Phoenix Contact IL MOD BK DI8 DO4-PAC Inline Bus Coupler

Phoenix Contact IL MOD BK DI8 DO4-PAC Inline Bus Coupler

Inline, bus coupler, Modbus/RTU, D-SUB 9 socket, digital inputs: 8, 24 V DC, digital outputs: 4, 24 V DC, 500 mA

Data sheet 7258_en_06. Published: 2018-06-15

1 Description

The bus coupler with integrated I/Os is intended for use within a Modbus RTU/ASCII network and represents the link to the Inline I/O system. Up to 61 Inline devices can be connected to the bus coupler. The bus coupler supports a maximum of 8 PCP devices.

Features

Valid from firmware version 1.03.

WARNING: Explosion hazard when used in potentially explosive areas. When using the terminal in potentially explosive areas, observe the corresponding notes. This data sheet is only valid in association with the IL SYS INST UM E user manual.

Make sure you always use the latest documentation. It can be downloaded at: phoenixcontact.net/product/2878696

3 Ordering Data

Main Product

Description Type Order No. Pcs./Pkt.
Inline, Bus coupler, Modbus/RTU, D-SUB-9 female connector, Digital inputs: 8, 24 V DC, connection method: 3-wire, Digital outputs: 4, 24 V DC, 500 mA, connection method: 3-wire, transmission speed in the local bus: 500 kbps / 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields IL MOD BK DI8 DO4-PAC 2878696 1

Accessories

Description Type Order No. Pcs./Pkt.
Quick mounting end clamp for NS 35/7,5 DIN rail or NS 35/15 DIN rail, with marking option, width: 9.5 mm, color: gray (Mounting) CLIPFIX 35 3022218 50
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems: Laser printer, mounting type: insert, lettering field size: 62 x 46 mm (Marking) ESL 62X46 0809502 5
Labeling field, width: 48.8 mm (Marking) IB IL FIELD 8 2727515 10
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems: Laser printer, mounting type: insert, lettering field size: 62 x 10 mm (Marking) ESL 62X10 0809492 1
Labeling field, width: 12.2 mm (Marking) IB IL FIELD 2 2727501 10
Connector set, for Inline bus coupler with I/Os mounted in rows (Connector/Adapter) IL BKDIO-PLSET 2878599 1
D-SUB connector, 9-pos., male connector, two cables to be fed in at 35°, bus system: for Inline Modbus RTU/ASCII bus coupler termination resistance can be connected via slide switch, pin assignment: 3, 5, 6, 8; screw connection terminal blocks (Connector/Adapter) SUBCON-PLUS-MODBUS/ IL/BK 2310808 1

Documentation

Type Order No. Pcs./Pkt.
Application note, English, Modbus information for the IL MOD BK DI8 DO4-PAC Inline bus coupler AH EN IL MOD BK DI8 DO4-PAC - MODBUS -
User manual, English, Automation terminals of the Inline product range IL SYS INST UM E -
Application note, German/English, I/O modules at bus couplers AH IL BK IO LIST -
Application note, English, Inline terminals for use in zone 2 potentially explosive areas AH EN IL EX ZONE 2 -

4 Technical Data

Dimensions (nominal sizes in mm)

Width: 80 mm

Height: 119.8 mm

Depth: 71.5 mm

Note on dimensions: Specifications with connectors

General Data

Colorgreen
Weight320 g (with connectors)
Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20
Protection classIII, IEC 61140, EN 61140, VDE 0140-1

Connection Data: Inline connector

Connection methodSpring-cage connection
Conductor cross section solid / stranded0.08 mm² ... 1.5 mm² / 0.08 mm² ... 1.5 mm²
Conductor cross section [AWG]28 ... 16
Stripping length8 mm

Connection Data for UL approvals: Inline connector

Connection methodSpring-cage connection
Conductor cross section solid / stranded0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
Conductor cross section [AWG]24 ... 16
Stripping length8 mm

5 Interface and System Limits

Interface: Modbus/RTU

Number1
Connection methodD-SUB-9 female connector
Note on the connection methodElectrically isolated supply, shielding directly connected to functional earth ground
Number of positions9
Transmission speed1.2 kBit/s ... 115.2 kBit/s (can be parameterized)

Interface: Inline local bus

Connection methodInline data jumper
Transmission speed500 kbps / 2 Mbps (automatic detection, no combined system)

System limits of the bus coupler

Number of supported devicesmax. 63 (per station)
Number of local bus devices that can be connectedmax. 61 (on board I/Os are two devices)
Number of devices with parameter channelmax. 8

Note: Observe the logic current consumption of each device when configuring an Inline station! It is specified in every terminal-specific data sheet. The current consumption can differ depending on the individual terminal. The permissible number of devices that can be connected therefore depends on the specific station structure.

