Stienen BO-AIR PL User Manual

Climate control for naturally ventilated poultry houses (24V and 230V versions)

1. About this manual

This manual is intended for the user of the BO-AIR PL device. It contains all necessary information for operating and cleaning the product. Please read all information and instructions carefully before using the product. Symbols in this manual mark warnings, important notes, and tips.

1.1 Symbols and definitions

1.2 Customer service

For any questions, please contact your installer. Ensure you have all necessary data readily available. Document the cause and circumstances of any faults to help your installer resolve issues quickly and effectively.

2. Safety instructions and warnings

Read the general safety instructions carefully before using the device. Installation and fault resolution must be performed by a certified installer according to applicable guidelines. Improper installation or use may void the warranty.

2.1 Sound, independent alarm system

While Stienen designs equipment with care, technical faults can occur. Many countries have stringent insurance requirements that necessitate connecting alarm contacts to a central alarm unit. It is recommended to install a sound-independent alarm system, such as a min/max thermostat. Manually test the alarm at least once a week.

2.2 During use

Operators must read the manual and be aware of potential hazards from improper use and maintenance. The device should only be opened by authorized personnel. Do not switch off the control computer while the house is empty; use the 'Off' mode to prevent condensation. Regularly check the device for damage, as a damaged device is unsafe. Report any damage to your installer immediately. Electronic equipment is splash-proof and should not be cleaned with a pressure cleaner. In case of an emergency, record the circumstances, installation settings, software date and version, and possible causes.

2.3 Disposal

The EU mandates separate collection for waste electrical and electronic equipment and batteries (Directive 20212/19/EU). Improper disposal may result in a fine. Electrical and electronic equipment must be collected separately at the end of its life.

3. Introduction

3.1 Purpose of use

Optimal ventilation is crucial for a healthy house climate for animals. The BO-AIR PL climate control system allows effective control of air inlets (curtains) to achieve ideal fresh air flow.

3.2 Control functions

Sensors

Curtains

Ventilation

Heating/cooling

Timer

Water consumption

Records water consumption (in liters) for the past 4 days, including today.

Feed consumption

Records feed consumption (in kilograms) for the past 4 days, including today.

4. Controls

4.1 General

The BO-AIR PL control has four operational zones (from low to high temperature):

Zone Temperature control
1. Heating Tsetpoint curtain + ΔT, heating
2. Curtain control Tsetpoint curtain
3. Tunnel ventilation Tsetpoint tunnel
4. Tunnel cooling Tsetpoint tunnel + ΔT, cooling

If tunneling is disabled, Tsetpoint curtain is used instead of Tsetpoint tunnel.

4.2 Heating-1 control

The heating control operates using an on/off mechanism with hysteresis. The activation temperature is defined as an offset below the curtain setpoint temperature. This offset is entered as a positive value but is subtracted from the setpoint.

Warning: If both curtain temperature sensors are faulty, the heating function will be deactivated.

4.3 Motor controls (curtains and tunnel air inlets)

The BO-AIR-PL manages two curtains—one on the left and one on the right. For tunnel air inlets, the control options vary depending on the BP04 variant used:

Motor control and operation

The BO-AIR-PL operates the two curtains via dedicated motor controls, one for each side (left and right). Curtain operation is the primary control function. In configurations using the BP04-24V variant, the BO-AIR-PL additionally operates two tunnel valves with separate motor controls for the left and right sides. All motors use the same control protocol and can operate automatically or manually via an external multi-position switch, which allows stopping the motor at any intermediate position. In manual mode, the automatic system detects the manual override and refrains from interfering, preventing alarms for unreachable target positions.

Feedback Control

Motor control relies on position feedback, typically from a potentiometer. In feedback mode, a one-time calibration is required to define minimum and maximum positions. No periodic recalibration is necessary.

During calibration, the system determines minimum and maximum feedback values. A 10% margin of this range validates the feedback signal.

Warning: If the feedback signal is outside this range, an alarm is triggered and motor movement is halted.

Warning: If the calculated margin falls outside the acceptable range (e.g., below 0.0 V, above 3.3V, or below 0 Ω), no validation check is performed.

Alarm Handling

Position errors and feedback alarms remain active until the underlying issue is resolved and confirmed. Alarms do not clear automatically.

Control Behaviour

The motor does not continuously adjust its position. Once the target position is reached, it remains idle for 15 seconds before re-evaluating. Hysteresis is applied to prevent unnecessary corrections unless the deviation from the setpoint exceeds the defined threshold. New position values are transmitted instantly to the BP04 without soft ramping; smooth motion is ensured by the curtain mechanism.

