RAK2461 Quick Start Guide
Prerequisite
Before going through each and every step in the installation guide of the WisNode Bridge IO Lite, make sure to prepare the necessary items listed below:
Hardware Tools
1. RAK2461 WisNode Bridge IO Lite 2. USB configuration cable 3. Gateway in range, for Testing 4. A Windows/macOS/Linux Computer
Software Tools
IO.Box Desktop is a software application that will allow you to configure the devices from the RAK24XX series. You can download the application from here:
Windows Linux Mac
Package Inclusions
Variant for Wall Mounting
Figure 1: RAK2461 Package Inclusions 1
Variant for DIN Rail Mounting

Documentation Center
Figure 2: RAK2461 Package Inclusions 2
The package inclusions depend on the bundle you purchase. Variant for Wall Mounting One (1) RAK2461 WisNode Bridge IO Lite (RS485-DIx4-DOx1 or RS485-DOx4) One (1) Screw Kit One (1) LoRa Antenna One (1) Power Adapter One (1) USB Cable (Type C to Type A) One (1) 4-Pin Terminal Block Two (2) 8-Pin Terminal Block Variant for DIN Rail Mounting One (1) RAK2461 WisNode Bridge IO Lite (RS485-DIx4-DOx1 or RS485-DOx4) One (1) DIN rail Mounting Kit One (1) LoRa Antenna One (1) Power Adapter One (1) USB Cable (Type C to Type A) One (1) 4-Pin Terminal Block Two (2) 8-Pin Terminal Block
Installation
RAK2461 allows for two installation methods: wall mounting and DIN rail installation.
Wall Mounting
1. Drill the wall corresponding to the device dimensions and insert the anchors in the holes.

Documentation Center
Figure 3: Hole drilling
2. Fix the device to the wall with two tapping screws.

Figure 4: Wall mounting
DIN Rail Mounting
1. Attach the DIN rail mounting clip on the device with two M3*6 countersink screws.

2. Mount the device to the DIN rail.

Figure 5: Attaching the clip

Documentation Center
Figure 6: DIN rail mounting
Product Configuration
Typical Network Application
RAK2461 WisNode Bridge IO Lite provides different Digital Inputs, Outputs (Relay), and RS485 communication. It can convert the data of the connected devices into LoRaWAN that can be sent to the cloud via a standard gateway. Cloud servers can also actively send data to RS485 terminals and control the DI/DO transmission to achieve two-way data transmission. Using RAK2461, what used to be a costly and time-consuming cable line network deployment can be transformed into a rapid and cost-efficient wireless network deployment. An example would be using the RAK7268V2 WisGate Edge Lite 2 LoRaWAN gateway coupled with the RAK WisDM cloud management platform, to realize an end-to-end industrial field data acquisition and control system. Using the built-in LoRa Server, which comes standard with any RAK LoRaWAN gateway, one could seamlessly achieve transmission of the end device data to any application server. Furthermore, the MQTT integration allows for high security and efficiency.
Figure 7: RAK2461 WisNode Bridge IO Lite network structure
Connect the RAK2461 to the Sensor
Power Interface Configuration
The RAK2461 device can be powered either by: 9-24 VDC input USB type-C
The USB type-C port of the device can be used for configuration. Powering the device from the type-C port will not provide power to the sensor but only to the device itself. To power the device and sensor, you should use the 9-

Documentation Center
24 VDC input of the RAK2461. The RS485 serial interface supports up to 32 RS485 devices. The Vout pin can supply the external power to the RS485 sensors connected to RAK2461.

Figure 8: Power interface connection
Data Interface Connection
For this example, an RS-FSXCS-N01-3 Ultrasonic Weather Station is used. Here are the basic communication parameters of the sensor:

Parameter Format Data bit Parity Stop bit Error checking Baud rate

Definition 8-bit binary 8-bit No 1 CRC Supports: 2400, 4800, 9600 (default is 4800)

Figure 9: Data interface connection
 NOTE
For connecting to other devices, read their specific documentation carefully and connect accordingly.