6 Power Supply and Consumption

Bus coupler supply UBC; Communications power UL (7.5 V) and the analog supply UANA (24 V) are generated from the bus coupler supply.

Bus coupler supply (UBC)

Supply voltage24 V DC (via Inline connector)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmin. 80 mA (without connected I/O terminal blocks)
max. 0.98 A

Communications power (UL)

Supply voltage7.5 V DC
Power supply unitmax. 0.8 A DC

Supply of analog modules (UANA)

Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unitmax. 0.5 A DC

Main circuit supply (UM)

Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unitmax. 8 A DC (sum of UM + US)
Current drawmax. 8 A DC

Segment circuit supply (US)

Supply voltage24 V DC (via Inline connector)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unitmax. 8 A DC (sum of UM + US)
Current drawmin. 6 mA (without connected peripherals)
max. 8 A DC

Power consumption

Power consumptiontyp. 1.7 W (entire device)

Protection

NOTE: Electronics may be damaged when overloaded

Provide external protection for the 24 V areas UBK, UM, and US. If you are using an external fuse, the power supply unit must be able to supply four times the nominal current of the fuse. This ensures that it trips in the event of an error.

7 Digital Inputs and Outputs

Digital inputs

Number of inputs8
Connection methodInline connector
Connection technology3-wire
Input characteristic curveIEC 61131-2 type 1
Nominal input voltage24 V DC
Nominal input currenttyp. 3 mA
Current flowLimited to 3 mA, maximum
Input voltage range "0" signal-30 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Delay at signal change from 0 to 1typ. 1.2 ms
Delay at signal change from 1 to 0typ. 1.2 ms
Permissible conductor length to the sensor100 m
Reverse polarity protectionSuppressor diode

Digital outputs

Number of outputs4
Connection methodInline connector
Connection technology3-wire
Nominal output voltage24 V DC
Voltage difference with nominal current< 1 V
Maximum output current per channel500 mA
Maximum output current per device2 A
Nominal load, ohmic12 W
Nominal load, inductive12 VA (1.2 H, 48 Ω)
Nominal load, lamp12 W
Signal delaytyp. 1.2 ms
Maximum operating frequency with inductive nominal load0.5 Hz (1.2 H, 48 Ω)

Digital outputs behavior

Behavior at voltage switch-offThe output follows the power supply without delay
Limitation of the voltage induced on circuit interruptionapprox. -30 V
Output current when switched offmax. 10 μA (When not loaded, a voltage can be measured even at an output that is not set.)
Behavior with overloadAuto restart
Behavior with inductive overloadOutput can be destroyed
Reverse voltage resistance to short pulsesReverse voltage proof
Resistance to permanent reverse voltagemax. 2 A
Overcurrent shut-downmin. 0.7 A
Short-circuit and overload protectionFreewheeling circuit in the output driver

Error messages to the higher level control or computer system

Short-circuit / overload of the digital outputsYes
Sensor supply failureYes
Failure of the actuator supplyYes

Mechanical tests

Vibration resistance in acc. with EN 60068-2-6/ IEC 60068-2-65g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse

Conformance with EMC Directive 2014/30/EU

Noise immunity test in accordance with EN 61000-6-2

Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2Criterion B, 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3Criterion A, Field intensity: 10 V/m
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4Criterion A, all interfaces 1 kV
Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5Criterion B, DC supply lines: 0.5 kV/1.0 kV (symmetrical/asymmetrical), fieldbus cable shield: 1 kV
Conducted interference EN 61000-4-6/IEC 61000-4-6Criterion A; Test voltage 10 V

Noise emission test as per EN 61000-6-4

Class A

Approvals

For the latest approvals, please visit phoenixcontact.net/products.

8 Internal Circuit Diagram

The internal circuit diagram illustrates the connections between the microprocessor (µP), protocol chip (IB), power supply units (5V, 7.5V, 24V), digital inputs (DI1-DI8), digital outputs (DO1-DO4), and the Modbus interface. The diagram highlights electrically isolated areas labeled A (Modbus interface), B (Logic), and C (I/O).

