KOHLER 20RCA(L) Multi-Fuel Generator Set

Models: 20RCA(L) - Multi-Fuel LPG/Natural Gas

The Kohler® Advantage

Standard Features

Model 20RCAL includes a model RXT automatic transfer switch. See last page for more details.

Generator Ratings

Model Alt Voltage Ph Hz Natural Gas LPG Line Circuit Breaker
kW/kVA Amps kW/kVA Amps Amps Poles
20RCA 2F7 120/240 1 60 18/18 75 20/20 84 100 2
20RCAL 120/208 3 60 17/21 59 17/21 59 70 3
20RCA 2G7 120/240 3 60 17/21 51 17/21 51 60 3
277/480 3 60 17/21 26 17/21 26 30 3

Note: The line circuit breaker is automatically selected based on the generator set model and voltage configuration.

RATINGS: Standby ratings apply to installations served by a reliable utility source. All single-phase units are rated at 1.0 power factor. The standby rating is applicable to variable loads with an average load factor of 80% for the duration of the power outage. No overload capacity is specified at this rating. Ratings are in accordance with ISO-3046/1, BS5514, AS2789, and DIN 6271. GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 4% per 305 m (1000 ft.) elevation above 153 m (500 ft.). TEMPERATURE: Derate 2% per 5.5°C (10°F) temperature increase above 16°C (60°F).

Availability is subject to change without notice. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler Co. generator dealer for availability.

[section] Check the appliance manufacturer's specifications for actual power requirements. Consult a Kohler® Power Systems professional to calculate your exact residential power system requirements.

[dagger] Meets NFPA guidelines for 18 inch clearance to combustible materials. Check state and local codes for minimum distance required from a structure.

Alternator Specifications

Specifications Alternator
Manufacturer Kohler
Type 2-Pole, Rotating Field
Leads, quantity
  • 2F7: 4
  • 2G7: 12
Voltage regulator Digital
Insulation: Material NEMA MG1-1.66 Class H
Temperature rise 130°C Standby
Bearing: quantity, type 1, Sealed
Coupling Direct
Amortisseur windings Full
Voltage regulation, no-load to full-load RMS ±1.0%
One-step load acceptance 100% of Rating
Peak motor starting kVA: (35% dip for voltages below)
  • 240 V, 1 ph: 2F7 (4 lead) 41 (60 Hz)
  • 240 or 480 V, 3 ph: 2G7 (12 lead) 69 (60 Hz)

Alternator Features

Engine Specifications

Specifications Engine
Manufacturer Kohler
Engine: model, type CH1000 4-Cycle
Cylinder arrangement V-2
Displacement, cm³ (cu. in.) 999 (61)
Bore and stroke, mm (in.) 90 x 78.5 (3.54 x 3.1)
Compression ratio 8.8:1
Main bearings: quantity, type 2, Heavy-Duty Sleeve Bearings
Rated RPM 3600
Max. engine power at rated rpm, kW (HP)
  • LPG: 23.0 (30.9)
  • Natural gas: 20.2 (27.1)
Cylinder head material Aluminum
Valve material Steel/Stellite®
Piston type and material Aluminum Alloy
Crankshaft material Heat Treated, Ductile Iron
Governor: type Electronic
Frequency regulation, no load to full load Isochronous
Frequency regulation, steady state ±0.5%
Air cleaner type Dry

Engine Electrical System

Exhaust, Lubrication, and Fuel Requirements

Exhaust System

  • Exhaust temperature exiting the enclosure at rated kW, dry, °C (°F): 260 (500)

Lubrication System

  • Type: Full Pressure
  • Oil capacity (with filter), L (qt.) [section]: 1.9 (2.0)
  • Oil filter: quantity, type [section]: 1, Cartridge
  • Oil cooler: Integral

[section] Kohler recommends the use of Kohler Genuine oil and filters.

Fuel Requirements

Fuel System

  • Fuel types: Natural Gas or LPG
  • Fuel supply inlet: 1/2 NPT
  • Fuel supply pressure, kPa (in. H₂O):
    • Natural gas: 0.9-2.7 (3.5-11)
    • LP: 1.7-2.7 (7-11)

Fuel Composition Limits *

Nat. Gas LPG
Methane, % by volume (minimum) 90 min.
Ethane, % by volume (maximum) 4.0 max.
Propane, % by volume 1.0 max. 85 min.
Propene, % by volume (maximum) 0.1 max. 5.0 max.
C4 and higher, % by volume 0.3 max. 2.5 max.
Sulfur, ppm mass (maximum) 25 max. 25 max.
Lower heating value, MJ/m³ (Btu/ft³), (minimum) 33.2 (890) 84.2 (2260)

[asterisk] Contact your local dealer for suitability and rating derates based on fuel compositions outside these limits.

