Honeywell Lyric Thermostat Professional Install Guide
This guide provides detailed instructions for the professional installation of the Honeywell Lyric Thermostat.
System Types
Compatible with 24-volt systems such as forced air, hydronic, heat pump, oil, gas, and electric. Does not work with electric baseboard heat (120/240V).
Important Notices
- Mercury Notice: If replacing a control with mercury, do not discard the old control in trash. Contact the Thermostat Recycling Corporation at 1-800-238-8192 or thermostat-recycle.org for proper disposal information.
- Electrical Hazard: Disconnect power before installation. Failure to do so can cause electrical shock or equipment damage.
- Professional Installation Required: Must be installed by a trained, experienced technician. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
Included in Your Box
- Honeywell Lyric Thermostat
- Wall plate
- Screws
- Anchors
- Optional wall cover
- “Getting started” homeowner guide
Installation Steps
Step 1: Install Wall Anchors
Insert the recommended wall anchors. It is recommended to use the provided anchors. Recommended drill bit size is 7/32 – 1/4-inch.
Step 2: Attach Optional Wall Cover
If desired, attach the optional wall cover to the wall plate to hide blemishes. Snap the wall plate to the optional wall cover before proceeding.
Step 3: Bundle and Insert Wires
Guide the wires through the clear rubber holder on the back of the wall plate. Do not remove the clear rubber wire holder.
Step 4: Set Jumper Switches
- R Jumper Switch: For single transformer systems, move the switch up. For dual transformer systems, move the switch down.
- Universal Jumper Switch (for humidifier, dehumidifier, or ventilation): For single wire products, set the switch to '1 Wire'. For two wire products, set the switch to '2 Wire'.
Step 5: Connect All Wires
Push each wire into its corresponding terminal until firmly in place. Gently tug on wires to verify they are secure. To release a wire, use a ballpoint pen to push down on the terminal.
Refer to the 'Wiring' section for detailed configurations.
Note: The illustration shows a common wiring configuration.
Step 6: Mount the Wall Plate
Mount the wall plate using the provided screws.
Step 7: Snap Thermostat into Place
Firmly snap the thermostat onto the wall plate. The thermostat will glow and display the Lyric screen for up to three minutes while it starts up.
Wiring
Terminal Designations
Terminal | Description |
---|---|
L | Heat pump system monitor |
C | Common wire from secondary side of cooling transformer, if 2 transformers |
W2 (AUX) | 2nd stage heat relay (heat pump auxiliary) |
W (O/B) | 1st stage heat relay (changeover valve for heat pumps) |
U1 | Universal terminal for indoor air quality products (humidifier, dehumidifier, ventilator) |
U2 | Universal terminal for indoor air quality products (humidifier, dehumidifier, ventilator) |
K | Optional wire saver module |
G | Fan relay |
Y2 | 2nd stage compressor contactor |
Y | 1st stage compressor contactor |
R | Heating power. Connect to secondary side of heating system transformer |
Rc | Cooling power. Connect to secondary side of cooling system transformer |
Wiring Configurations
Two Stage Furnace and Air-Conditioning
Wiring Diagram Description: Shows connections for L, C, W2, W, G, U1, U2, R terminals on the left, and K, G, Y2, Y, R, Rc terminals on the right, with wires connected to corresponding terminals. The R & RC jumper is also shown.
Terminal Mapping:
- C: Common wire (optional)
- W2: Heat relay (stage 2)
- W: Heat relay
- G: Fan relay
- Y2: Compressor contactor (stage 2)
- Y: Compressor contactor (stage 1)
- R: Power
Notes: Thermostat C wire is optional for this application. Set the R Jumper Switch on the wall plate to R.
Separate Heating and Cooling Transformers
Wiring Diagram Description: Similar to the above, showing connections for L, C, W2, W, G, U1, U2, R terminals on the left, and K, G, Y, R, Rc terminals on the right. The R & RC jumper is shown.
Terminal Mapping:
- C: Common wire (optional)
- W: Heat relay
- G: Fan relay
- Y: Compressor contactor (stage 1)
- R: Power
- Rc: Power
Notes: Thermostat C wire is optional for this application. Set the R Jumper Switch on the wall plate to R & Rc.
