Blueridge Free Match Series R410A System-Outdoor Unit

Owner's Manual - Commercial Air Conditioners

Model: BMKH42M-NDG3

Preface

The Blueridge Free Match System utilizes cutting-edge manufacturing technology and the globally acknowledged, environmentally-friendly R410A refrigerant, positioning it as a green product for the 21st century. Please read this manual carefully before installation and operation.

Important Instructions Before Reading:

  • This unit complies with UL1995 standards.
  • The Free Match System conforms to the design standard ARI 210240-2008.
  • For personal safety during operation, strictly follow the instructions provided in this manual.
  • The total capacity of indoor units operating simultaneously must not exceed that of the outdoor unit; otherwise, cooling (heating) performance for each indoor unit may be poor.
Connectable Unit Capacity
ModelMinimum number of connectable indoor unitsMaximum number of connectable indoor unitsMinimum capacity of connectable indoor unitsMaximum capacity of connectable indoor units
30K2418K Btu42K Btu
36K2518K Btu48K Btu
BMKH42M-NDG32518K Btu56K Btu

Operational Notes:

  • Switch the main power on 8 hours before starting the unit to ensure a successful startup.
  • It is normal for the indoor unit fan to continue running for 20-70 seconds after receiving the "stop" signal, allowing for efficient use of residual heat for the next operation.
  • If the running modes of the indoor and outdoor units conflict, an indicator will appear on the wired controller within five seconds, and the indoor unit will stop. To restore normal operation, harmonize the running modes: cooling mode is compatible with dehumidifying mode, and fan mode is compatible with any other mode. If power fails during operation, the indoor unit will send a "start" signal to the outdoor unit three minutes after power recovery.
  • Cautions for Debugging and Maintenance Personnel: Prior to compressor startup during debugging and maintenance, ensure the compressor's heating belt has been energized for at least eight hours. Once started, the compressor must run continuously for at least 30 minutes to prevent damage.

User Notice

This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning the appliance's use by a person responsible for their safety. Children should be supervised to ensure they do not play with the appliance.

This appliance is intended for use by expert or trained users in shops, light industry, and on farms, or for commercial use by laypersons.

DISPOSAL: Do not dispose of this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.

Safety Precautions

⚠️ WARNING: This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

⚠️ WARNING: This mark indicates procedures which, if improperly performed, might lead to death or serious injury.

⚠️ CAUTION: This mark indicates procedures which, if improperly performed, might possibly result in personal harm or property damage.

NOTICE: Used to address practices not related to personal injury.

General Safety Instructions:

  • Installation and use instructions are provided by the manufacturer with each unit.
  • Installation must be performed by authorized personnel in accordance with NEC and CEC requirements.
  • Before installation, verify power supply compatibility with the nameplate specifications and ensure power safety.
  • Properly earth the unit after plugging it into the socket to prevent electric shock. Do not connect the ground wire to gas pipes, water pipes, lightning rods, or telephone lines.
  • Use only exclusive accessories and parts to prevent water leakage, electric shock, and fire accidents.
  • If refrigerant leakage occurs during installation, ventilate the area immediately. Refrigerant gas can form poisonous gas if it meets fire.
  • Ensure the power cord wire size is adequate. Replace damaged power cords or connection wires with exclusive cables.
  • Securely fix the electric box cover after connecting the power cord to prevent accidents.
  • Always comply with nitrogen charge requirements and charge nitrogen when welding pipes.
  • Never short-circuit or bypass the pressure switch to prevent unit damage.
  • Connect the wired controller before energization; otherwise, it cannot be used.
  • Before use, check piping and wiring for correctness to avoid water leakage, refrigerant leakage, electric shock, or fire.
  • Do not insert fingers or objects into the air outlet/inlet grille.
  • Ensure good ventilation by opening doors and windows when using gas/oil supplied heating equipment to avoid oxygen deficit.
  • Never start or stop the air conditioner by directly plugging or unplugging the power cord.
  • Turn off the unit only after it has run for at least five minutes; otherwise, compressor oil return may be affected.
  • Do not allow children to operate this unit.
  • Do not operate the unit with wet hands.
  • Turn off the unit or cut off the power supply before cleaning to prevent electric shock or injury.
  • Never spray or flush water directly at the unit, as this may cause malfunction or electric shock.
  • Do not expose the unit to moist or corrosive environments.
  • Energize the unit 8 hours before operation. Do not cut off power during a 24-hour short-time halt to protect the compressor.
  • Volatile liquids, such as diluents, can damage the unit's appearance. Clean the outer casing with a soft cloth and a little neutral detergent.
  • During cooling mode, avoid setting the room temperature too low. Maintain a temperature difference of no more than 41°F (approx. 5°C) between indoor and outdoor units.
  • If any abnormality occurs (e.g., burning smell), immediately power off the unit, cut off the main power supply, and contact a Blueridge appointed service center. Continued abnormality may lead to unit damage, electric shock, or fire.
  • Users are not permitted to repair the unit. Faulty service may cause electric shock or fire accidents. Contact a Blueridge appointed service center for assistance.

