conditioner is powered by a generator, please first confirm whether the generator power matches the air conditioner, whether the generator runs normally and generates electricity, and whether voltage output of the generator is stable.
- If the RV is connected to the main supply, please make sure that the specification of power line matches the operating load of this product and that there is power supply. Check whether the mains voltage meets related requirements (the operating voltage of air conditioner is 115V).
- Check whether the connecting wires of air conditioner are inserted in place and connected in good condition. If the air conditioner still cannot work normally after the above inspection, please contact the factory for further help.
Code | Cause | Solution |
---|---|---|
E1 | Fault of indoor temperature sensor | 1. Check the sensor butt joint 2. Replace the temperature sensing head |
E2 | Fault of indoor coil temperature sensor | 1. Check the sensor butt joint 2. Replace the temperature sensing head |
E5 | Communication failure | 1. Check the connecting line between the power board and the controller by wire 2. Replace the electric control board or wire controller |
E6 | Dial switch error | Check the dial switch |
CAUTION
The equipment must be repaired by professional personnel.
7 Circuit Diagram
7.1 Mechanical type
Diagram of mechanical type circuit:
- MOTOR, COMPRESSOR, FAN, HERM
- 6 PIN CONN: 1, 2, 3, 4, 5, 6
- Wires: GRN/YEL, BRN, WHT, BLK, YEL, RED
Diagram of electrical connections for mechanical type:
- 115 VAC 60 Hz 1 PH USE COPPER CONDUCTORS ONLY
- FIELD WIRING, FACTORY WIRING, LINE SPLICE
- ELEC CONN FROM A/C
- ROTARY SWITCH: BLK, WHT, BLU, GRY
- THERMOSTAT: C,4 H,6 L,3
7.2 Wire control model with cooling and heating
Diagram of wire control model circuit:
- MOTOR, COMPRESSOR, FAN, HERM, PTC
- 3 PIN CONN: WHT, BLK
- 6 PIN CONN: 1, 2, 3, 4, 5, 6
- Wires: GRN/YEL, BRN, WHT, BLK, YEL, RED, GRY
Diagram of electrical connections for wire control model:
- 115 VAC 60 Hz 1 PH USE COPPER CONDUCTORS ONLY
- FIELD WIRING, FACTORY WIRING, LINE SPLICE
- ELEC CONN FROM A/C
- ROTARY SWITCH: BLK, WHT, BLU, GRY
- THERMOSTAT: C,4 H,6 L,3
7.3 Wire Controller type
Diagram of wire controller type circuit:
- MOTOR, COMPRESSOR, FAN, HERM
- 6 PIN CONN: 1, 2, 3, 4, 5, 6
- Wires: GRN/YEL, BRN, WHT, BLK, YEL, RED
Diagram of electric control for wire controller type:
- ELECTRIC CONTROL, WIRE CONTROLLER
- FREEZE SENSOR, TEMPERATURE SENSOR
- IPT, CN6, RT
- K1 RELAY
- Wires: BLU, BLK, WHT, GRN/YEL, BLK(LINE)
- CONDUCTORS ONLY USE COPPER 115VAC 60Hz
7.4 Mechanical model with cooling and heating
Diagram of mechanical model circuit:
- MOTOR, COMPRESSOR, FAN, HERM, PTC
- 3 PIN CONN: WHT, BLK
- 6 PIN CONN: 1, 2, 3, 4, 5, 6
- Wires: GRN/YEL, BRN, WHT, BLK, YEL, RED
Diagram of electric control for mechanical model:
- ELECTRIC CONTROL, WIRE CONTROLLER
- PTC 1500W
- TEMPERATURE SENSOR
- IPT, CN6, RT
- K1 RELAY
- Wires: BLU, BLK, WHT, GRN/YEL, BLK(LINE)
- CONDUCTORS ONLY USE COPPER 115VAC 60Hz
Service details are available at www.fogattiliving.com
WARNING: Risk of electric shock can cause injury or death: disconnect all remote electric power suppliers before servicing.