Quell 240V Mains Photoelectric Long Life Smoke Alarm

User Manual

Model: Q2300, Q2300LL

Product Features

The Quell Q2300 / Q2300LL is a 240V AC powered smoke alarm with a DC battery back-up. It ensures protection during power failures and can be interconnected with up to 23 other compatible Quell models (Q2300, Q2300LL, and Q1300). Do not connect to other types or models of smoke or heat alarms not listed.

Warning: Removal of the smoke alarm battery and disconnecting or loss of AC power will render the unit inoperative. The smoke alarm is a sealed unit; return to the supplier for any repairs.

Product Specifications

Model Q2300, Q2300LL
Electrical Rating 240V AC 50Hz, DC battery back up (9V battery). Q2300- back up, 9V battery. Q2300LL- back up, 9V Lithium battery. Q1300 - back up, 9V battery.
Sensor Photoelectric Smoke Sensor
Interconnecting Smoke Up to any combination of 23 other alarm models. Compatible Models include: Q2300 & Q2300LL and Q1300.
Operating Temperature 0 °C to 40°C
Operating Humidity Up to 93% Humidity (Non-Condensing)
Storage and Transport Conditions -20° C to +60° C, 5-95%RH (non-condensing)
Loud alarm 85 decibels at 3 metres

Note: The model Q2300LL has a lithium battery that will last the life of the alarm.

Recommended Locations for Alarms

This alarm must only be wired to a 240VAC 50Hz sine wave supply. Laws on smoke alarms vary by state; consult local fire emergency services or state regulations for specific requirements.

Recommended Locations:

Things to Consider:

For Ceiling Mounting:

For Wall Mounting:

Mobile Home Installation:

For Well Insulated Mobile Homes:

Install alarms as recommended for standard homes. Be aware that poorly insulated walls and roofs can create thermal barriers affecting alarm performance.

For Poorly Insulated Mobile Homes:

Warning: Test your alarm operation after caravan or mobile home vehicle has been in storage, before each trip, and at least once a week during use.

Locations To Avoid:

Note: Smoke alarms are not to be used with detector guards unless the combination has been evaluated and found suitable.

Installation

Danger: Electrical Shock Hazard. Turn off power at the main fuse box or circuit breaker before installation.

Warning: This smoke alarm must be installed by qualified (licensed) electricians only.

Wiring Requirements:

Warning: This alarm cannot be operated from power derived from a square wave or modified square wave inverter, as these can produce high peak voltages that will damage the alarm.

Wiring Instructions:

Caution: Turn off the main power to the circuit before wiring the alarm.

Note: Use approved Australian Standards cable 1.0mm² TPS or larger as required by local codes.

FIGURE 3 "INTERCONNECT WIRING DIAGRAM"

[Diagram showing interconnection wiring between Q2300, Q2300LL, and Q1300 smoke alarms, with connections for AC power (A, N) and interconnect line (I/C).]

Note: AC power should be turned off at this stage.

Caution: Turn off the main power to the circuit before wiring the alarm.

Surface Mount Cable Applications:

  1. Install duct to terminate at the side of the alarm base.
  2. Remove a 'knock out' / 'cable access' on the alarm base.
  3. Position the duct to the alarm base, aligning the channel.
  4. Transition the cable from the duct to the base.
  5. Remove outer sheath if necessary before securing the base to the ceiling.
  6. Terminate cables in the provided terminals according to local code requirements.
  7. Secure the alarm base to the surface with the provided fixings (refer to Figures 4D).

Concealed Cable Applications:

  1. If the cable runs through wall or roof space and enters the rear of the alarm base:
  2. Remove outer sheath if necessary before securing the base to the ceiling.
  3. Terminate cables in the provided terminals according to local code requirements.
  4. Secure the alarm base to the surface with the provided fixings (refer to Figures 4A and 4B).
  5. Ensure no wires obstruct the terminal cover before closing.
  6. Close the terminal cover until it 'clicks' securely.
  7. If the alarm is not interconnected, the interconnect terminal (I/C) remains unused.

[Figures 4A, 4B, and 4C show details of alarm base wiring and terminal cover.]

Mounting Instructions

Battery Activation:

Note: If the battery compartment is empty, the alarm cannot mount on the mounting base.

A. Mounting on the ceiling

[Diagram showing how to slide the alarm onto the mounting base until it clicks.]

B. Mounting on the wall

[Diagram showing how to slide the alarm onto the mounting base until it clicks.]

Figure 5

Note: Please ensure that the battery is installed prior to mounting of the smoke alarm.