Blueridge is not responsible for personal injury or equipment damage caused by improper installation, commissioning, unnecessary service, or failure to follow the rules and instructions in this manual.

Product Introduction

The Blueridge Free Match System employs inverter compressor technology, enabling stepless capacity regulation from 15% to 120% based on compressor displacement changes. With a capacity range from 30K to 42K Btu, it is suitable for boarding houses, working areas, and locations with variable load changes, making it an excellent choice for commercial air conditioning.

2.1 Name of Main Parts

The outdoor unit comprises the following main components:

  • (1) Motor: Powers the fan.
  • (2) Fan: Circulates air.
  • (3) Electric Box: Houses electrical components.
  • (4) Gas valve assembly: Manages refrigerant gas flow.
  • (5) Liquid valve assembly: Manages refrigerant liquid flow.

The unit features air inlets on the sides and an air outlet at the front.

2.2 Combinations for Outdoor and Indoor Units

The Free Match Series air conditioning system allows one outdoor unit to operate up to five indoor units. These indoor units can be of various types, including Wall Mounted, Duct Type, Cassette Type, and Flooring Ceiling types.

The outdoor unit operates whenever any indoor unit receives a running command. All indoor units stop when the outdoor unit is turned off.

Table 1: Energy Level and Capacity Code of the Indoor Units
Indoor unit ModelCapacity CodeOutdoor unit
Cozy (Wall mounted)09K30K36KBMKH42M-NDG3
12K
18K
24K
Hansol (Wall mounted)09K
12K
18K
24K
Flooring ceiling09K
12K
18K24K
Duct type09K
12K
18K
21K
Cassette type24K
12K
18K
Console24K
09K
12K
18K

2.3 Rated Working Condition

Table 2: Rated Working Condition
RatingIndoor side stateOutdoor side state
Dry bulb temp. °FWet bulb temp. °FDry bulb temp. °FWet bulb temp. °F
Cooling80.0666.929575.02
Heating69.9860.084743.00

NOTICE:

  1. Cooling/heating capacity and noise levels are tested before shipment.
  2. Parameters are tested under rated working conditions. Refer to the nameplate for any changes.
  3. Heating capacity parameters exclude auxiliary electric heating power.
  4. Performance parameters are tested according to ANSI/AHRI 1230-2010.

2.4 The Range of Production Working Temperature

Table 3: Production Working Temperature Range
ConditionTemperature Range
Cooling Working rangeOutdoor temperature 0~118°F
Heating Working rangeOutdoor temperature -4~86°F

Preparation before Installation

3.1 Standard Parts

Use the following standard parts supplied by Blueridge:

Table 4: Parts of Outdoor Unit
NumberNamePicture DescriptionQuantityRemark
1Owner's manualA booklet titled "Free Match Series R410A System-Outdoor Unit Owner's Manual"1
2Tube connector subassemblyA set of connectors for refrigerant pipes.30K: 8
36K: 8
42K: 9

3.2 Selecting Installation Site

⚠️ WARNING:

  • Install the unit where it can adequately withstand its weight and will not shake or fall off.
  • Avoid direct sunshine and rainfall. Install the unit in a location protected from dust, typhoons, and earthquakes.
  • Keep the unit away from combustible, inflammable, and corrosive gases or exhaust gases.
  • Ensure sufficient space for heat exchange and servicing to guarantee normal operation.
  • Position indoor and outdoor units close to each other, considering pipe length and bends.
  • Prevent children from approaching the unit and take measures to avoid contact.