Key:

9 Notes on Using the Terminal Block in Potentially Explosive Areas

WARNING: Explosion hazard. Please make sure that the following notes and instructions are observed.

Approval according to ATEX Directive 2014/34/EU: II 3 G Ex nA IIC T4 Gc X

Installation notes

The category 3 device is designed for installation in zone 2 potentially explosive areas. It meets the requirements of EN 60079-0:2012 + A11:2013 and EN 60079-15:2010.

10 Connecting Modbus, Supply, Actuators, and Sensors

7.1 Connecting Modbus

Connect Modbus to the bus coupler via a 9-pos. D-SUB connector (see ordering data). For the pin assignment, please refer to the figure and the table.

Figure 2: Pin assignment of the 9-pos. D-SUB female connector

PinAssignment
1Reserved
2Reserved
3RxD/TxD-P (receive/transmit data +), cable B
4CNTR-P (control signal for repeater), direction control
5DGND (reference potential to 5 V)
6VCC (+5 V DC)
7Reserved
8RxD/TxD-N (receive/transmit data –), cable A
9Reserved

7.2 Mains termination resistors

Using the SUBCON connector specified in the ordering data ensures that the cable termination meets the Modbus RTU/ASCII specification.

11 Terminal Point Assignments and Connection Example

7.3 Terminal point assignment of input and output connectors

Power connector (1)

Terminal pointAssignmentTerminal pointAssignment
1.1US2.1UM
1.2UBK2.2UM
1.3GND UBK2.3GND UM, US
1.4Functional earth ground (FE)2.4Functional earth ground (FE)

Output connector

Terminal pointAssignmentTerminal pointAssignment
1.1OUT012.1OUT02
1.2GND2.2GND
1.3FE2.3FE
1.4OUT032.4OUT04

Input connector (3)

Terminal pointAssignmentTerminal pointAssignment
1.1IN012.1IN02
1.2US2.2US
1.3GND2.3GND
1.4IN032.4IN04

Input connector (4)

Terminal pointAssignmentTerminal pointAssignment
3.1IN054.1IN06
3.2US4.2US
3.3GND4.3GND
3.4IN074.4IN08

8 Connection example

Figure 4 shows a typical connection example for the bus coupler, illustrating the power supply connections (24 V DC for US and UBK) and the Modbus RTU interface.

12 Local Status and Diagnostic Indicators

Figure 5: Local diagnostic and status indicators

DesignationColorMeaningStateDescription
PWR (UL)GreenULogicON24 V bus coupler supply/7.5 V communications power present
OFF24 V bus coupler supply/7.5 V communications power not present
USGreenUSegmentON24 V segment circuit supply present
OFF24 V segment circuit supply not present
UMGreenUMainON24 V I/O supply present
OFF24 V I/O supply not present
TRYellowTrafficONData exchange at the RTU/ASCII interface.
OFFNo data exchange at the RTU/ASCII interface.
CORedConfigurationONThe active configuration of the local bus differs from the saved configuration.
OFFThe active configuration of the local bus matches the saved configuration.
WDRedWatchdogONTime between two Modbus telegrams exceeded during active connection monitoring (Modbus telegram watchdog).
Flashing (2 Hz)On a power-on reset: new parameters are read in successfully.
Flashing (0.5 Hz)On a power-on reset: new parameters have been applied successfully.
Flashing (5 Hz)On a power-on reset: new parameters have not been applied successfully.
OFFNo error
O1 DGreenDiagnosticsONData transmission active within the station
FlashingData transmission not active within the station
ERedErrorONI/O error, short-circuit/overload of outputs
OFFNo I/O error
1 ... 4 (OUT01 ... OUT04)YellowON/OFFOutput is set/not set.
I1, I2 (1 ... 8) (IN01 ... IN08)YellowON/OFFInput is set/not set.

13 Parameterization of the Hardware

10.1 Address setting

The address is set using two rotary encoding switches. The left switch sets the tens position, and the right switch sets the units position. Addresses can be set between 1 and 99. Figure 6 illustrates the address setting 74.

A valid address is applied on power up and cannot be modified during operation.

10.2 Parameterization via rotary coding switches

In addition to the address, various operating parameters can be set via the rotary coding switches. These parameters are read only upon a power-on reset. If the tens switch is set to a position not valid for an address (≥ 10), the bus coupler enters "Parameter setting" mode.

