Honeywell C7232A,B Sensor and Controller

Carbon Dioxide Sensor

Application

The C7232 Sensor and Controller is a stand-alone carbon dioxide (CO2) sensor designed for use in determining ventilation necessity with HVAC controllers. It measures the CO2 concentration in ventilated spaces or ducts and is utilized in ventilation and air conditioning systems to regulate the amount of fresh outdoor air supplied, thereby maintaining acceptable CO2 levels within a space.

Features

Specifications

Models: C7232 Sensor and Controller. A stand-alone carbon dioxide (CO2) sensor with two jumper-adjustable outputs (one analog and one SPST relay).

C7232A: Wall mount model.

C7232B: Duct mount model.

Note: Models are available with or without a 4-digit LCD indicating the current CO2 concentration.

Dimensions

C7232A: See Figure 1. Figure 1 illustrates the dimensions for the C7232A wall mount model, showing its compatibility with a standard single-gang junction box and providing key measurements: 3-5/32" (80mm) H, 2-3/8" (60mm) W, 1" (25mm) D.

C7232B: See Figure 2. Figure 2 shows C7232B duct mount dimensions, including a sampling tube, with key measurements: 5-5/8" (142mm) H, 1-5/8" (41mm) W, 8" (203mm) L (incl. tube).

Sensor Performance Ratings

Response Time: 2 minutes.

Carbon Dioxide Sensor

Operation: Non-dispersive infrared (NDIR).

Sampling: Diffusion.

Range: 0 to 3000 ppm ±5% and ±50 ppm.

Annual Drift: 20 ppm (nominal).

Calibration Interval: Five years.

Electrical Ratings

Power Supply: 24 Vac ±20%, 50/60 Hz (Class 2).

Maximum Power Consumption: 3W.

Peak Current (at 20 ms): 600 mA.

Relay

Configuration: Shipped Normally Open (N.O.), configurable with software.

Contact Rating: 1A at 50 Vac/24 Vdc.

Minimum Permissible Load: 1 mA at 5 Vdc.

Linear Analog Output

Voltage: 0/2-10 Vdc (resistive load greater than 5000 ohms).

Current: 0/4-20 mA (resistive load less than 500 ohms).

Outputs (Jumper Adjustable)

Analog: 0-10 Vdc (Default: 2-10 Vdc, 500 to 1500 ppm).

Relay: Normally Open SPST (Default: Close at 1000 ppm).

Ambient Ratings

Temperature:

Operating: +32°F to +122°F (0°C to +50°C).

Storage: -4°F to +158°F (-20°C to +70°C).

Relative Humidity (non-condensing): 0 to 95 percent.

CO2 Pressure Dependence: 1.4% change in reading per 1 kPa deviation from 100 kPa.

Connections

Wiring:

C7232A: 20-gauge cable with six 8-inch leadwires.

C7232B: 20-gauge cable with six 6-inch leadwires.

Mounting

C7232A: Vertical surface mounting with a standard single-gang junction box.

C7232B: Sheet metal duct mounting with a sampling tube.

Automatic Background Calibration (ABC) default: On.

Approvals

Underwriters Laboratories Inc. Component Recognition: UL94-5V, File No. E191465.

CE Marking.

C7232A: NEMA1 rated.

C7232B: NEMA3 rated.

Accessories

32002181-001: Zero Calibration and Service Kit.

CO2 Range Jumper Settings

Jumper SW1Jumper SW2CO2 Range Setting
ONON0 to 1000 ppm
ONOFF0 to 2000 ppm
OFFON500 to 1500 ppm
OFFOFF500 to 2000 ppm
Relay SwitchingON800 ppm (contacts close)
Relay SwitchingOFF1000 ppm (contacts close)
Relay Switching(Default)1200 ppm (contacts close)

Note: Relay switching points are set by jumpers. When the level reaches this value, the contacts close; when the level drops 100 ppm below this value, the contacts open.