Manual Control

Curtain motors support software-based manual control, sending a fixed position command directly to the motor after successful calibration. Hardware-based manual control is always available via an external switch, overriding internal motor logic for direct run, stop, or reverse control. A hand icon appears on the status screen when manual control is active.

Wiring requirements for operation

Ensure limit switches are correctly wired or that terminal P is connected to both Open and Close for proper motor function. Also, ensure the external manual switch is installed and connected, or a jumper is placed between terminals P and Auto. Without this, magnetic switches for curtain operation will not work. These requirements apply to both BP04-230V and BP04-24V base boards.

4.4 Tunnel ventilation control

Tunnel ventilation directs airflow from the front to the back of the poultry house. To enable this, the left and right side curtains must be nearly closed. Tunnel ventilation uses up to three fan stages and a tunnel air inlet, each with an offset temperature relative to the main tunnel ventilation setpoint. Fan stages must be configured in order of increasing offset temperature (e.g., stage 2 must have a higher offset than stage 1). You can configure between 1 and 3 active fan stages.

A configurable startup delay ensures fans start only when curtains are in the correct position. A fixed hysteresis of 0.5 °C is applied between each stage. When tunnel ventilation is activated, a tunneling switch timer begins, and the system cannot exit tunnel mode until this timer expires. Similarly, when tunnel mode ends, the timer prevents re-entry until it completes.

The current ventilation stage (1, 2, or 3) is displayed above the tunneling icon. A value of 0 indicates tunnel mode is inactive. If the icon is grayed out, tunnel ventilation is not yet active because tunnel air inlets are still moving. Once inlets reach target positions and the configurable delay passes, the first fan starts, and the icon highlights.

For BP04-230V, the tunnel inlet position (%) is displayed alongside the ventilation stage. For BP04-24V, this position is shown below the tunnel inlet status icon. The BoAir 24V also supports an analog output (0–10 V) for two tunnel valves (left and right) that operates in parallel with motor controls.

If the controller is configured as a secondary controller, it receives a signal from the primary controller indicating tunnel mode activity, allowing the secondary controller to adjust its curtains accordingly.

4.5 Heating-2 or cooling control

The control type can be selected as Cooling or Heating 2.

Heating-2 control

Functions identically to Heating 1 and uses the same settings.

Cooling control

If tunnel ventilation fails to keep the temperature below the threshold level, cooling is required. Cooling can operate in two modes:

! Only standalone and primary controllers can operate cooling control.

Warning: If both temperature sensors for the curtains fail, cooling will be deactivated.

4.6 Wind and rain influences

Wind influence (based on wind speed and direction) can be enabled or disabled. When enabled, wind direction determines which side of the building is considered wind-affected.

A neutral zone is defined, within which the wind is considered to come from neither the left nor the right. The angle of this neutral zone (β) is configurable. A typical setting is 40°, creating a 40° sector at the front and rear of the building. The remaining 140° is split evenly between the left and right wind zones.

A hysteresis of 12° is applied to determine the wind direction zone (6° on either side). At startup, wind direction is initialized at 0°, with a hysteresis band from -6° to +6°. When the actual wind direction moves outside this band, that new value becomes the updated reference, and the hysteresis band re-centers. Wind direction is averaged over a 10-minute period, but occasional short-term fluctuations can occur. Hysteresis prevents rapid switching between zones by requiring a meaningful directional change for zone transitions.

If only one house is in use, the weather station can be aligned with it (0° front, 180° back). If multiple houses are in use and not aligned, an offset may be required. For example, if the anemometer is aligned north-south, and the left house needs a +20° offset while the right needs a -30° offset, the actual direction used by the controller is relative to the house's front-back axis. Negative angles are not entered directly; for instance, a -30° offset for the right house would be entered as 330° (360° - 30°).

Wind speed determines how much the curtain control reduces the position of the curtain facing the wind, or both curtains if the wind is in the neutral zone. Starting at a specific velocity and using a defined bandwidth, the curtain position gradually reduces from 0% at the start of the bandwidth to maximum reduction at the end. Wind speed is measured using a moving average buffer of 40 samples, taken at 15-second intervals.