Documentation Center
 NOTE
For a demonstration, the RAK2461 Bridge Lite shall be connected to an RAKwireless gateway. For the gateway, the built-in LNS will be used. Listed below are the requisites for this section.
IOBox Desktop WisGateOS 2 User Manual - a guide on how to configure the RAK7268 WisGate Edge Lite 2 V2 RS-FSXCS-N01-3 Manual - guide for the Ultrasonic Integrated Weather Station
Gateway Configuration
Set-up the Built-in Network Server
1. Start by accessing the gateway. You can see how to do it on the WisGateOS V2 user manual.
Figure 10: WisGateOS2 login page
2. Once logged in, head to the LoRa menu.
Figure 11: LoRa page

Documentation Center
1. By default, the gateway works as a Built-In Network Server. If that is not the case, check the Built-in Network Server Mode Settings on the WisGateOS V2 User manual to switch the mode.
Adding Application
1. Once the gateway is in Built-in network server mode, head to the Applications tab.
Figure 12: Create Application in the Built-In Network Server
2. Click the Add application button or add one now link to add a new application. On the new page, fill in the following information: Application name - type a name for the application. Application description - optionally you can write a description of the application. Application Type - from the drop-down menu select the type of application. Unified Application key - all devices will use the same application key. Selecting this option pops up an Application Key field. You can type your application key there or use the Autogenerate button to generate one.
Figure 13: Unified application key
The Auto Add Device switch activates the Application EUI field. The device will be automatically added to the application after the application EUI and key verification.
Figure 14: Auto add device

Documentation Center
Separate Application keys ­ each device will have its own application key. The key is added when registering the device. Payload type - from the drop-down, select CayenneLPP payload type and turn on the Only forward data object feature.
Figure 15: Adding application
3. Once set, click Save application to add the application. 4. After the application is added, head to the End devices tab. The devices should automatically register upon join
request if you are using the Auto Add Device feature.

Documentation Center
Figure 16: Successfully added end device
If that's not the case, click the Add end device button. On the End device information page fill in the following information:
Activation Mode - choose the activation mode of your device: OTAA ABP - This mode pops up two additional fields: Application Session Key Network Session Key
Figure 17: Adding ABP device
End device (group) name ­ the name of the device. End device description (optional) ­ optionally, you can add a description for the device. Class ­ the class of the device. Frame Counter width ­ the width of the frame counter. Leave it as default. LoRaWAN MAC Version ­ the LoRaWAN MAC version. V1.0.2 pops up a LoRaWAN Regional Parameters reversion field where you need to select the reversion of the device.

Documentation Center
Figure 18: Successfully created application
Adding the Device
1. Once everything is set, click Add end devices to go to the page and add the device.
Figure 19: Adding end device
2. On the Adding end devices page, type the device EUI at the End Device EUI (main) and click Add to "End Devices list". If the EUI is correct, the device will show in the End devices list. If the EUI is not correct, the devices will show in the End devices with an error.

Documentation Center
3. Once the device is added to the End devices list click Add end devices. Confirm you are adding the device.
Figure 20: Confirmation message for adding a device
RAK2461 Configuration
Connect the rak2461 to Your Network
1. Download and open the IO.Box application. 2. Connect the rak2461 to a computer using the USB type-C cable. Note that this will work for the LoRaWAN
configuration, but when configuring the sensor you would need to connect the 9-24 VDC power supply in order to provide power to the sensor itself. Make sure that the USB type-C cable that you are using supports data transfer and no other serial software is connected to the COM port that RAK2461 uses. 3. Click Connect Device in the IO.Box console.
Figure 21: IOBox get started
If an error occurs that shows no device detected, here are some possible causes for that and how to fix it: Double-check the quality of the USB cable and if the correct COM port is used. Check if other terminal software is active and still connected to the RAK2461.