Output Signal Jumper Settings

AN1 and AN2Output TypeRange
Set as ON (Default)Voltage0-10 Vdc
Set as OFFVoltage2-10 Vdc
Set as ON (Default)Current0-20 mA
Set as OFFCurrent4-20 mA

Note: Jumpers AN1 and AN2 should be set identically. The factory default setting is ON for both. The high and low values of the CO2 range are not affected by the output signal range.

C7232 Wiring Connections

Wire ColorDesignationFunction
RedG+24 Vac Hot
BlackG024 Vac Common
YellowOUT1Analog Output Signal
BrownMAnalog Output Common
OrangeNORelay Output Normally Open
GreenCOMRelay Output Common

Figure 6 is a wiring diagram for the C7232, detailing power connections (Red for 24 Vac Hot, Black for 24 Vac Common) and output signal connections (Yellow for Analog OUT1, Brown for Analog Common, Orange for Normally Open Relay, Green for Relay Common). It includes a note regarding the requirement for disconnect means and overload protection.

Ordering Information

To purchase replacement and modernization products, refer to the TRADELINE® Catalog or price sheets from your TRADELINE® wholesaler or distributor for the complete ordering number.

For additional questions, further information, or comments on products or services, please write or phone:

  1. Your local Home and Building Control Sales Office (refer to your phone directory).
  2. Home and Building Control Customer Logistics, Honeywell Inc., 1885 Douglas Drive North, Minneapolis, Minnesota 55422-4386. Phone: (612) 951-1000.
  3. In Canada: Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.

International Sales and Service Offices are located in all principal cities worldwide. Manufacturing facilities are located in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, and U.S.A.

Installation

When Installing this Product:

  1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
  2. Verify that the ratings provided in the instructions and on the product are suitable for your application.
  3. The installer must be a trained and experienced service technician.
  4. After installation, perform a product checkout as detailed in these instructions.

IMPORTANT: All wiring must comply with applicable codes, ordinances, and regulations.

CAUTION: Health Hazard

Improper use can create dangerous situations. This device is intended for sensing carbon dioxide only. For life-safety applications, it should function only as a secondary or lesser device.

CAUTION: Electrical Shock or Equipment Damage Hazard

Can shock individuals or short equipment circuitry. Disconnect power supply before installation.

CAUTION: Equipment Damage Hazard

Electrostatic discharge can short equipment circuitry. Ensure you are properly grounded before handling the unit.

C7232A Cover Removal/Replacement

C7232A Cover Removal (See Figure 3)
  1. Remove the button head socket cap screw and set it aside.
  2. Insert the head of a small screwdriver into the slot located at the center and near the top of the cover.
  3. Gently pull the handle down towards the bottom of the device until a small gap appears between the subbase and the cover.
  4. Remove the screwdriver and pull the cover straight down until it reaches a stop.
  5. Pull the cover straight off the subbase.
C7232A Cover Replacement
  1. Feed the wires through the opening in the subbase.
  2. Place the cover, with a small gap at the top, flat on top of the subbase.
  3. When the cover rests flat on the subbase, slide it straight up until it latches in place.

Location and Mounting

C7232 Sensors can be mounted directly on a wall, sheet metal duct, or a panel. When planning the installation, ensure sufficient clearance for maintenance and service. Mount the sensor in a well-ventilated area.

NOTES: Do not install the sensor where it may be affected by:

Wall Mounting

The C7232 Wall Mount models can be attached using two or four screws:

  1. Remove the C7232 cover.
  2. Mount the subbase to the wall using washers and two or four screws (not supplied), appropriate for the wall material.
  3. NOTE: For mounting on a junction box, refer to Figure 4. Figure 4 depicts C7232A junction box mounting, showing the subbase attached to a conduit box.
  4. Replace the cover.

Duct Mounting (See Figure 5)

  1. Place the gasket on the aspiration tube.
  2. IMPORTANT: Ensure the largest tab at the tube control end is positioned at the top.

  3. Insert the tube into the duct and attach using screws and washers.
  4. IMPORTANT: Leakage into the duct or the C7232 box cover from the room can skew sensor readings. Ensure the box cover and duct seal completely.