When the outdoor unit is surrounded by walls, follow the installation space requirements shown in Fig. 3:

Fig. 3 Description: Installation space diagram for an outdoor unit surrounded by walls, showing dimensions in inches: 78 3/4 inches height, 39 3/8 inches width, with 19 2/3 inches clearance on the sides.

3.3 Piping Connection

The maximum pipe length is detailed in the table below. Exceeding these limits may affect normal unit operation.

Table 5: Piping Specifications and Height Difference
ModelConnecting Pipe (inch)Max. Pipe length(ft)Max. Height Difference between Indoor Unit and Outdoor Unit (ft)
LiquidGas
30K1/4"3/8"229.6When the outdoor unit is above, maximum height difference is up to 49.2ft; When the indoor unit is above, maximum height difference is up to 49.2ft.
36K1/4"3/8"246.1
BMKH42M-NDG31/4"3/8"246.1

NOTICE:

  • Use water-proof insulating pipe.
  • Pipe wall thickness should be 0.019-0.039 inches, with a bearing pressure of 3.0MPa.
  • Longer connection pipes may decrease cooling and heating capacity.

Installation Instruction

4.1 Outline and Dimension of the Outdoor Unit

For 30K Model:

Fig. 4 Description: Outline and mounting hole dimensions for the 30K outdoor unit, shown in inches. Front view shows width approx. 38 3/7 inches. Side view shows height approx. 31 inches and depth approx. 15 5/7 inches. Top view shows width approx. 36 2/9 inches and depth approx. 17 1/3 inches.

For 36K and BMKH42M-NDG3 Models:

Fig. 5 Description: Outline and mounting hole dimensions for the 36K and BMKH42M-NDG3 outdoor units, shown in inches. Front view shows width approx. 42 1/2 inches. Side view shows height approx. 43 3/7 inches and depth approx. 15 3/4 inches. Top view shows width approx. 40 inches and depth approx. 17 1/3 inches.

4.2 Installation of the Connection Pipe

Connecting piping for indoor and outdoor units is done in a manifold mode, as illustrated in Fig. 6.

Fig. 6 Description: Diagram showing refrigerant piping connecting one outdoor unit to multiple indoor units (wall-mounted, duct, cassette, flooring ceiling types).

4.2.1 Piping between the Indoor and Outdoor Units

  • If liquid and gas stop valves (A, B, C, D, E) are not connected to indoor units, turn off the screw cap with a spanner to ensure airtightness.
  • Refer to Fig. 7 for screw tightening torque moments.
  • Align the flare end of the copper pipe with the screw and tighten by hand.
  • Subsequently, tighten the screw using a torque wrench until it clicks, as shown in Fig. 7.
  • Avoid bending the pipe at excessively small angles, which could cause cracking. Use a pipe tube bender for all bends.
  • Wrap exposed refrigerant pipes and joints with sponge and secure with plastic tape.

Fig. 7 Description: Diagram illustrating the connection of a pipe, flare nut, spanner, and torque wrench. A table lists pipe diameters (1/4", 3/8", 1/2", 5/8"), copper tube thickness (≥0.0315 inch or ≥0.0394 inch), and corresponding tightening torque values (e.g., 11-22 ft·lbf for 1/4" pipe).

CAUTION:

  • When connecting indoor units and refrigerant pipes, do not pull any joints by force to prevent cracking of capillary or other pipes, which could lead to leakage.
  • Support refrigerant pipes with brackets; do not let the unit bear their weight.
  • If the piping connection size of the outdoor unit differs from the indoor unit, use the indoor unit's connection dimension and appropriate different-diameter joints.
  • For the Free Match system, label each pipe to identify its corresponding system and avoid incorrect piping.

4.2.2 Allowable Pipe Length and Drop Height

No additional refrigerant is required if the total refrigerant pipe length (liquid pipe) is within the limits specified in Table 6.

Table 6: Total Liquid Pipe Length
ModelTotal Liquid Pipe Length (a+b+c+d+e)
30K131.2ft
36K131.2ft
BMKH42M-NDG3131.2ft

Fig. 8 Description: Diagram illustrating equivalent length of the farthest fitting pipe (Lx) and height differences (H1, H2, H3) between indoor and outdoor units. It shows an outdoor unit connected to multiple indoor units (a-e) with pipe segments (L1-L5).