Documentation Center
Figure 22: No device error
4. On the IO.Box dashboard screen, you can see information about the devices connected to the PC in the form of a list of connected devices with device models and EUIs. Choose the device that you wish to configure via the Connect button next to it.
Figure 23: List of connected devices
5. On the main menu to the left, choose LoRaWAN to configure the LoRaWAN settings as needed. Do not forget to click Save below the changes. Device EUI - This is the unique identifier provided by RAKwireless. Region - The LoRaWAN region/band. Class - The LoRaWAN class (C). Join Mode - Choose between OTAA and ABP according to LoRaWAN protocol. Application EUI - Enter the unique identifier assigned by the application server. Application Key - Enter the unique secure key assigned by the application server. Confirm Mode - Activate to receive confirmation messages from the network server for each uplink. ADR - Enable Adaptive Data Rate allowing the network server to control the data rate for your device. DataRate - Manually set the data transmission rate. Lower rates extend coverage but increase transmission time and power usage. Choose based on the distance and signal quality to the gateway. TX Power Level - Adjust the transmission power level. The lower the number the higher the power. 0 is the maximum allowed in the selected region and each incrementation of 1 to the number reduces the power by 2 dBm. Data Report Interval - Set up the global data report period of the device. Range: 60­86400 in seconds.

Documentation Center
LoRaWAN Status - Indicates the activity of the device in the LoRaWAN network. To check the previously configured Application EUI and Key, run the commands:
Figure 24: LoRaWAN tab
6. Make sure you've added the RAK2461 WisNode Bridge IO Lite to the LoRaWAN Network Server of choice (Built-in LNS in this example).
7. After the device has successfully joined the LNS, you will see the LoRaWAN status toggle as activated. You might need to refresh the page.
Figure 25: LoRaWAN status
RS485 Configuration
RS485 Interface Configuration
Go to the RS485 tab from the main menu and configure the interface according to the sensor/device you are connecting to. Do not forget to save your changes. In this tab you will find:
Baudrate - Select the communication speed for the RS485 interface, measured in bits per second. Choose a rate that matches your device's requirements. Databits - Select the number of data bits for each character in the RS485 communication. Typically, options include 7 or 8 bits, depending on your device's protocol requirements. Stopbits - Select the number of stop bits used in the RS485 communication. Common options are 1 or 2, depending on your device's data transmission protocol. Parity - Select the parity setting for the RS485 interface. Options typically include None for no parity, Even for even parity, or Odd for odd parity. Choose based on your device's communication requirements.

Documentation Center
Figure 26: RS485 interface configuration
Add Modbus Poll Task
In the Modbus Poll Task menu click + Add for a new poll. You will see the Polling Task parameters that need to be configured.
Figure 27: Add poll task
Task ID - Enter the identifier for the polling task. This ID is included in the device's uplink data to indicate the task. Device Address - The Modbus slave address in decimal format. Range: 1-254. Function Code - The Modbus function code defines this poll's operation. Register Addr - The address of the register that you wish to access in hexadecimal format. Quantity - The number of register addresses that you want to access. Data Type - The data type of the Modbus response. Scale - To adjust the raw data from the Modbus response to the desired units. For example, to convert kilograms to grams set the scale to X1000. Remark - Length: 15 characters. Enable - Enable or disable this polling task. Sensor Type - Choose the unit of the data obtained from the Modbus slave device. If no exact match is available, select Generic xxxx as a default option. Modbus Request - Displays the Modbus command generated based on the settings you've selected above. This command will be used to communicate with the Modbus device. Modbus Response - Displays the response received from the Modbus slave device.

Documentation Center
Value - This shows the data extracted from the Modbus Response is parsed according to the above configuration. Uplink Data - Displays the data payload format that will be sent to the server, based on the configuration above. Check - Modbus CRC check. Before saving the task click Check for automatic validation. Save - Save the polling task.
Figure 28: Polling task parameters
Creating a Raw Data in Binary Poll Task
Fill in the register address and other relevant fields according to the specific sensor's datasheet, then after clicking the Check button, you will see the Reply Frame on the IO.Box.
Figure 29: Fill-in sensor specific data
After saving the polling task, wait awhile and you will see the uplink data from the LoRaWAN network. The format of the uplink message would be as follows: TaskID + Sensor Type + Length + Value
sh
01 + f1(Raw Data in Binary) + 07 + 010302007d7865