Table 1: Beaufort scale
Beaufort m/s Description km/h
0 0.0-0.2 Calm 0-0.7
1 0.3-1.5 Light air 0.8-5
2 1.6-3.3 Light breeze 6-11
3 3.4-5.4 Gentle breeze 12-19
4 5.5-7.9 Moderate breeze 20-28
5 8.0-10.7 Fresh breeze 29-38
6 10.8-13.8 Strong breeze 39-49
7 13.9-17.1 Near gale 50-61
8 17.2-20.7 Gale 62-74
9 20.8-24.4 Strong gale 75-87
10 24.5-28.4 Storm 88-102
11 28.5-32.6 Violent storm 103-117
12-17 32.7-56.0 Hurricane force 118-202

Rain detection can be enabled or disabled independently. If enabled, and the wind is neutral or blowing toward a curtain with wind speed exceeding the minimum threshold (with 1 m/s hysteresis), that curtain closes to its lowest position. If the wind is neutral, both curtains close.

Rain detection works continuously. Once rain is detected, the rain status remains true for X minutes (configurable from 0 to 30 minutes). Each rain detection resets the timer. If no rain is detected for more than X minutes, the rain status becomes false. If rain is falling and the minimum wind speed is set to 0 m/s, and the actual wind speed is also 0 m/s, the affected curtain closes. If the wind direction is neutral, both curtains close.

If the controller is a secondary controller, it uses its own weather data or data from the primary controller. If wind and rain detection are off on the secondary controller, no changes are made.

The wind direction sensor gives 0 V at the top and increases clockwise: 0 V (0°) is north, 2.5 V (90°) is east, 5 V (180°) is south, and so on. Both wind speed and direction are measured using a moving average buffer of 40 measurements over 10 minutes (one every 15 seconds), meaning changes take time to reflect in the control system.

4.7 Outside temperature compensation

In certain situations, it may be necessary to close curtains more tightly due to cold outside conditions. This is achieved by increasing the curtain control bandwidth as the outside temperature drops.

Example values:

The compensated bandwidth is calculated as: (20.0 – 12.0 – 5.0) × 0.5 + 5.0 = 6.5°C.

Outside temperature compensation applies only to the side where the wind is blowing, or to both sides if the wind direction is neutral. For wind to affect a curtain, the wind speed must be at least the configured threshold for wind speed compensation. If temperature compensation increases the curtain control bandwidth, the curtain position will decrease accordingly. However, outside temperature compensation only functions when wind compensation is active. Depending on wind conditions, the curtain position may decrease even further.

Warning: If the outside temperature sensor is defective (triggering the outside temperature alarm), outside temperature compensation will remain inactive until the issue is resolved.

4.8 Humidity control

As humidity rises above the setpoint, minimum ventilation increases by up to 50% of the set minimum ventilation over a bandwidth of 20% relative humidity (RH).

Example calculation:

4.9 CO2 control

As the CO2 level rises above the setpoint, minimum ventilation increases by up to 50% of the set minimum ventilation over a bandwidth of 1000ppm CO2.

The influence is calculated as: (500 (Δ CO2) / 1000) × 50% = 25%

So, the minimum ventilation will increase to: 10% × 1.25 (+25%) = 12.5%

4.10 Water consumption registration

The water consumption function monitors water usage over the last three days (including today). It uses a counter input along with a factor representing water volume per pulse. Daily records are shifted at midnight: yesterday becomes the day before yesterday, today becomes yesterday, and the counter for today resets. If the controller is turned off for an extended period, this downtime is accounted for.

[Image showing water consumption data with three entries labeled 'OL']

4.11 Feed consumption registration

The feed consumption function works similarly, monitoring feed usage instead of water usage.

[Image showing feed consumption data with three entries labeled '0kg']

4.12 Light timer

The light timer option allows programming 4 on-off times for the light timer relay. Overlapping times are merged. For example, settings from 05:00 to 10:00 and 08:00 to 12:00 combine into a single setting from 05:00 to 12:00. If the start time is later than the stop time (e.g., 10:00 to 05:00), the relay will be on from 00:00 to 05:00 and from 10:00 to 00:00.

[Image showing light timer settings with times like 05:00, 06:15, 00:00]

4.13 LED bar

The BO-AIR-PL is equipped with an LED bar indicating its global state:

[Image of the BO-AIR PL device with its LED bar]

5. Operation

5.1 Screen layout

The main overview screen displays active controls and their measurements on the left. The right side of the screen allows swiping up and down through control icons. Tapping an icon allows changing desired settings.