Single Stage Heat Pump with Auxiliary Electric Heat
Wiring Diagram Description: Shows connections for L, C, AUX, W2, O/B, U1, U2, R terminals on the left, and K, G, Y2, Y, R terminals on the right. The R & RC jumper is shown.
Terminal Mapping:
- C: Common wire (optional)
- AUX: Auxiliary/Emergency heat
- O/B: Reversing valve
- G: Fan relay
- Y: Compressor contactor (stage 1)
- R: Power
Notes: Thermostat C wire is optional for this application. Set the R Jumper Switch on the wall plate to R.
Two Stage Heat Pump with Auxiliary Electric Heat
Wiring Diagram Description: Shows connections for L, C, AUX, W2, O/B, U1, U2, R terminals on the left, and K, G, Y2, Y, R terminals on the right. The R & RC jumper is shown.
Terminal Mapping:
- C: Common wire (optional)
- AUX: Auxiliary/Emergency heat
- O/B: Reversing valve
- Y2: Compressor contactor (stage 2)
- G: Fan relay
- Y: Compressor contactor (stage 1)
- R: Power
Notes: Thermostat C wire is optional for this application. Set the R Jumper Switch on the wall plate to R.
Power Open Hot Water Zone Valve
Wiring Diagram Description: Shows connections for L, C, AUX, O/B, U1, U2, R terminals on the left, and K, G, Y2, Y, R, Rc terminals on the right. The R & RC jumper is shown.
Terminal Mapping:
- C: Common wire (optional)
- W: Heat relay
- R: Power
Notes: Thermostat C wire is optional for this application. Set the R Jumper Switch on the wall plate to R.
Two Wire Powered Humidifier, Dehumidifier, Ventilator
Wiring Diagram Description: Shows connections for L, C, AUX, W2, O/B, U1, U2, R terminals on the left, and K, G, Y2, Y, R, Rc terminals on the right. The 1 Wire and 2 Wire labels are shown.
Terminal Mapping:
- U1: Universal relay
- U2: Universal relay
Notes: Set the Universal Jumper Switch on the wall plate to 2 Wire.
Single Wire Non-Powered Humidifier, Dehumidifier, Ventilator, or Dehumidification with Low Speed Fan
Wiring Diagram Description: Shows connections for L, C, AUX, W2, O/B, U1, U2, R terminals on the left, and K, G, Y2, Y, R, Rc terminals on the right. The 1 Wire and 2 Wire labels are shown.
Terminal Mapping:
- U1: Universal relay
Notes: Set the Universal Jumper Switch on the wall plate to 1 Wire.
Setup
Use one of the following options to set up the Lyric thermostat:
- Honeywell Lyric App: Download and log in to complete the setup.
- On-screen Menus: Follow instructions on the following pages.
On-Screen Menu Setup Steps:
- Access Main Menu: Press and hold the Weather button (?) for 5 seconds to access the Main Menu.
- View Device Details: Using the down arrow (?), highlight 'Device Details' and press OK. Find the 4-digit password (date code) and record it. Press OK to exit.
- Navigate Setup: Using the down arrow (?), highlight 'Setup' and press OK.
- Select User Type: Using the down arrow (?), highlight 'Contractor' and press OK.
- Enter Password: Use the up (?) or down (?) arrows to select the first digit of the password and press OK. Continue for all four digits.
- Access Contractor Menu: Highlight 'Setup' in the Contractor Menu and press OK.
- Configure Settings: Press the up (?) or down (?) arrows to highlight a setting and press OK. Continue until all settings are configured. For a full list of setup options, see “Setup Options” on page 14. To exit setup early, press the down arrow (?) to highlight 'Exit' and press OK.
- Save Changes: When all settings are configured, you will be prompted to save changes. To save and confirm, highlight 'Yes' and press OK. To exit without saving, press the down arrow (?) to highlight 'No' and press OK.
Setup Options
From the Contractor Menu, highlight 'Set Up' and press OK. Press the up (?) or down (?) arrows to highlight the setting and press OK. Continue until all settings have been configured. You will be prompted to save changes; highlight 'Yes' and press OK to save and exit, or highlight 'Exit' and press OK to exit without saving.