Operation And Test

The smoke alarm operates when AC power is applied, a new battery is installed, and testing is complete. When smoke is detected, the horn will sound a loud (85db) pulsating alarm (3 beeps repeating).

Red and Green LED Indicators:

The LEDs are visible through the Push-to-Test button or the LED lens above the test button.

The LEDs indicate the following:

Testing the smoke alarm:

Warning: Test each smoke alarm to ensure it is installed correctly and operating properly. Stand at arm's length when testing; the sounder is loud.

Test the smoke alarm weekly, upon returning from holiday, or after the house has been unoccupied for several days.

Test all smoke alarms weekly by doing the following:

  1. Check that the green LED above the test button is ON, confirming AC power.
  2. Firmly depress and hold the TEST/Hush button for at least five (5) seconds. The alarm will sound 3 long beeps, pause, 3 long beeps, repeating for up to 10 seconds. Release the button.
  3. Note: If alarms are interconnected, all alarms should sound within three (3) seconds after the test button is pushed.
  4. If the smoke alarm does not sound, turn off power at the distribution board, check wiring, and retest. If it still does not sound, contact your electrician.

Warning: If the alarm sounder activates and the unit is not being tested, the alarm is sensing smoke. The sound requires immediate attention and action.

Nuisance Alarms and Hush Function

This alarm is designed to minimize nuisance alarms. Cigarette smoke or cooking smoke blown directly into the alarm may cause it to sound. Using a range hood fan that vents outside can help prevent nuisance alarms.

HUSH

If you know the cause of the alarm and it is not a life-threatening situation, press the button on the alarm to silence it for up to 10 minutes. The alarm will silence if the smoke is not too dense and will automatically reset. If smoke is still present after the Hush period, the alarm will sound again. You can use Hush repeatedly until the air is clear.

Note: Dense smoke will override Hush and sound a continuous alarm. If no fire is present, check LOCATIONS TO AVOID (page 7). If a fire is discovered, exit the building and call the fire brigade.

Troubleshooting

PROBLEM SOLUTION
Smoke alarm does not sound when tested. 1. Check that AC power is turned on (Green LED illuminated).
2. Check that the battery is installed correctly (see page 15).
Single chirp about once every 40 seconds Turn off AC power and replace the battery (see page 15: Battery Replacement).
Smoke alarm sounds unwanted alarms (e.g., from cooking, showers). Relocate the smoke alarm to a new location using a licensed electrician (see page 8: Installation Instructions and page 7: Locations to Avoid).
Interconnected smoke alarms do not sound when system is tested. 1. Press and hold the button for at least 5 seconds after the initiating unit sounds.
2. Engage a licensed electrician to verify the interconnect wiring (see Section 5 Wiring instructions).
3 chirps every 40 seconds 1. Before 10 years of operation: unit is in fault mode. If fault continues, contact customer service.
2. After 10 years of operation: end of life warning. Replace the alarm IMMEDIATELY!

Note: Contact Customer Service at 1800 672 171 if your alarm does not seem to operate correctly.

Battery Replacement

Alarm removal:

Press down the resist tab on the mounting base and release the alarm (see Figure 6).

[Figure 6 shows how to remove the alarm from the mounting base.]

Battery Installation and Replacement:

After removing the alarm, you can replace the battery (see Figure 7).

Note: If the battery compartment is empty, the alarm cannot mount on the mounting base.

[Figure 7 shows battery installation.]

USE ONLY THE FOLLOWING 9VOLT REPLACEMENT BATTERIES:

Note: Weekly testing is recommended.

Warning: Use only the specified batteries. Different batteries may have a detrimental effect on the alarm. Exposure to temperature extremes and/or high humidity may reduce battery life.

Cleaning Your Alarm

YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR

To clean your alarm, remove it from the mounting bracket (page 16 Battery Replacement or page 11, Figure 5). Clean the interior (sensing chamber) using compressed air or a vacuum cleaner hose through the openings around the perimeter. Wipe the outside with a damp cloth.

After cleaning, reinstall the alarm and test it using the test button. If cleaning does not restore normal operation, the alarm should be replaced.

After cleaning, reinstall your alarm and check that the green LED is on. Then test your alarm using the test button.

Limitations Of Smoke Alarms

Warning: Smoke alarms provide early warning but have sensing limitations.

Ionization alarms detect invisible fire particles (fast flaming fires) sooner than photoelectric alarms. Photoelectric alarms detect visible fire particles (slow smoldering fires) sooner than ionization alarms.