A. Alarm bell icon: Indicates alarm status:

B. Control icons: Tapping an icon allows changing settings. Set values are shown to the right.

C. Main overview:

Additional features (installer settings dependent):

Above each curtain, a tunnel valve status is shown for BP04-24V when tunneling is active. The icon has three states for both left and right sides:

5.2 Changing settings

Tapping a control icon brings up the settings bar. Adjust settings using '+' (increase) or '-' (decrease). Tap OK to confirm. To cancel, tap anywhere on the left half of the screen; the settings bar closes, and the value resets.

[Image showing scrolling and selecting]

[Image showing changing value using plus and minus buttons]

[Image showing confirming settings by OK]

5.3 Display mode: Controller enabled/disabled

The Bo-Air Touch controller can be enabled or disabled using a slider.

Communication between all controllers and devices remains active, ensuring synchronization and data exchange, regardless of their enabled/disabled or role status.

6. User menu settings

6.1 Home screen

This chapter covers settings accessible from the home screen. The visibility of functions depends on the controller's configuration (Primary, Secondary, Follower, or Standalone). If Secondary, settings are inherited and read-only. If Follower, settings are not visible.

[Image of the Home screen]

6.2 24-hour overview

Opens a graph displaying measurements' statuses over the past 48 hours. Different graphs can be selected using icons on the right. Press 'X' to close.

6.3 Time

Adjust the system time here.

6.4 Date

Adjust the system date here.

6.5 Day count

Displays the current animal day count and selects relevant values from the ventilation curve. Items that can be set include curtain setpoint temperature, minimum curtain position, and maximum curtain position. The day counter starts at day 0 and increments daily but can be manually adjusted. This is visible only when curve mode is enabled.

6.6 Curtain setpoint temperature

Set the temperature for curtain control ventilation. The temperature unit (°C / °F) can be adjusted in the installer menu. In curve mode, this value is calculated from the curve. If secondary, setting is inherited and read-only. If follower, setting is not visible.

6.7 Curtain bandwidth

Set the desired temperature range for ventilation increase from minimum to maximum.

[Diagram showing Ventilation, Min. ventilation, Bandwidth, Max. ventilation, Temperature, Temperature setpoint]

If secondary, setting is inherited and read-only. If follower, setting is not visible.

6.8 Minimum curtain position

Set the desired minimum position for the left and right curtains. In curve mode, this value is calculated from the curve. If secondary, setting is inherited and read-only. If follower, setting is not visible.

6.9 Maximum curtain position

Set the desired maximum position for the left and right curtains. In curve mode, this value is calculated from the curve. If secondary, setting is inherited and read-only. If follower, setting is not visible.

6.10 Minimum temperature alarm level

Set the minimum temperature alarm level. An alarm is activated when the house temperature reaches this level. If follower, setting is not visible. If disabled, the temperature alarm is inactive.

6.11 Maximum temperature alarm level

Set the maximum temperature alarm level. An alarm is activated when the house temperature reaches this level. If follower, setting is not visible. If disabled, the temperature alarm is inactive.

6.12 Tunnel (offset) temperature setpoint

Set the temperature at which tunneling starts, relative to the curtain setpoint temperature. Tunneling uses stages, each with an offset temperature relative to the tunnel setpoint. Tunneling is not available on secondary or follower controllers, but a secondary controller can detect primary controller tunneling and adjust its curtain position accordingly.

6.13 Cooling offset

Set the desired temperature offset relative to the tunnel temperature setpoint when tunnel ventilation is enabled. If tunnel ventilation is not enabled, the offset is relative to the curtain temperature setpoint. Cooling stops after the hysteresis threshold is reached. This option is only visible when cooling control is enabled and the controller is standalone or primary.

6.14 Cooling bandwidth

For modulating cooling, this is the temperature range over which cooling increases from minimum to maximum. This option is only visible when cooling control is enabled and the controller is standalone or primary.

6.15 RH cooling stop

Set the humidity level at which cooling stops. A fixed hysteresis of 2% is applied. This option is only visible when humidity control is enabled and the controller is standalone or primary.

6.16 Heating offset

The heating relay activates when room temperature drops below the set temperature minus the heating offset. It turns off after the hysteresis threshold. The heating icon is shown when Heating 1 and/or Heating 2 is enabled. Heating 1 and Heating 2 share this setting. If the controller is secondary and the primary has Heating 1 enabled, the setting is inherited and read-only. If the primary has no heating enabled, the offset can be set on the secondary controller.

6.17 Humidity level setpoint

Set the desired humidity level for humidity control. When humidity reaches this level, the system increases ventilation to reduce it. This option is only visible when humidity control is enabled and the controller is standalone or primary.