ISU # | Description | Setting |
---|---|---|
1160 | Temperature indication scale | 0 = Fahrenheit 1 = Celsius |
2120 | Heating system type | 1 = Conventional forced air heat 2 = Heat pump 3 = Radiant heat 5 = None (cool only) |
2140 | Heating equipment type | Conventional Forced Air Heat: 1 = Standard efficiency gas forced air 2 = High efficiency gas forced air 3 = Oil forced air 4 = Electric forced air 5 = Hot water fan coil Heat Pump: 7 = Air to air heat pump 8 = Geothermal heat pump Radiant Heat: 9 = Hot water radiant heat 12 = Steam |
2160 | Reversing valve O/B | 0 = O (O/B on cool) 1 = B (O/B on heat) |
2180 | Cool stages / compressor stages (#2120=HP) | 0, 1, 2 |
2200 | Heat stages / backup heat stages (#2120=HP) | Heat stages: 0, 1, 2 Backup heat stages: 0, 1 |
2220 | Fan operation in heat | 0 = No fan 1 = Equipment controls fan 2 = Thermostat controls fan |
2240 | Backup heat type | 31 = Electric forced air 32 = Gas/Oil Forced air (or Fossil forced air) |
2260 | External Fossil Fuel Kit | 0 = Thermostat controls backup heat 1 = External Fossil Fuel Kit controls backup heat |
3120 | Staging control - backup heat differential | Comfort 2.0°F to 15.0°F from setpoint (in 0.5°F increments) 1.0°C to 7.5°C from setpoint (in 0.25°C increments) |
3140 | Backup heat upstage timer | Off 30, 45, 60, 75, 90 minutes 2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hours |
3160 | Compressor lockout / balance point | Off 5°F to 60°F (in 5°F increments) -15.0°C to 15.5°C (in 2.5°C or 3.0°C increments) |
3180 | Backup heat lockout | Off 5°F to 65°F (in 5°F increments) -15.0°C to 18.5°C (in 2.5°C or 3.0°C increments) |
3200 | Cool cycles per hour | 1 - 6 |
3220 | Cool cycles per hour - stage 2 | 1 - 6 |
3240 | Heat cycles per hour | 1 - 12 |
3260 | Heat cycles per hour - stage 2 | 1 - 12 |
3280 | Backup heat cycles per hour | 1 - 12 |
4120 | Adaptive intelligent recovery | 0 = No 1 = Yes |
4160 | Minimum cool setpoint | 50°F to 99°F 10.0°C to 37.0°C |
4220 | Maximum heat setpoint | 40°F to 90°F 4.5°C to 32.0°C |
8100 | Humidifier type | 0 = None 1 = Steam 2 = Bypass or fan powered |
8120 | Humidification - window protection | 0 = Off 1 = On |
8140 | Humidification control | 0 = Humidify only when heat is On 1 = Humidify only when fan is On 2 = Humidify on demand: Thermostat controls fan 3 = Humidify on demand: Humidifier controls fan |
9100 | Dehumidification equipment | 0 = None 1 = A/C with low speed fan 2 = A/C with high speed fan 4 = Whole house dehumidifier |
9140 | Dehumidification equipment setup | 0 = Normally open 1 = Normally closed |
9160 | Dehumidification overcooling limit | 0, 1, 2, 3°F 0.0, 0.5, 1.0, 1.5°C |
9180 | Dehumidifier fan control | 0 = Thermostat controls fan 1 = Equipment controls fan |
10100 | Ventilation type | 0 = None 1 = ERV / HRV 2 = Passive (fan only) 3 = Fresh air damper |
10160 | Ventilation fan control | 0 = Thermostat controls fan 1 = Equipment controls fan |
10240 | Ventilation percent on time | 10% to 100% (in 10 % increments) |
10280 | Ventilation low temperature lockout | Off -20°F to 40°F (in 5°F increments) -29.0°C to 4.5°C (in 2.5°C or 3.0°C increments) |
10300 | Ventilation high temperature lockout | Off 80°F to 110°F (in 5°F increments) 26.5°C to 43.5°C (in 2.5°C or 3.0°C increments) |
10320 | Ventilation high dew point lockout | Off 65°F to 85°F (in 5°F increments) 18.5°C to 29.5°C (in 2.5°C or 3.0°C increments) |
11100 | Home heat setpoint | 40°F to 90°F 4.5°C to 32.0°C (in 0.5°C increments) |
11120 | Home cool setpoint | 50°F to 99°F 10.0°C to 37.0°C (in 0.5°C increments) |
11140 | Setpoint for away mode | 0 = Away setpoints 1 = Smart temperature setpoints |
11160 | Away heat setpoint | 40°F to 90°F 4.5°C to 32.0°C (in 0.5°C increments) |
11180 | Away cool setpoint | 50°F to 99°F 10.0°C to 37.0°F (in 0.5°C increments) |
Advanced Setup
Change Language
To change the language to either English, French, or Spanish:
- From the Main Menu, press the down arrow (?) to highlight 'Language' and press OK.