Tens switch (x10)Pos.MeaningUnits switch (x1)Pos.MeaningDefault
10 Mode0RTUX
1ASCII
2Factory configuration
3Activate Plug and Play mode
4Deactivate Plug and Play mode
11 Baud rate (bps)01200X
12400
24800
39600
419200
538400
657600
7115200
Tens switch (x10)Pos.MeaningUnits switch (x1)Pos.MeaningDefault
12 Data bits07X
18X
13 Parity0NoneX
1EvenX
2Odd
14 Stop bit01X
12
15 Watchdog0ONX
1OFF

Default parameters are set upon delivery and after factory configuration reset. On a power-on reset, the bus coupler reads and saves the current operating parameter. Repeat for multiple parameters. The watchdog LED indicates parameter reading status: quick flash (reading), slow flash (accepted), very quick flash (invalid).

Example: To set "Disable Plug and Play" and "ASCII" operating parameters:

14 Parameterizing via Modbus Registers

Configuration can be modified via Modbus registers in addition to rotary coding switches.

IndexParameterValueMeaningDefault
2100Transmission mode0RTUX
1ASCII
2101Baud rate (bps)01200X
12400
24800
39600
419200
538400
657600
7115200
2102Data bits07X
18
2103Parity0NoneX
1Even
2Odd
2104Stop bit01X
12
1280Watchdog0Watchdog deactivatedX
xx200 ms ... 65000 ms (1 ms increments)10000 ms
2002Fault response mode0Standard fault modeX
1Reset fault mode
2006Command register0Deactivate Plug and Play modeX
1Activate Plug and Play mode

All registers are 16-bit. New parameters are applied after a positive response. The last valid parameter record applies after power-up. Changing the baud rate also adjusts RTU framing times (t1.5, t3.5). For more details, visit www.modbus.org.

15 Modbus Telegram Watchdog and Plug and Play Mode

10.4 Modbus telegram watchdog (connection monitoring)

Monitors Modbus telegrams and triggers on correct reception. Can be enabled/disabled via rotary switches. Time set via register 1280 (0=disabled; 200ms-65000ms). Actions upon triggering depend on fault response mode (default: reset fault mode - set digital outputs to zero, freeze analog outputs, watchdog LED on). Settings modified by write access are applied on power-up reset, except for watchdog activation via register 1280, which is immediate.

The Modbus telegram watchdog does not operate during Plug and Play mode.

10.5 Plug and Play mode

Supports Plug and Play mode for starting local bus modules without a higher-level computer. Activated/deactivated via "ADDRESS" rotary switches (register 2006). Activated by default. Stores configuration retentively. Detects modules, checks function, and stores reference configuration. Deactivating prevents overwriting. If Plug and Play is disabled, the bus starts only if the configuration matches the saved one. If enabled, process data writing is rejected by exception; read access is possible. Deactivating PnP acknowledges reference configuration and enables process data exchange. If configurations differ, CO LED turns red; if they match, the bus enters RUN state. Options: Restore original configuration or activate PnP and restart.

16 Modbus Protocol

The Modbus protocol defines data exchange between a client and a server. It includes an Application Data Unit (ADU) comprising a Protocol Data Unit (PDU) with Function Code, Data, and Error Check.

Modbus RTU

RTU telegrams consist of Station address, Function, Data, and CRC. They are separated by end-of-frame times. RTU offers higher data throughput than ASCII.

Modbus ASCII

ASCII telegrams use start and end characters and are less time-critical.

12 Modbus functions

The protocol functions determine data read/write operations. Supported functions include:

17 Examples for Modbus Functions

Function code fc1 (Read digital outputs)

Details request, response, and error structures for reading digital outputs. An example shows reading outputs 20 through 38.

Function code fc2 (Read digital inputs)

Details request, response, and error structures for reading digital inputs. An example shows reading inputs 197 through 218.

Function code fc3 (Read analog inputs)

Details request, response, and error structures for reading registers. An example shows reading registers 108 through 110.

Function code fc4 (Read analog inputs)

Details request, response, and error structures for reading input registers. An example shows reading input register 9.

Function code fc5 (Write digital output)

Details request, response, and error structures for writing a digital output. An example shows writing output 173 ON.

Function code fc6 (Write analog output)

Details request, response, and error structures for writing a single register. An example shows writing register 2 to 0003hex.

Function code fc15 (Write multiple digital outputs)

Details request/response PDU structures and error codes for writing multiple outputs. An example demonstrates writing a series of 10 outputs starting with output 20, including binary value assignment.