6.18 Actual humidity level

Readout of the actual humidity level. This option is only visible when humidity control is enabled and the controller is standalone or primary.

6.19 Humidity control maximum alarm level

Set the maximum humidity level for the humidity control alarm. An alarm is activated when humidity reaches this level. This option is only visible when humidity control is enabled and the controller is standalone or primary.

6.20 CO2 control setpoint

Set the CO2 level setpoint for CO2 control. When the CO2 level reaches this setpoint, the system increases ventilation to reduce it. This option is only visible when CO2 control is enabled and the controller is standalone or primary.

6.21 Actual CO2 level

Readout of the actual CO2 level. This option is only visible when CO2 control is enabled and the controller is standalone or primary.

6.22 Maximum CO2 alarm level

Set the maximum CO2 level. An alarm is activated when the CO2 level reaches this value. This option is only visible when CO2 control is enabled and the controller is standalone or primary.

6.23 Light timer configuration

Selecting this function opens a popup to define four periods for controlling lights from on to off. This configuration applies to a single day, with the same schedule used every day of the week. This option is visible if the light timer is enabled and the controller is not a follower.

6.24 Water consumption status

Selecting this function displays water consumption from today to three days ago. At midnight, values shift by one day, resetting the current day's consumption to zero liters. This option is visible if the water timer is enabled and the controller is not a follower.

6.25 Feed consumption status

Selecting this function displays feed used today, yesterday, and the day before yesterday. At 0:00 nightly, values shift by one day, and the current day resets to 0. This option is visible if the feed timer is enabled and the controller is not a follower.

6.26 Manual mode for left curtain

Manually activate control for the left curtain. If enabled, the curtain automatically adjusts to the specified position. This software manual option is separate from the hardware manual option (via a 5-position external switch: close – off – auto – off – open), which always has priority. The option is available if the controller is not a follower; if it is a follower, the manual mode position is adopted from the primary controller.

6.27 Manual position left curtain

Enter the position to which the left curtain should move when manual mode is enabled. This function is only visible when manual mode is enabled.

6.28 Manual mode for right curtain

Manually activate control for the right curtain. If enabled, the curtain automatically adjusts to the specified position. This software manual option is separate from the hardware manual option (via a 5-position external switch: close – off – auto – off – open), which always has priority. The option is available if the controller is not a follower; if it is a follower, the manual mode position is adopted from the primary controller.

6.29 Manual position right curtain

Enter the position to which the right curtain should move when manual mode is enabled. This function is only visible when manual mode is enabled.

6.30 Controller enabled / disabled

Enabled Controller

Disabled Controller

Secondary and Follower Controllers

Communication between all controllers and devices remains active, ensuring synchronization and data exchange, regardless of their enabled/disabled or role status.

6.31 User manual

This function opens a QR code containing a hyperlink to this manual for digital download. Scan the QR code with a mobile device for easy access.

6.32 Support mode

Activate support mode to display function ID numbers in every icon. This facilitates easy identification of functions, especially during remote support sessions.

6.33 Installer login

Log in here to access the installer menu.

7. Curve mode

7.1 General

The curves menu pop-up window shows ventilation curve settings. Curve mode is enabled in the installer menu. In the user menu, tap the 'Curve' menu item.

The curve supports eight breakpoints. At each breakpoint, temperature setpoint, minimum curtain position, and maximum curtain position can be adjusted to meet animal needs at a specific age (day). Transitions between breakpoints occur linearly over the days between them.

For example, if the set temperature decreases from 30°C to 20°C between day 10 and day 20, the temperature setpoint at the beginning of day 10 will be 30°C, and at the end of day 10, it will be 29°C. At the beginning of day 20, the set temperature will be 20°C as configured.

[Diagram showing Curve day, Temperature setpoint, Minimum curtain position, Maximum curtain position linked to 'Open curve table']

[Image showing a curve table with values for Day, Temperature, Min. position, Max. position]

7.2 Curve Day

Select the curve day for the following values.

7.3 Temperature setpoint

Enter the temperature setpoint for the specified curve day in the corresponding row.

7.4 Minimum curtain position

The minimum curtain position for the specified curve day in the corresponding row.

7.5 Maximum curtain position

The maximum curtain position for the specified curve day in the corresponding row.

8. Alarm overview

8.1 General

This chapter discusses possible alarms for the BO-AIR PL.