Table 7: Allowable Length and Height Fall of the Refrigerant Pipe
ParameterAllowable Value30K36KBMKH42M-NDG3Fitting Pipe
Total length (actual length) of fitting pipe229.6ft246.1ft246.1ftL1+L2+...+LM (M≤5)
Length of farthest fitting pipe (ft)82ft82ft82ftLx (X=1,2,3,4,5)
Height difference between outdoor unit and indoor unitOutdoor unit at upper49.2ft49.2ft49.2ftH1
Outdoor unit at lower49.2ft49.2ft49.2ftH3
Height difference between indoor units (m)24.6ft24.6ft24.6ftH2

4.2.3 Installation of the Protection Layer of the Refrigerant Pipe

  • Insulate the refrigerant pipe with insulating material and plastic tape to prevent condensation and water leakage.
  • Wrap the joints of the indoor unit with insulating material, ensuring no gaps, as shown in Fig. 9.

Fig. 9 Description: Cross-section of a refrigerant pipe joint showing the application of thermal insulating layer and plastic tape, emphasizing the need for "No gap".

After adequate pipe protection, avoid bending it at sharp angles to prevent cracking or breaking.

(3) Wrap the Pipe with Tape:

  • Bundle the refrigerant pipe and electric wire together with tape, separating them from the drain pipe to prevent condensate overflow.
  • Wrap the pipe from the bottom of the outdoor unit to where it enters the wall. Overlap the previous wrap by half.
  • Secure the wrapped pipe to the wall using clamps.

CAUTION:

  • Do not wrap the pipe too tightly, as this can weaken the insulation effect. Ensure the drain hose is kept separate from the pipe.
  • After installation, seal the hole in the wall with sealing material to prevent wind and rain ingress.

4.2.4 Support and Protection for Pipeline

Provide support for hanging connection pipes. The distance between supports should not exceed 1 meter.

4.3 Air Purging and Refrigerant Charge

4.3.1 Air Purging

  1. The outdoor unit is pre-charged with refrigerant before shipment; additional refrigerant is needed for the refrigerant pipe during field installation.
  2. Ensure the liquid and gas valves of the outdoor unit are fully closed.
  3. Expel air from the indoor unit and refrigerant pipe using a vacuum pump, as depicted in Fig. 10.

Fig. 10 Description: Diagram illustrating the air purging process. It shows a setup with a liquid valve ("LO" Knob), gas valve ("HI" Knob), two manometers, a vacuum pump, and a connection hose.

(4) With the compressor not running, charge R410A refrigerant into the pipe via the outdoor unit's liquid valve (not the gas valve).

4.3.2 Additional Refrigerant Charging

Refrigerant Charge in the Outdoor Unit before Shipment

NOTICE:

  • The outdoor unit is pre-charged with refrigerant before delivery. This charge does not include any additional refrigerant added to the indoor unit or refrigerant pipe.
  • The amount of additional refrigerant charge depends on the diameter and length of the liquid refrigerant pipe, determined by installation requirements.
  • Record the additional refrigerant charge for future maintenance.

(2) Calculation of the Additional Refrigerant Charge:

Additional Refrigerant Charge = (Length of Liquid Pipe × 0.375 × 54 + Length of Liquid Pipe × 0.25 × 22) - 880

The maximum allowable additional refrigerant charge is 800g. If the calculated value exceeds 800g, use 800g. If it is less than 800g, use the calculated value.

4.4 Electric Wiring

4.4.1 Wiring Precautions

  • Installation must comply with national wiring regulations.
  • Use only power cords with the correct voltage rating and dedicated circuits for the air conditioning.
  • Do not pull the power cord forcefully.
  • Electrical installation should be performed by a technician according to local laws, regulations, and this manual.
  • The power cord diameter must be sufficient; replace any damaged cord with a dedicated one.
  • Ensure reliable earthing by connecting the earth wire to a dedicated building device. Equip the system with an air switch and a leakage current protection switch that have adequate capacity and magnetic/thermal tripping functions for short circuits and overloads.
Table 8: Electrical Specifications
ModelsPower SupplyCapacity of the Air Switch (A)Recommended Cord (pieces × sectional area)
30K208/230V~60Hz303×0.0062 sq in
36K208/230V~60Hz353×0.0062 sq in
BMKH42M-NDG3208/230V~60Hz403×0.0062 sq in

Fig. 11 Description: Wiring diagram for the 30K model, showing connections from the power supply to the outdoor unit terminals (XT, XTA, XTB, XTC, XTD) and then to indoor units A, B, C, and D, including grounding (G).