Function code fc16 (Write multiple registers)

Details request/response structures and error codes for writing multiple registers. An example shows writing two registers starting with 2 to 000Ahex and 0102hex.

18 Modbus Tables

14.1 Process data

Modbus register tables provide information on process data location. Bit-oriented data typically precedes byte-oriented data.

Static table

Modbus register tableDigital Modbus inputs tableDigital Modbus outputs tableInternal IL MOD BK tablesFunction codes that can be used
0 - 191 (16-bit word)0 - 3071 (bits)Digital inputsfc2
192 - 383 (16-bit word)Analog inputsfc4
384 - 575 (16-bit word)0 - 3071 (bits)Digital outputsfc1, fc5, fc15
576 - 767 (16-bit word)Analog outputsfc3, fc6, fc16

The assignment of process data in static tables is illustrated by diagrams showing the physical layout and corresponding register addresses for data input (DI, AI) and data output (DO, AO).

Dynamic table

For dynamic tables, register areas are not fixed. The general order of process data is: DATA IN (bit-oriented), DATA IN (byte-oriented), DATA OUT (bit-oriented), DATA OUT (byte-oriented).

Modbus register tableInternal IL MOD BK tablesFunction codes that can be used
8000 - 8192 (16-bit word)Dynamic process data tablefc2 to fc16

The assignment of process data in dynamic tables is also illustrated by diagrams showing the physical layout and corresponding register addresses.

19 Special Registers

14.2 Special registers

Modbus register tableAccessInternal IL MOD BK tables
1280 (16-bit word)Read/writeModbus telegram watchdog (connection monitoring), (default = 10000 ms)
1400-1463 (16-bit word)ReadUp to 1400: Number of local bus devices; Above 1401: ID code of the relevant device
2002 (16-bit word)Read/writeFault response mode (default = reset fault mode)
2004 (16-bit word)ReadNet Fail reason
2006 (16-bit word)Read/writeCommand register (command word)
2100 (16-bit word)WriteTransmission mode: RTU, ASCII (default = 0 = RTU mode)
2101 (16-bit word)WriteBaud rate: 1200 ... 115200 (Default = 4 = 19200)
2102 (16-bit word)WriteData bits: 7, 8 (default = 1 = 8 bits)
2103 (16-bit word)WriteParity: None, even, odd (default = 1 = even parity)
2104 (16-bit word)WriteStop bits: 1, 2 (default = 0 = 1 stop bit)
6020-6093 (16-bit word)WritePCP
7996 (16-bit word)ReadStatus register (status word)
7997 (16-bit word)ReadLocal bus diagnostic status register
7998 (16-bit word)ReadLocal bus diagnostic parameter register 1
7999 (16-bit word)ReadLocal bus diagnostic parameter register 2

14.3 Description of special registers

Modbus telegram watchdog (connection monitoring), (1280): Valid values are 0; 200 ms to 65000 ms. Monitors Modbus telegrams, triggers on correct reception. Can be enabled/disabled via rotary switches. Time set via register 1280 (0=disabled). Actions upon triggering depend on fault response mode (default: reset fault mode - set digital outputs to zero, freeze analog outputs, watchdog LED on). Settings modified by write access are applied on power-up reset, except for watchdog activation via register 1280, which is immediate.

Fault response mode, (2002):

Fault response modeValueFunction
Standard fault mode0All outputs are set to "0".
Reset fault mode (default)1The digital outputs are set to "0" and the analog outputs are held at the last value.
Hold last state mode2All outputs are held at their last value.

Net Fail reason, (2004): Used to read the reason after a Net Fail signal. For IL MOD BK DI8 DO4-PAC, the reason is connection monitoring watchdog failure (value 000Dhex in register 2004).

Command register (command word), (2006): Activation/deactivation of Plug and Play mode is performed by Bit 0 (0=deactivated, 1=activated). Bit 1 acknowledges Net Fail; Bit 2 acknowledges peripheral fault.

Status register (status word), (7996): Bit 0 indicates error status (0=error, 1=no error). Bit 1 indicates Net Fail status (1=Net Fail occurred, 0=not occurred). Status word values: 0 (error), 1 (no error), 2 (Net Fail).

Local bus diagnostic status register (7997): Each bit indicates a state of the local bus master. Error bits (USER, PF, BUS, CTRL) are detailed in the diagnostic parameter register. If an error bit is set, the diagnostic parameter register is rewritten; otherwise, it is 0000hex.