Home fires are unpredictable. For maximum protection, Quell recommends installing both ionization and photoelectric alarms, subject to applicable legal requirements.

Loose batteries must be of the specified type, in good condition, and installed properly. AC-only alarms will not operate if AC power is cut off. All alarms must be tested regularly.

Life safety relies on early notification and appropriate egress actions. If an alarm is located outside a sleeping room or on a different floor, it may not wake a sound sleeper. Alcohol or drugs can impair hearing. For maximum protection, install a smoke alarm in each sleeping area on every level of a home.

Smoke alarms cannot provide an alarm if smoke does not reach the unit. They may not sense fires starting in chimneys, walls, on roofs, behind closed doors, or on different floors.

Hearing-impaired individuals should consider additional accessories for visual or tactile alarms.

Smoke alarms help save lives by providing early warning but do not prevent property damage. Ensure adequate home insurance.

If you believe your smoke alarm is defective, do not tamper with it.

Good Safety Habits

DEVELOP AND PRACTICE A PLAN OF ESCAPE:

What To Do When The Alarm Sounds

Warranty & Contact Details

TEN YEAR WARRANTY

Quell warrants to the original consumer purchaser that each new alarm will be free from defects in materials and workmanship under normal use for 10 years from the date of purchase. Quell agrees to repair or replace any defective product upon presentation of proof of purchase.

Australia warranty claims:

Warranty benefits are in addition to rights under the Australian Consumer Law. Consumers are entitled to replacement or refund for a major failure and compensation for other loss or damage. Goods are also entitled to repair or replacement if they fail to be of acceptable quality.

New Zealand warranty claims:

Warranty benefits are in addition to rights under relevant New Zealand consumer protection laws. Consumers are entitled to replacement or refund for a major failure and compensation for other loss or damage. Goods are also entitled to repair or replacement if they fail to be of acceptable quality.

Exclusions

This warranty does not cover:

To make a claim:

If a defect appears within the warranty period, return the product to the address below. Contact Chubb Monday to Friday, 9:00 AM - 5:00 PM. Ensure the product is properly packaged to prevent transit damage. Postage and packaging expenses are at your cost. Provide original or copy of proof of purchase and an explanation of the problem.

Chubb may elect to repair the product using refurbished goods or parts.

This warranty is provided by:

Chubb Fire & Security Pty Ltd
ABN 47 000 067 541
Building F, Unit 1
3-29 Birnie Avenue, Lidcombe, NSW, Australia
Telephone: 1800 654 435
Website: www.quell.com.au

Chubb New Zealand
3 Fisher Crescent, Mt Wellington, Auckland, New Zealand
Telephone: 09 270 7288
Website: www.quell.co.nz

Models: Q2300 Q2300LL 240V Mains Photoelectric Long Life Smoke Alarm, Q2300, Q2300LL, 240V Mains Photoelectric Long Life Smoke Alarm, Mains Photoelectric Long Life Smoke Alarm, 240V Photoelectric Long Life Smoke Alarm, Long Life Smoke Alarm, Life Smoke Alarm, Smoke Alarm, 240V Smoke Alarm, Alarm

File Info : application/pdf, 24 Pages, 1.13MB

PDF preview unavailable. Download the PDF instead.

1373-7216-00 Q2300 Q2300LL User Manual V1

References

Adobe PDF Library 10.0.1 Adobe InDesign CS6 (Macintosh)

Related Documents

Preview Quell 240V Mains Photoelectric Smoke Alarm User Manual
User manual for the Quell Q2300 and Q2300LL 240V Mains Photoelectric Smoke Alarm, covering features, specifications, installation, operation, testing, troubleshooting, and warranty information.
Preview Quell Smoke Alarm Product Selection Guide
Compare Quell smoke alarms and carbon monoxide alarms. Find the right smoke detector for your home with Quell's easy-to-use product selection guide, featuring detailed specifications, features, and model comparisons.
Preview Quell Wearable Pain Relief Technology Quick Start Guide
A quick start guide for Quell Wearable Pain Relief Technology, detailing therapy sessions, adjustments, and setup options via app or manual calibration. Includes important guidelines and warnings for safe and effective use.
Preview Quell Home Fire Safety Kit: Essential Fire Protection for Home and Vehicle
Comprehensive guide to the Quell Home Fire Safety Kit, featuring a 1.0kg ABE fire extinguisher and a 1.0m x 1.0m fire blanket. Certified to Australian Standards for effective fire safety in homes, vehicles, boats, and caravans.