Fig. 12 Description: Wiring diagram for the 36K and BMKH42M-NDG3 models, showing connections from the power supply to the outdoor unit terminals (XT, XTA, XTB, XTC, XTD, XTE) and then to indoor units A, B, C, D, and E, including grounding (G).

4.4.2 Earthing Requirements

  • The air conditioner is classified as Class I appliance; reliable earthing is mandatory.
  • The yellow-green wire is the earth line and must not be used for other purposes, cut off, or fixed with tapping screws, as this poses a risk of electric shock.
  • Provide a reliable earth terminal. Do not connect the earth wire to running water pipes, coal gas pipes, sewage pipes, or other locations deemed unreliable by professionals.

4.4.3 Electrical Cable Connection

CAUTION:

  • Incorrect wiring can lead to malfunction. After wiring, ensure wires have sufficient slack between connection and fixed points.
  • Connect piping and wiring for each indoor unit according to instructions.
  • Electrical installation must be performed by a technician following local laws, regulations, and this manual.
  • The installation location should be dry and protected from direct sunlight or strong breezes.
  • Install a breaker in the circuit to shut off the main power supply. An air switch with leakage current protection is also required.

4.4.4 Wiring of the Power Cord

  1. Open the side plate.
  2. Connect the power cord to terminals "L1", "L2", and the earthing screw. Connect the wiring terminals "N(1), 2, 3" of the indoor unit to the outdoor unit correspondingly. Use the green bonding screw for the earthing cord, as shown in Fig. 13.
  3. Secure the power cord with wire clips.
  4. Route the power cord through the rubber ring.

CAUTION: If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or a similarly qualified person to avoid hazards.

Fig. 13 Description: Detail showing the connection of the power cord to the terminal block, highlighting the location to "Tighten the green bonding screw here" for the earthing cord.

Troubleshooting

⚠️ WARNING: In case of abnormal conditions (e.g., strange smell), immediately shut off the main power supply and contact a Blueridge appointed service center. Continued abnormal operation can damage the unit and pose risks of electric shock or fire.

Do not attempt personal repairs; contact qualified personnel at a Blueridge appointed service center, as incorrect repairs can cause electric shock or fire hazards.

Check before Contacting Service Center

Table 9: Troubleshooting Checklist
Check ItemsConditions Might HappenCheck
Has the unit been fixed firmly?The unit may drop, shake, or emit noise.
Have you done the gas leakage test?It may cause insufficient cooling/heating capacity.
Is the unit get proper thermal insulation?It may cause condensation and dripping.
Does the unit drain well?It may cause condensation and dripping.
Is the voltage in accordance with the rated voltage specified on the nameplate?It may cause malfunction or damage the part.
Is the electric wiring and piping connection installed correctly and securely?It may cause malfunction or damage the part.
Has the unit been earthed securely?It may cause electrical leakage.
Is the power cord specified?It may cause malfunction or damage the part.
Has the inlet and outlet been blocked?It may cause insufficient cooling/heating capacity.

NOTICE! If the air conditioner continues to run abnormally after these checks, please contact a local appointed service center and provide a description of the error and the unit model.

6 The Conditions Listed Below Are Not Classified Into Errors

Table 10: Normal Operating Conditions and Causes
ConditionCause
The unit does not runWhen restart the unit soon after it is stopped: The overload protection switch delays startup for three minutes. As soon as power is on: The unit will stand by for approximately one minute.
The unit blows out mistWhen the cooling operation starts: High-humidity indoor air is cooled rapidly.
The unit generates noiseThe unit "clatters" as soon as it starts running: Sound generated during electronic expansion valve initialization. The unit "swishes" during cooling operation: Sound of refrigerant gas flowing inside the unit. The unit "swishes" when it is started or stopped: Sound of refrigerant gas stopping. The unit "swishes" when it is in and after running: Sound from the draining system operating. The unit "squeaks" when it is in and after running: Sound from panel expansion due to temperature changes.
The unit blows out dust.When the unit restarts after a long period of shutdown: Dust inside the unit is blown out.
The unit emits odors.When the unit is running: Odors absorbed by the unit are blown out.

NOTICE! If problems persist after checking these items, contact the Blueridge service center with the observed phenomena and unit models.

