SMC HRLE Series Thermochillers

Laser Application Dual / Basic Type, Air-Cooled Refrigeration Type

CE ? RoHS

Key Features and Benefits

Dual System Temperature Control

One chiller unit can individually control two independent systems.

Space Saving

Achieves a 21% reduction in installation area compared to using two separate chillers.

Diagram Description: A visual comparison shows a single dual thermochiller unit occupying less space than two individual thermochiller units.

Energy Saving

Achieves a 17% reduction in power consumption.

  • One unit each for chiller, fan, and pump.
  • Heaterless heating method.

General Specifications

Core Performance

  • Cooling Capacity (CH1, 2 total): 8.0 kW / 9.5 kW (50Hz/60Hz)
  • Heating Capacity (CH1, 2 total): 2.0 kW / 2.5 kW (50Hz/60Hz)
  • Temperature Stability: ±0.1℃ (CH1), ±0.5℃ (CH2)
  • Setting Temperature Range: 15~25℃ (CH1), CH1 Temperature +0~15℃ (CH2)

Environmental & Design Features

  • Outdoor Installation: Weatherproof (IPX4 equivalent) ?
  • Low Noise Function: Variable fan speed ⚙️

Available Options

  • Cooling Capacity Up Function (Refrigerant Inverter: Option C)
  • Circulating Liquid Pressure Adjustment Function (Pump Inverter: Option P)

Series Name

HRLE Series

Model Specifications

HRLE090-A-20 (200V Class)

ItemUnitValue (50Hz)Value (60Hz)
Cooling MethodAir-Cooled RefrigerationAir-Cooled Refrigeration
RefrigerantR410A (HFC)R410A (HFC)
Refrigerant Chargekg22
Control MethodPID ControlPID Control
Ambient Operating Temp2 to 452 to 45
Circulating Fluid SystemWater, DI Water (Pure Water)Water, DI Water (Pure Water)
Circulating FluidCH1: 15~25, CH2: CH1+0~15CH1: 15~25, CH2: CH1+0~15
Cooling Capacity (CH1, 2 total)kW8.09.5
Heating Capacity (CH1, 2 total)kW2.02.5
Temp StabilityCH1: ±0.1, CH2: ±0.5CH1: ±0.1, CH2: ±0.5
Pump Flow Rate (CH1)L/min2535
Pump Flow Rate (CH2)L/min22
Max Head (CH1)m5050
Max Head (CH2)m22
Min Required Flow Rate (CH1)L/min2535
Min Required Flow Rate (CH2)L/min11
Tank CapacityL1818
Circulating Liquid PortsCH1: Rc1, CH2: Rc1/2CH1: Rc1, CH2: Rc1/2
Drain PortRc1/4Rc1/4
Wetted Parts MaterialStainless steel, copper (heat exchanger brazing), bronze (pump), ceramic, carbon, FKM, PP, PE, POM, PVC, PA, EPDMStainless steel, copper (heat exchanger brazing), bronze (pump), ceramic, carbon, FKM, PP, PE, POM, PVC, PA, EPDM
Electrical
Power Supply3-Phase AC200V (50Hz)3-Phase AC200-230V (60Hz)
Voltage Fluctuation±10%±10%
Rated CurrentA3030
Rated Operating CurrentA1417
Rated Power ConsumptionkW (kVA)4.3 (4.9)5.3 (5.8)
Communication FunctionContact I/O, Serial Comm. (RS-485)Contact I/O, Serial Comm. (RS-485)
Noise LeveldB(A)6565
Standard AccessoriesManuals (JP/EN), Anchor bolt fixing brackets (incl. M8 bolts)Manuals (JP/EN), Anchor bolt fixing brackets (incl. M8 bolts)
Masskg140140

HRLE090-A-40 (400V Class)