Fuel Pipe Size

Minimum Gas Pipe Size Recommendation, in. NPT

Pipe Length, m (ft.) Natural Gas (281,000 Btu/hr.) LPG (340,000 Btu/hr.)
8 (25) 1 3/4
15 (50) 1 1
30 (100) 1 1/4 1
46 (150) 1 1/4 1 1/4
61 (200) 1 1/4 1 1/4

Generator Set Sound Data

Model 20RCA average sound levels are 66 dB(A) during weekly engine exercise and 70 dB(A) during full-speed generator diagnostics and normal operation. [asterisk]

All sound levels are measured at a distance of 23 ft. (7 m) from the generator set.

[asterisk] Lowest of 8 points measured around the generator. Sound levels at other points around generator may vary depending on installation parameters.

Operation Requirements

Fuel Consumption, m³/hr. (cfh) @ 60Hz

% Load Natural Gas LPG
m³/hr. (cfh) m³/hr. (cfh)
100 8.0 (281) 3.9 (136)
75 6.9 (243) 3.1 (109)
50 4.6 (161) 2.3 (82)
25 3.6 (127) 1.7 (59)
Exercise 2.0 (71) 1.0 (35)

Nominal fuel rating: Natural gas: 37 MJ/m³ (1000 Btu/ft.³)

LPG: 93 MJ/m³ (2500 Btu/ft.³)

LPG conversion factors:

RDC2 Controller Features

The RDC2 controller provides integrated control for the generator set, Kohler® Model RXT transfer switch, programmable interface module (PIM), and load shed kit.

Membrane keypad:

LED indicators:

LCD display:

Scrolling system status display:

Exercise modes:

System settings:

ATS status (Model RXT ATS required):

ATS control (Model RXT ATS required):

Programmable Interface Module (PIM) status displays:

Load control menus:

Generator Set Standard Features

Available Options

Concrete Mounting Pads

Electrical Accessories

[dagger] Battery heater is recommended below -17°C (0°F).

[section] Do not use a carburetor heater with a cold weather kit.

[triple-dagger] Cold weather kit is recommended below 0°C (32°F).

Enclosure Options (single-phase only)

Mossy Oak is a trademark used under license from Haas Outdoors, Inc., by Kohler Co.

Fuel System Accessories

Literature, Maintenance, and Warranty

Literature

Maintenance

Warranty

Warranties cover parts, labor, and travel for the entire warranty period.

Automatic Transfer Switches and Accessories

Generator Set Dimensions and Weights

Generator Set Size, L x W x H: 1193 x 660 x 820 mm (47 x 26.0 x 32.3 in.)

Shipping Weights:

NOTE: Dimensions are provided for reference only and should not be used for planning installation. Contact your local dealer for more detailed information.

DISTRIBUTED BY:

KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com

Models: 20RCAL-200SELS, 20RCAL Multi Fuel LPG Natural Gas, 20RCAL, Multi Fuel LPG Natural Gas, LPG Natural Gas, Natural Gas, Gas

File Info : application/pdf, 4 Pages, 187.42KB

PDF preview unavailable. Download the PDF instead.

445015017

References

Acrobat Distiller 23.0 (Windows)

Related Documents

Preview Kohler 18RCAL Multi-Fuel Standby Generator - Specifications and Features
Detailed specifications, features, and operational data for the Kohler 18RCAL Multi-Fuel Standby Generator, designed for reliable power generation with LPG or natural gas. Includes information on performance, installation, and controller features.
Preview Kohler 14RCA(L) Multi-Fuel Generator: Specifications and Features
Explore the Kohler 14RCA(L) multi-fuel generator, featuring advanced RDC2 controller, Kohler Command PRO engine, premium warranty, and detailed specifications for natural gas and LPG operation.
Preview Kohler 12RES Generator: Features, Specifications, and Accessories
Comprehensive overview of the Kohler 12RES generator, detailing its advantages, standard features, engine and alternator specifications, ADC-RES controller functions, fuel requirements, and available accessories for reliable power generation.
Preview Kohler OnCue Plus Generator Management System
Learn about the Kohler OnCue Plus system, a remote monitoring application for Kohler Residential and Light Commercial generators. Discover its features, applicable models, and system requirements for seamless generator management.
Preview Kohler KG80R Generator Set: Specifications and Features
Detailed specifications and features for the Kohler KG80R generator set, an EPA-certified stationary emergency application unit. Includes information on standard features, alternator specifications, engine details, fuel consumption, cooling, electrical systems, and sound enclosure options.
Preview Kohler KG200 Generator Set: Specifications and Features
Comprehensive details on the Kohler KG200 stationary gas generator set, including EPA certification, performance ratings, standard and optional features, engine specifications, and controller information for natural gas, LP gas, and dual fuel applications.
Preview Kohler 14/18/20RCA Generator Dimension Print and Installation Clearances
Detailed dimension print and installation clearance guidelines for the Kohler 14/18/20RCA series generators, including external views, internal component identification, and required spacing for safe operation.
Preview Kohler RXT Automatic Transfer Switch Operation and Installation Manual
Comprehensive guide for the operation and installation of Kohler RXT Automatic Transfer Switches, detailing safety precautions, electrical wiring, operation sequences, and maintenance schedules for reliable power transfer.