Following Circumstances Are Not Malfunction

Table 11: Non-Malfunction Circumstances
Malfunction DescriptionReason
Unit doesn't runWhen unit is started immediately after it is just turned off: Overload protection switch makes it run after 3 minutes delay. When power is turned on: Standby operating for about 1 minute.
Mist comes from the unitUnder cooling: Indoor high humidity air is cooled rapidly.
Noise is emittedSlight cracking sound when just turned on: Noise from electronic expansion valve initialization. There is consecutive sound when cooling: Sound of gas refrigerant flowing in the unit. There is sound when unit starts or stops: Sound of gas refrigerant stopping flow. There is slight and consecutive sound when unit is running or after running: Sound from the drainage system. Cracking sound when unit is operating and after operating: Sound caused by expansion of panel and other parts due to temperature change.
The unit blows out dust.When unit runs after no operation for a long period: Dust in the indoor unit is blown out.
The unit emits odor.Operating: Room odor absorbed by the unit is blown out again.
Indoor unit still runs after switch offAfter every indoor unit receives "stop" signal, fan will keep running 20-70s to utilize residual cooling/heating and prepare for next operation.

Mode Conflict

Condition: COOL or HEAT mode cannot be operated.

Reason: When the indoor operating mode conflicts with the outdoor unit's mode, the indoor fault indicator will flash, and the conflict will be displayed on the wired controller after 5 minutes. The indoor unit will stop running and adjust its operating mode to match the outdoor unit. The unit will then return to normal. COOL mode does not conflict with DRY mode. FAN mode does not conflict with any mode.

7 Troubleshooting

Error codes will be displayed on the wired controller and the main board of the outdoor unit. The meaning of each error is shown in Table 12.

Table 12: Malfunction Indicator Display
Name of MalfunctionThe Indicator Display
Yellow lightRed lightGreen light
Compressor runsFlash once
DefrostFlash twice
Anti-freezing protectionFlash 3 times
IPM protectionFlash 4 times
AC over-current protectionFlash 5 times
Over-burden protectionFlash 6 times
Compressor exhaust high temperature protectionFlash 7 times
Compressor overload protectionFlash 8 times
Power protectionFlash 9 times
EEPROM reads and write protectionFlash 11 times
Low PN voltage protectionFlash 12 times
Over voltage protection for PNFlash 13 times
PFC protectionFlash 14 times
PFC module temperature protectionFlash 15 times
Low pressure protectionFlash 17 times
High pressure protectionFlash 18 times
Limit/decline frequency (electric current)Flash 1 time
Frequency limit (exhaust)Flash 2 times
Frequency limit (Over-burden)Flash 3 times
Outdoor ambient sensor malfunctionFlash 6 times
Outdoor tube sensor malfunctionFlash 5 times
Exhaust sensor malfunctionFlash 7 times
Attain the temperature of switch onFlash 8 times
Frequency limit (power)Flash 13 times
Outdoor fan malfunctionFlash 14 times
Frequency limit (PFC module temperature)Flash 15 times
PFC module sensor malfunctionFlash 16 times
Liquid pipe temperature sensor malfunction of AFlash 17 times
Gas pipe temperature sensor malfunction of AFlash 18 times
Liquid pipe temperature sensor malfunction of BFlash 19 times
Gas pipe temperature sensor malfunction of BFlash 20 times
Liquid pipe temperature sensor malfunction of CFlash 21 times
Gas pipe temperature sensor malfunction of CFlash 22 times
Liquid pipe temperature sensor malfunction of DFlash 23 times
Gas pipe temperature sensor malfunction of DFlash 24 times
Liquid pipe temperature sensor malfunction of EFlash 25 times
Gas pipe temperature sensor malfunction of EFlash 26 times
Exit of the condenser tube sensor malfunctionFlash 27 times
Correspondence is normalFlash n times (n=indoor unit number)
Communication failure between indoor unit and outdoor unitOften bright (indoor unit all Communication failure)

Maintenance

Regular checks, maintenance, and care should be performed by professional personnel to prolong the unit's lifespan.

8.1 Outdoor Heat Exchanger

Clean the outdoor heat exchanger every two months. Use a vacuum cleaner with a nylon brush to remove dust and debris. Compressed air can be used to blow away dust if available. Never use water to wash the heat exchanger.

8.2 Drain Pipe

Regularly check the drain pipe for clogs to ensure smooth condensate drainage.