ItemUnitValue (50Hz)Value (60Hz)
Cooling MethodAir-Cooled RefrigerationAir-Cooled Refrigeration
RefrigerantR410A (HFC)R410A (HFC)
Refrigerant Chargekg22
Control MethodPID ControlPID Control
Ambient Operating Temp2 to 452 to 45
Circulating Fluid SystemWater, DI Water (Pure Water)Water, DI Water (Pure Water)
Circulating FluidCH1: 15~25, CH2: CH1+0~15CH1: 15~25, CH2: CH1+0~15
Cooling Capacity (CH1, 2 total)kW8.09.5
Heating Capacity (CH1, 2 total)kW2.02.5
Temp StabilityCH1: ±0.1, CH2: ±0.5CH1: ±0.1, CH2: ±0.5
Pump Flow Rate (CH1)L/min2535
Pump Flow Rate (CH2)L/min22
Max Head (CH1)m5050
Max Head (CH2)m22
Min Required Flow Rate (CH1)L/min2535
Min Required Flow Rate (CH2)L/min11
Tank CapacityL1818
Circulating Liquid PortsCH1: Rc1, CH2: Rc1/2CH1: Rc1, CH2: Rc1/2
Drain PortRc1/4Rc1/4
Wetted Parts MaterialStainless steel, copper (heat exchanger brazing), bronze (pump), ceramic, carbon, FKM, PP, PE, POM, PVC, PA, EPDMStainless steel, copper (heat exchanger brazing), bronze (pump), ceramic, carbon, FKM, PP, PE, POM, PVC, PA, EPDM
Electrical
Power Supply3-Phase AC380-415V (50/60Hz)3-Phase AC460-480V (60Hz)
Voltage Fluctuation±10%+4%, -10% (max 500V)
Rated CurrentA2020
Rated Operating CurrentA6.88.2
Rated Power ConsumptionkW (kVA)4.3 (4.9)5.3 (5.8)
Communication FunctionContact I/O, Serial Comm. (RS-485)Contact I/O, Serial Comm. (RS-485)
Noise LeveldB(A)6767
Standard AccessoriesManuals (JP/EN), Anchor bolt fixing brackets (incl. M8 bolts)Manuals (JP/EN), Anchor bolt fixing brackets (incl. M8 bolts)
Masskg140140

Performance Graphs

Cooling Capacity

Diagram Description: Two graphs illustrate cooling capacity (kW) versus circulating liquid temperature (℃) for the HRLE090-A-20/40 models. The left graph shows performance at 50Hz, and the right graph at 60Hz. Both graphs display performance curves for ambient temperatures of 32℃, 40℃, and 45℃. Note: Cooling capacity is the sum for CH1 and CH2. The 32℃ ambient condition assumes 60% fan output, while 40℃ and 45℃ assume 100% fan output, resulting in approximately a 3 dB(A) increase in noise.

Pump Capacity

Diagram Description: A graph shows circulating liquid pressure (MPa) versus circulating liquid flow rate (L/min) for the HRLE090-A-20/40 models. It indicates the usable range for 50Hz and 60Hz operation. The graph specifies that the pump capacity shown is for CH1 when CH2 is operating at 2 L/min.

Outline Dimensions and Part Identification

Diagram Description: Detailed external dimension drawings are provided for the HRLE090-A-20/40 models, showing front, side, and rear views with key dimensions labeled (e.g., Height: 1055mm, Width: 445mm, Depth: 965mm). Anchor bolt mounting positions are indicated. A diagram also labels various parts of the unit, including the tank water inlet, liquid level gauge, operation panel, dust filter, circulating liquid discharge and return ports (specifying sizes like Rc1 for CH1 and Rc1/2 for CH2), power cable outlet, communication cable outlet, and drain port (Rc1/4).

Available Options

Option C: Refrigerant Inverter

Equipped with a refrigerant inverter, this option enhances cooling capacity in 50Hz regions to match the performance of 60Hz specifications. External dimensions remain unchanged.

Option M: DI Water (Pure Water) Piping Compatible

This specification uses materials that avoid copper alloys in the circulating liquid path, suitable for DI water applications. Wetted parts include stainless steel, SiC, carbon, PA, PP, PE, POM, FKM, EPDM, PVC, and PTFE. External dimensions remain unchanged.