PCP registers (6020 - 6093): Divided into Communication registers (for data exchange) and Configuration registers (for invoke ID, index, subindex). Refer to IBS SYS PCP G4 UM E user manual for details. The terminal supports eight PCP devices.

Local bus diagnostic parameter register 1 (7998): Contains error location (e.g., device number 0.3).

Local bus diagnostic parameter register 2 (7999): Contains additional information about error codes. Refer to IBS SYS FW G4 UM E user manual for details.

20 PCP Registers

PCP registers are categorized into Communication registers and Configuration registers. The table below outlines the mapping for different Communication References (CR).

Communication referenceCommunication registerConfiguration registerRemark
CR 260206021Index
6022Subindex
6023Invoke ID
6024-6029Reserved
CR 360306031Index
6032Subindex
6033Invoke ID
6034-6039Reserved
CR 460406041Index
6042Subindex
6043Invoke ID
6044-6049Reserved
CR 560506051Index
6052Subindex
6053Invoke ID
6054-6059Reserved
CR 660606061Index
6062Subindex
6063Invoke ID
6064-6069Reserved
CR 760706071Index
6072Subindex
6073Invoke ID
60724-6079Reserved
CR 860806081Index
6082Subindex
6083Invoke ID
6084-6089Reserved
CR 960906091Index
6092Subindex
6093Invoke ID
6094-6099Reserved

Example: To read object 5FE0hex of an IB IL RS 232-PAC with communication reference 4, first set configuration registers (6041-6043) with FC 16 command (e.g., 6041 index: 5FE0hex, 6042 subindex: 0hex, 6043 invoke ID: 0hex). Then use fc3 command to read 29 words via communication register 6040. Modbus functions are used for read/write access to PCP indexes. Accessing reserved registers generates an exception response.

PDF preview unavailable. Download the PDF instead.

db en il mod bk di8 do4 pac 7258 en 06 Acrobat Distiller 10.0.0 (Windows)

Related Documents

Preview AXL F BK PN TPS - Bus Coupler | Phoenix Contact
Detailed technical specifications and features of the Phoenix Contact AXL F BK PN TPS Bus Coupler, a PROFINET device for industrial I/O systems. Includes dimensions, electrical properties, connection technology, and environmental data.
Preview Phoenix Contact IB IL AO 2/U/BP-ME Analog Module Technical Data
Technical specifications and product information for the Phoenix Contact IB IL AO 2/U/BP-ME Analog Module, including dimensions, electrical properties, connection data, and environmental compliance.
Preview PLCnext and S7-1200 Communication via Node-Red: Technical Guide
A technical guide from PHOENIX CONTACT detailing the setup and configuration for communication between PLCnext controllers and Siemens S7-1200 PLCs using Node-Red, including Tia Portal and Node-Red configurations.
Preview Phoenix Contact PLCnext Technology: Controllers, I/O Systems, and Software
Explore Phoenix Contact's PLCnext technology, featuring advanced PLC controllers, versatile Axioline I/O systems (F, SE, E), and powerful engineering software for industrial automation. Discover open architecture, multi-language programming, and extensive communication protocols.
Preview Phoenix Contact VARIOFACE System Cabling: Efficient Industrial Automation Wiring
Discover Phoenix Contact's VARIOFACE system cabling solutions for industrial automation. Reduce wiring time, errors, and costs with pre-assembled, plug-in components compatible with major PLC systems. Explore front adapters, system cables, and termination boards.
Preview Technical Guide: PLCnext and Compactlogix Communication via Node-RED
Learn how to integrate PHOENIX CONTACT PLCnext and Allen Bradley Compactlogix controllers using Node-RED for industrial automation. This guide covers configuration, variable reading, and writing.
Preview Phoenix Contact INTERBUS Diagnostics Guide for Generation 4 Controller Boards
Comprehensive guide to diagnosing INTERBUS systems, detailing diagnostic displays, LED indicators, error codes, menu navigation, and troubleshooting for Phoenix Contact Generation 4 controller boards.
Preview Guia Técnico: Comunicação OPC UA entre Node-RED e PLCnext
Este guia técnico da PHOENIX CONTACT detalha a configuração e implementação da comunicação OPC UA entre o software Node-RED e o sistema PLCnext. Abrange desde a instalação do Node-RED e configuração do servidor OPC UA no PLCnext até a configuração de nós OPC UA Client no Node-RED para leitura e escrita de variáveis.