8.3 Notice before Seasonal Use

  1. Check if the inlet/outlet of the indoor/outdoor unit is clogged.
  2. Verify that the ground wire is reliably earthed.
  3. Check if the remote wireless controller's batteries have been replaced.
  4. Ensure the filter screen is securely fitted.
  5. After a long period of shutdown, turn on the main power switch 8 hours before re-operation to preheat the compressor crankcase.
  6. Check if the outdoor unit is installed firmly. If any abnormality is found, contact the Blueridge appointed service center.

8.4 Maintenance after Seasonal Use

  1. Turn off the unit's main power supply.
  2. Clean the filter screen and both indoor and outdoor units.
  3. Remove dust and debris from the indoor and outdoor units.
  4. If rusting occurs, apply anti-rust paint to prevent its spread.

8.5 Parts Replacement

Purchase replacement parts from a Blueridge appointed service center or dealer as needed.

NOTICE! During airtight and leakage tests, never mix oxygen, ethyne, or other dangerous gases into the refrigeration circuit. For safety, use nitrogen or refrigerant for such tests.

9 After-sales Service

For any quality issues or inquiries regarding your purchased air-conditioning unit, please contact the local after-sales service agency designated by Blueridge.

Warranty Requirements:

  • The initial startup of the unit must be performed by professional personnel from a Blueridge appointed service center.
  • Only Blueridge manufactured accessories may be used on the machine.
  • All instructions provided in this manual must be followed.
  • The warranty will be automatically void if any of the above conditions are not met.
Models: BMKH42M-NDG3, 42000 BTU 21 SEER Five Zone Ductless Mini Split Outdoor Condenser

File Info : application/pdf, 24 Pages, 5.98MB

PDF preview unavailable. Download the PDF instead.

ownermanualbmkh42m-ndg3

References

Microsoft Office Word 2007

Related Documents

Preview Blueridge BMKH Series Split Air Conditioner Outdoor Unit Technical Specifications
Detailed technical specifications for the Blueridge BMKH series split air conditioner outdoor units, including models BMKH18M-NDG3, BMKH24M-NDG3, and BMKH30M-NDG3. Covers cooling and heating capacity, EER, COP, SEER, HSPF, airflow, sound levels, power requirements, compressor details, fan specifications, condenser information, operating temperature ranges, refrigerant details, dimensions, weight, and connection pipe specifications.
Preview Blueridge BMKH24M-NDG3 Split Air Conditioner Outdoor Unit Technical Specifications
Detailed technical specifications for the Blueridge BMKH24M-NDG3 Split Air Conditioner Outdoor Unit, including electrical, performance, and physical characteristics.
Preview Blueridge PTAC Series Owner's Manual: Installation, Operation, and Maintenance
Comprehensive owner's manual for the Blueridge PTAC Series Packaged Terminal Air Conditioner/Heat Pump, covering safety precautions, installation, operation, customization, care, maintenance, and troubleshooting.
Preview Blueridge Remote Controller Owner's Manual
Comprehensive guide for the Blueridge air conditioner remote controller, detailing specifications, button functions, screen indicators, basic and advanced operating modes, and usage instructions.
Preview Blueridge Inverter Split-Type Room Air Conditioner User Manual
Comprehensive user manual for Blueridge Inverter Split-Type Room Air Conditioners, covering safety precautions, operation, maintenance, and troubleshooting for models like BM09Y17, BM12Y18, BM18Y18, BM24Y16, BM30Y18, and BM36Y16.
Preview Blueridge Split Air Conditioner Owner's Manual
This owner's manual provides comprehensive instructions for the installation, operation, and maintenance of Blueridge Split Air Conditioners. It covers safety precautions, parts identification, remote controller functions, error codes, and troubleshooting.
Preview Blueridge XK19 Wired Remote Controller Owner's Manual
Comprehensive owner's manual for the Blueridge XK19 Wired Remote Controller, detailing its features, operation, installation, and troubleshooting for various compatible Blueridge mini-split systems.
Preview Blueridge Standard Single Zone Ductless Mini-Split Specifications Sheet
Detailed technical specifications for Blueridge Standard Single Zone Ductless Mini-Split air conditioning and heating systems, including capacity, dimensions, electrical, and refrigerant data for models BM09Y17, BM12Y18, BM18Y18, BM24Y16, BM30Y18, and BM36Y16.