Wired Thermostat, 230V

EASY230W / EASYBATW

EASY230B / EASYBATB

Quick Guide

Ver. 3 Release date: I 2024
Soft: v0.6

Producer: Engo Controls S.C. 43-262 Kobielice
4 Rolna St. Poland

Distributor: QL CONTROLS Sp z o.o. Sp. k.
43-262 Kobielice 4 Rolna St. Poland

www.engocontrols.com

Wired, non-programmable thermostat, battery powered (2xAAA) or 230V AC powered. It is used for wired control of heating or cooling devices and systems. It works by maintaining comfortable conditions in the room, in line with the setpoint temperature set by the user. It is connected directly to a heat source or wiring centre. For a better fit, the model is available in two colors. Safe, reliable, easy to use.
Product Compliance
This product complies with the following EU Directives: 2014/53/EU, 2011/65/EU
Technical Informations

Power supply Max current

230V or 2xAAA batteries 3 (1) A

Temperature range Display temperature accuracy
Control algorithm Communication Output control IP protection class

5 ­ 35°C 0,1°C TPI or Hysteresis (±0.2°C to ±2°C) Wired COM / NO (voltage-free) IP30

Dimension [mm]

80 x 80 x 22 mm

Connection description for EASY230W / EASY230B

a) Connection diagram for gas boiler

AC 230V L

L L

EASY230W COM

EASY230B

NO

N

N

N

b) Connection diagram to pump / actuator

AC 230V L
L

EASY230W COM

MAX

EASY230B

3(1)A

NO

N

N

c) Connection diagram to the control box

EASY230W EASY230B
COM NO NL

BOILER CONNECTION* BOILER CONNECTION*

Connection description for EASYBATW / EASYBATB

AC 230V
a) Connection diagram L

for gas boiler

EASYBATW

EASYBATB

L

3V

COM

2 xAAA

NO

N

N

b) Connection diagram to pump / actuator

AC 230V L

EASYBATW EASYBATB

3V

COM

MAX

2 xAAA

3(1)A

NO

N

c) Connection diagram to the control box

EASYBATW EASYBATB
3V 2 xAAA
COM NO

N L SL1
1 - 8 Zones ECB08M230
control box N SL1

N L SL1
1 - 8 Zones ECB08M230
control box N SL1

Legend:

Boiler - Boiler connection* - Boiler's contacts for ON/OFF thermostat (according to the boiler's instructions)
Pump
Valve

L, N - power supply COM, NO - voltage-free output SL1 - 230V control input in the control box
- fuse

Description of the LCD display + description of the buttons

SWITCH (MODE SELECTION):
12

HEATING

OFF

3

COOLING

4

1

2

1. Current / set room temperature 2. Temperature unit 3. Heating mode icon 4. Cooling mode icon

Proper thermostat location

1. "MINUS" button 2. "PLUS" button

For the thermostat to work properly, it must be installed in a suitable place. Preferably approx. 150 cm above floor level, away from sources of heat or cold. In addition, the thermostat should not be installed behind curtains or other obstacles or in places with high humidity, as this will prevent an accurate measurement of the temperature in the room. It is not recommended to install the thermostat on an outside wall, in a draft or in a place where it will be exposed to direct sunlight.

Lock / Unlock the thermostat's keys

To lock the keys on the thermostat, press and hold simultaneously
- and + buttons for 7
seconds. After the screen appears, release the keys. Thermostat is locked.

To unlock the keys on the thermostat,

press and hold simultaneously

- and + buttons for 7

seconds. After the screen appears,

7 SEC

7 SEC release the keys. Thermostat is unlocked.

Installer parameters

0

MAIN SCREEN

To enter the service menu, press and hold ,,MINUS"and,,PLUS"buttons for 5 seconds.

-
5 SEC

1

CHOOSE A CONTROL ALGORITHM

UFH - underfloor heating

RAD - radiator heating

ELE - electric heating

H - hysteresis in the range from 0,4°C to 4,0°C

Example: H = 0,4°C = ±0.2°C

-

2

MIN. TEMP SETPOINT LIMIT

Set the minimum temperature

setpoint limit.

-

3

MAX. TEMP SETPOINT LIMIT

Set the maximum temperature

setpoint limit.

-

4

TEMPERATURE CALIBRATION

Displayed (measured) temperature can be

calibrated in steps of 0.1°C

(from -3.5°C to + 3.5°C).

-

5

BATTERY STATUS*

Check the current battery status (%).

*only for battery version

-

6

OUTPUT CONTROL

Select whether the thermostat output has

to work as NO = Normally Open

or NC = Normally Closed.

-

7

RESET

Reset thermostat settings

to default values.

WARNING!

After entering the service menu, use - or + buttons to choose parameter.

For the parameter selection to be confirmed, wait 3 seconds.

The screen will appear with the settings that you can change with

- or + buttons.

Wait 3 seconds for the selection to be confirmed.

+

The thermostat will go to the home screen.

5 SEC

WAIT 3 SEC
+

-
...

+
...

WAIT 3 SEC

-

+

+
WAIT 3 SEC

-

+

+

WAIT 3 SEC
+

-

+

WAIT 3 SEC
+

WAIT 3 SEC
+

-

+

WAIT

-

+

3 SEC