  5. Place the o-ring on the tube end and mount the control to the tube. Figure 5 illustrates C7232B duct mounting, showing aspiration tube insertion and control unit attachment.

Wiring

The device is shipped with default output settings as shown in Tables 1 and 2. Set the jumpers and wire the device according to Table 3 and Figure 6.

CAUTION: Electrical Shock or Equipment Damage Hazard

Can shock individuals or short equipment circuitry. Disconnect power supply before installation.

CAUTION: Equipment Damage Hazard

Electrostatic discharge can short equipment circuitry. Ensure you are properly grounded before handling the unit.

IMPORTANT:

Calibration

To calibrate the sensor:

  1. Using the 32002181-001 Calibration Kit, eliminate the CO2 gas.
  2. IMPORTANT: Any CO2 present during calibration will skew the sensor zero level, resulting in incorrect CO2 level reports.

  3. Once the sensor stabilizes, use a screwdriver to connect the two MENU soldering pads.
  4. The display should indicate "CAL".
  5. Execute the zero calibration by connecting the two ENTER soldering pads.
  6. The display should return to showing the measured CO2 level.

Checkout

Perform a quick test of the unit while powered:

  1. Stand close to the unit and breathe air into the sensor.
  2. Check the CO2 level registered by the controller to ensure a significant rise.
  3. When connected to a damper in a ventilation system, the controller typically signals an increase in air flow.

PDF preview unavailable. Download the PDF instead.

C7232-V Acrobat Distiller 4.0 for Windows FrameMaker 5.5.6p145

Related Documents

Preview Honeywell MultiRAE Portable Gas Monitor: Advanced Six-Gas Detection
Discover the Honeywell MultiRAE, an advanced portable gas detector with six-gas capability and advanced VOC detection. Learn about its features, applications in industrial hygiene, personal protection, and hazardous material response, and technical specifications.
Preview Honeywell MultiRAE Portable Gas Detector - Technical Specifications and Features
Detailed specifications and features of the Honeywell MultiRAE, a wireless, portable six-gas detector with advanced VOC detection capabilities. Covers applications, technical data, sensors, and safety certifications.
Preview Honeywell XNX Universal Transmitter Technical Manual
This technical manual provides comprehensive information for the Honeywell XNX Universal Transmitter, a versatile gas detection system. It covers installation, operation, maintenance, and calibration procedures for detecting toxic, flammable, and oxygen depletion gas hazards using catalytic bead, electrochemical (EC), and infrared (IR) sensor technologies. The manual details communication options including HART, Modbus, and Foundation Fieldbus protocols.
Preview Honeywell C7089 Outdoor Sensor: Installation and Operation Guide
Detailed installation and operation guide for the Honeywell C7089 Outdoor Sensor, compatible with TH8000 and TH7000 thermostats. Includes specifications, wiring, and performance verification.
Preview Honeywell BW™ RigRat Portable Multi-Gas Area Monitor Datasheet
Datasheet detailing the Honeywell BW™ RigRat portable multi-gas area monitor, highlighting its advanced features, benefits, technical specifications, and safety certifications for industrial gas detection applications.
Preview Honeywell MultiRAE Portable Gas Detector: Features and Specifications
Discover the Honeywell MultiRAE, an advanced wireless portable gas detector for VOCs and other gases. Learn about its versatile applications, key features, benefits, and technical specifications for industrial hygiene, personal protection, and hazardous material response.
Preview Honeywell SS41F6 Hall-Effect Sensor IC Installation Instructions
Detailed installation instructions for the Honeywell SS41F6 High Voltage and ESD Protection Bipolar Hall-Effect Digital Position Sensor IC, including performance specifications, magnetic characteristics, and safety warnings.
Preview Honeywell MultiRAE Advanced VOC and Toxic Gas Detector
The Honeywell MultiRAE is a portable multi-gas detector with advanced VOC detection capabilities. It supports up to 25 intelligent, interchangeable sensor options for various applications including industrial hygiene, personal protection, leak detection, and hazardous response. This document outlines its features, specifications, and applications.