8.2 Resolving alarm situation or silencing the alarm

To deactivate an alarm, tap the alarm icon on the home screen. Once resolved, the icon turns grey. If the alarm persists, the alarm bell icon turns orange, indicating it has been muted. If the BO-AIR PL detects the alarm hasn't been resolved properly within 5 minutes or if a new alarm arises, the display reverts to showing the active alarm bell icon.

! Different alarm icons appear only if the corresponding control is active and an alarm relates to it.

Icon Status Description
? No alarm No alarms are currently active.
? Warning alarm One or more alarms are active, but they have been silenced for 5 minutes.
? Alarm One or more alarms are active, and the alarm relay has been triggered.
IO IO alarm Communication between the front and IO board disrupted. No communication between BP04 and E4 board established.
?️ Left side temperature sensor alarm Measured temperature on the left side is out of range. See note 1.
?️ Right side temperature sensor alarm Measured temperature on the right side is out of range. See note 1.
☀️ Outside temperature sensor defect alarm Measured outside temperature is out of range. See note 1.
? CO2 sensor alarm If measured CO2 value is smaller than 200ppm or larger than 8000ppm, the sensor is considered defective.

RH sensor alarm

Triggered if measured relative humidity (RH) is below 10%. No check for high RH readings (max 100%) is performed. Similar to temperature alarms, this alarm signals even if the controller is deactivated.

Maximum CO2 level alarm

Triggered if the measured CO2 level equals or exceeds the set maximum level.

Maximum humidity alarm

Triggered if the measured humidity level is higher than or equal to the set maximum level.

Left curtain control alarm

Right curtain control alarm

Operation is similar to the left curtain.

Left tunnel inlet control alarm

Operation is similar to the left curtain.

Right tunnel inlet control alarm

Operation is similar to the right curtain.

LMN communication alarm

If the controller is configured to receive data from another BO-AIR PL but fails, an alarm is triggered on the receiving controller. This could be hardware-related or due to faulty configuration (e.g., no BO-AIR PL configured to send data). Additionally, if the controller sends data while another BO-AIR PL sends data in the same timeslot, an alarm is raised on both controllers, requiring user intervention.

Models: 24V version, 230V version, BO-AIR-PL Micro Climate Computer, BO-AIR-PL, Micro Climate Computer, Climate Computer, Computer

File Info : application/pdf, 31 Pages, 860.53KB

PDF preview unavailable. Download the PDF instead.

BO-AIR-PL-G-EN02030

References

Vera Dings Adobe PDF Library 11.0

Related Documents

Preview Stienen AeroWing Air Inlet System for Agricultural Ventilation
Detailed information on the Stienen AeroWing air inlet, designed for optimal climate control in poultry and pig farms. This brochure covers its constant air throw, aerodynamic design, minimal freezing risk, and easy installation, along with technical specifications and benefits for efficient farm ventilation.
Preview PL-9500 Software Update v2.48: New Features and Installation Guide
Details the PL-9500 software update version 2.48 by Stienen, introducing automatic silo switching, imperial units, external alarms, and bug fixes. Includes installation and operational guidance.
Preview Stienen Bravo Touch Climate Control System
Information on the Stienen Bravo Touch climate control system for animal housing, detailing its touch technology, capabilities, and specifications for ventilation, heating, cooling, and environmental monitoring.
Preview Stienen Bravo Touch Climate Control for Livestock Farming
Discover the Stienen Bravo Touch, an advanced climate control system for livestock farming. Featuring a user-friendly capacitive touch screen, the Bravo Touch offers intuitive operation for ventilation, heating, and cooling. Learn about its sensor inputs, capabilities, and technical specifications for optimizing farm environments and energy efficiency.
Preview Stienen BRAVO TOUCH Climate Controller User Manual
This user manual provides comprehensive instructions for operating and maintaining the Stienen BRAVO TOUCH climate controller, designed for pig farming environments. It covers setup, operation, configuration, and alarm management.
Preview Stienen BRAVO TOUCH Climate Control System
Stienen BRAVO TOUCH climate control system for livestock farms, offering advanced touch screen technology for ventilation, heating, and cooling management. Features include sensor inputs for temperature, humidity, CO2, and ammonia, along with digital and analog outputs for precise environmental control.
Preview Stienen Bravo Touch Climate Controller User Manual
User manual for the Stienen Bravo Touch climate controller, designed for pig farming environments. Covers installation, operation, settings, and alarm management.
Preview Stienen AeroWing Ventilation: Optimal Airflow for Livestock
Discover the Stienen AeroWing, an advanced ventilation system designed for optimal airflow and climate control in livestock buildings. Learn about its features, benefits, and specifications for poultry and pig farming.