- Press the down arrow (?) to highlight the desired language and press OK.
- To save and confirm the changes, highlight 'Yes' and press OK. To exit without saving, press the down arrow (?) to highlight 'No' and press OK.
View Device Details
To view device details, such as model, version, Wi-Fi version, and date code:
- From the Main Menu, press the down arrow (?) to highlight 'Device Details' and press OK.
- Press OK to exit back to the main menu.
Perform a System Test
To perform a system test:
- From the Contractor Menu, press the down arrow (?) to highlight 'System Test' and press OK.
- Press the down arrow (?) to highlight the category and press OK.
- Press the down arrow (?) to highlight the test and press OK.
- Once the test is complete, press OK to return to the Contractor Menu.
View Power Supply Details
To view power supply details, such as battery status and external power details:
- From the Contractor Menu, press the down arrow (?) to highlight 'Power Supply' and press OK.
- Press OK to exit.
Frequently Asked Questions
- Will Lyric still work if Wi-Fi connection is lost? Yes, some features, including shortcuts and geofencing, are managed via the Lyric app and will not function without a connection. Temperature can be adjusted directly at the thermostat. Lyric will automatically reconnect to Wi-Fi once the network is restored.
- Will Lyric work with a Static IP Address Network scheme? No, the router network must be set up for Dynamic Host Control Protocol (DHCP) for the thermostat to obtain an IP address. Consult the router's manual for setup instructions.
- What Wi-Fi security standards are compatible with Lyric?
- OPEN
- WEP_PSK
- WPA_TKIP_PSK
- WPA2_AES_PSK
- WPA2_MIXED_PSK
- Lyric is not finding the in-home Wi-Fi network. Lyric operates in the 2.4GHz range. Routers often broadcast two networks: one SSID on the 5GHz radio and one SSID on the 2.4GHz radio. Ensure your smartphone is connecting to the 2.4GHz network if Lyric is not visible.
- Can Lyric be used in a home that does not have Wi-Fi? Yes, Lyric can function as a basic thermostat without Wi-Fi. However, features like geofencing, Fine Tune, and Smart Cues require a Wi-Fi connection.
- Is Wi-Fi needed to control ventilation, humidity, or dehumidification? Yes, these features are managed through the Lyric app.
Troubleshooting
- Installation complete but screen shows 'Lyric' with circles: When power is first restored, the thermostat takes up to three minutes to start up. The display will show circles as it powers on, then a network name (e.g., 'Lyric Stat 03'). Touch 'OK' to begin configuration.
- Multiple users for geofencing: Yes, geofencing triggers based on the last person to leave and the first to return. Each user needs their own Lyric account and should use their login ID and password across devices. No two users should share the same account.
- How to set up multiple users: Access can be granted via the Lyric app. From the home screen, press the menu icon, then the gear wheel next to the location name. Select 'Users', then '+ Add User'. Enter the invitee's email address. If they have a Lyric account, the location is added automatically. If not, they receive an invitation to download the app and create an account. All users share the same privileges.
- Screen goes blank: The display enters sleep mode to conserve energy when no one is near. It can still be controlled via the Lyric app. A motion detector wakes the screen when someone approaches.