Option P: Pump Inverter

Features a pump inverter that improves pump capacity to match 60Hz specifications in 50Hz regions. It also enables adjustable pressure control, allowing automatic adjustment to any desired pressure without needing to modify valve openings. External dimensions remain unchanged.

Optional Accessories

  • G-thread Conversion Fitting Set: Converts Rc ports to G-threads.
  • NPT Thread Conversion Fitting Set: Converts Rc ports to NPT threads.
  • Bypass Piping Set: Ensures minimum required flow rate to maintain temperature stability.
  • Electrical Conductivity Control Set: Monitors and controls the electrical conductivity of the circulating fluid.
  • Particle Filter Set (CH1/CH2): Removes foreign particles from the circulating fluid.
  • Handle: For removing filter cases.
  • Tank Water Inlet Filter: Prevents foreign matter from entering the tank during water supply.
  • Auto Water Supply Set: Automatically replenishes circulating liquid when levels decrease.
  • Ball Valve Set (with Pressure Gauge): Allows adjustment of circulating liquid pressure and flow rate.

Safety Information

Caution: Please read the "SMC Product Handling Precautions" (M-03-3) and the "Instruction Manual" before use to ensure correct operation.

Company Information

SMC Corporation

Website: https://www.smcworld.com

Head Office: 15F Akihabara UDX, 4-14-1 Sotokanda, Chiyoda-ku, Tokyo 101-0021, Japan

Customer Support Desk: Free Dial 0120-837-838 (Mon-Fri, 9:00-12:00, 13:00-17:00, excluding holidays)

Content is subject to change without notice.

©2021 SMC Corporation. All Rights Reserved.

PDF preview unavailable. Download the PDF instead.

21-770-HRLE Adobe PDF Library 10.0.1 Adobe InDesign CS6 (Macintosh)

Related Documents

Preview SMC HEF Series Peltier-type Chillers: Specifications, Features, and Applications
Explore the SMC HEF Series compact, air-cooled Peltier-type chillers. This document details their precise temperature control capabilities, low-noise operation, refrigerant-free design, specifications, application examples, ordering information, and important operational precautions.
Preview SMC Pneumatic Recommendations for Efficient and Safe Machine Operation & Energy Saving
Explore SMC's Engineering Aids and Energy Saving Program (Ver.2) for pneumatic systems. Discover recommendations for efficient, safe, and cost-effective machine operation, including leak detection, air preparation, blow guns, and vacuum components.
Preview SMC Thermo-chiller Operation Manual
This operation manual provides detailed instructions for the installation and operation of the SMC Thermo-chiller, including safety precautions, product specifications, and troubleshooting.
Preview SMC HRS-PF005 Particle Filter Set - Installation and Operation Guide
Comprehensive guide for installing and operating the SMC HRS-PF005 Particle Filter Set, compatible with SMC Thermo-chiller HRS Series. Includes safety precautions, parts identification, and step-by-step mounting instructions.
Preview SMC ZL Series Digital Pressure Switch Operation Manual
Comprehensive guide to the SMC ZL Series digital pressure switch for energy-saving control ejectors, covering safety, installation, operation, settings, and troubleshooting.
Preview SMC IN508-36-A Series Fieldbus SI Unit for AS-Interface: Instruction Manual
Detailed instruction manual for the SMC IN508-36-A series Fieldbus SI unit for AS-Interface. Covers product specifications, safety guidelines, assembly, installation, settings, maintenance, and contact information for industrial automation.
Preview SMC KFG2 Series Stainless Steel 316 Insert Fitting Operation Manual
Comprehensive operation manual for SMC's KFG2 series Stainless Steel 316 Insert Fittings, detailing safety instructions, product specifications, mounting procedures, troubleshooting, and fluid compatibility for industrial pneumatic systems.
Preview SMC-PAD User Manual
User manual for the SMC-PAD MIDI Controller, detailing its features, connections, and operation.