- App changes not showing on thermostat: There may be a short delay after making temperature or setting changes in the app.
- Message: Thermostat Power Lost: Indicates power to the thermostat has been interrupted. Confirm the heating and cooling system is powered. If power is normal but the thermostat is offline, contact Lyric Technical Support at 1-800-633-3991.
- Message: Internet Connection Lost: The thermostat is connected to the router, but the router is not connected to the internet.
- Extend signal strength: Wi-Fi signal range depends on the homeowner's router. Consult the router's manual for more information.
- Message: Wi-Fi Signal Lost: The Wi-Fi signal is lost. Wait for reconnection or select a new network from the connection menu. If reconnection fails, troubleshoot the router.
- What happens if power goes out: Settings and shortcuts are stored and managed via the Lyric app. No reset is needed. The thermostat will resume operation automatically when power is restored.
- Thermostat showing as offline: This means the thermostat has lost network connection. Ensure the router is powered and broadcasting. Power cycling the router may be necessary. The thermostat will reconnect automatically when the network is restored.
- Activation email not received: An activation email from connected-Home@alarmnet.com is required for account setup. Check the spam folder if not received within five minutes. Use the 'Resend' button if needed. Contact Lyric Technical Support at 1-800-633-3991 if the email is still not received.
Specifications
Electrical Ratings
Terminal | Voltage (50/60 Hz) | Max. Current Rating |
---|---|---|
W - O/B (Heating) | 18 to 30 VAC | 1.00 A |
W2 - Aux/E (Heating) | 18 to 30 VAC | 0.60 A |
Y (Cooling) | 18 to 30 VAC | 1.00 A |
Y2 (Cooling) | 18 to 30 VAC | 0.60 A |
K | 18 to 30 VAC | 1.00 A |
G (Fan) | 18 to 30 VAC | 0.50 A |
L (Output) | 18 to 30 VAC | 1.00 A |
U1, U2 | 18 to 30 VAC | 0.10 A |
Power Consumption
Full brightness = 3.0 VA
Wi-Fi Communication
2.4GHz band
Temperature Setting Range
Heating: 40 to 90 °F (4.5 to 32 °C)
Cooling: 50 to 99 °F (10 to 37 °C)
Humidification Setting Range
10% to 60% RH
Dehumidification Setting Range
40% to 80% RH
Humidity Display Range
0% to 99% RH
Basic Operations
The Lyric thermostat features a circular interface:
- Center Display: Shows current temperature (large digits) and set temperature (smaller digits above).
- Left Side: Weather icon (tap to view 6 and 12-hour forecasts).
- Right Side: Home/Away icon (tap to set to Home/Away).
- Top/Bottom Indicators: Indicate heating or cooling status.
- Outer Ring: Turn the ring to set your desired temperature. Tap the ring to turn on/off Cooling or Heating.
How to Use the Lyric App
Once your thermostat is configured and connected to your smartphone, you can utilize the following features:
- Access Menu: Tap to access the main menu.
- Thermostat Controls: Tap to access thermostat controls.
- Shortcuts: Double-tap shortcuts to easily activate favorite settings.
- Create Shortcut: Tap to create a new shortcut.
- Edit Shortcut: Tap to edit an existing shortcut.
- View/Adjust Preferences: Tap to view or adjust thermostat preferences.
- Turn On/Off: Double-tap to turn on/off cooling or heating.
- Change Temperature: Drag the temperature control on the app interface.
Get the Most from Lyric
- Geofence: Enable geofencing to automatically adjust settings based on your smartphone's location. You can also manually override settings by tapping the 'Away' button.
- Shortcuts: Tailor comfort to any situation by creating unique shortcuts or saving favorites for easy access via the app.
- Fine Tune: The thermostat considers indoor temperature, humidity, and outdoor weather to make subtle adjustments for optimal comfort.
- Smart Cues: Receive maintenance notifications and extreme condition alerts to help manage your heating/cooling system.
- Adaptive Recovery: The Lyric thermostat learns your heating and cooling cycle times to deliver the right temperature precisely when you want it.