Documentation Center
Figure 30: Uplink data
Creating a Wind Speed Poll Task - Example
Fill in the relevant fields according to the specific sensor's datasheet, then after clicking the Check button, you will see the Reply Frame on the IO.Box.
Figure 31: Fill in sensor specific data
After saving the polling task wait awhile and you will see the uplink data from the LoRaWAN network in the gateway Web UI. The format of the uplink message would be as follows: TaskID + Sensor type + Value
sh
02 + 92(Wind Speed) + 007D(Hex) 125(Dec) 1.25m Wind Speed
Figure 32: Uplink data
Click Reload to Fetch the Latest Uplink Data

Documentation Center

Search Task

Figure 33: Fetching latest uplink

Figure 34: Search task
Sort Task Based on the Task ID, Address, Function Code, Register Address, Data Type, Sensor Type or Remark
Figure 35: Sort task
Export an Existing Task List and Import it into Another Node

Figure 36: Export/Import task
Digital Input/Output Configuration
From the main menu of IO.Box, go to the DI/DO tab and configure the interface according to the sensor/device you are connecting to. Do not forget to save your changes. In this tab you will find:
Port ID - The identifier of the digital input port. You can find the port ID on the device's enclosure label.

Documentation Center
Task ID - An identifier of the polling task. The ID will be included in the uplink data to indicate the source of the data. Debounce - Set a delay (Range: 50-2000 ms) to stabilize the signal from a switch or button, ensuring only a single action is registered and eliminating false triggers due to contact bounce. Input State - Displays this digital input port's status (active or inactive). Output State - Toggle to change this digital output port's current state (active or inactive). Enable - Toggle to activate the polling task for this port, allowing it to report the port's state.
Figure 37: DI/DO parameters
Connecting a PIR Motion Sensor With Digital Input
For this example, a DH-ARD631-50 Outdoor active PIR sensor is used in the following way: 1. Have two devices, one transmitter and one receiver. 2. The transmitter's POWER(1/2) is connected to the Vout and GND of the bridge. 3. The receiver's POWER(2/3) is connected to the 12V_Out and GND of the bridge. 4. The receiver's ALARM(5/6) is connected to the DI4 COM and DI4 IN of the bridge.

Documentation Center
Figure 38: Sensor to Bridge wiring
5. Enable the DC Vout and the 12 VDC power outputs in the IO.Box console, located in the System tab.
Figure 39: Enabling power outputs
6. After enabling DI4 and reloading, you will see the input state enabled.

Documentation Center
Figure 40: Enabling DI4
7. When triggered, the LNS will receive the packet after the debounce time or a periodic uplink.
Digital Output for Switching Applications
1. You can connect any module or device to the port of the Digital Output as long as it operates on the recommended voltage rating.
Figure 41: Wiring
2. When the output state is enable in the IO.Box console, the left bulb is supplied, when it is disabled, the right bulb is supplied.

Documentation Center
Figure 42: Output state
3. Additionally, modifications can be made through a Downlink message.
Figure 43: Downlink
System
From the main menu of IO.Box, go to the System tab to find device information for the RAK2461 as well as power output toggles and firmware update options. Do not forget to save your changes. In this tab you will find:
Hardware Version - Displays the specific version of the device's hardware. Firmware Version - Displays the device's firmware version. Device EUI - Displays the unique identifier assigned by the manufacturer. Device Model - Displays the specific model name or number of the device. Serial Number - Displays the device's serial number of the device. Device Type - Indicates the category or classification of the device, defining its interface types and functionalities. For detailed specifications refer to the device's model information. Frequency Band - The device's frequency band. DC Vout Output - Toggle to enable or disable the Vout power output. When enabled, Vout passes through the same voltage as the Vin input. DC 12V Output - Toggle to enable or disable the 12V_Out power output. When enabled, it provides a 12 V / 0.5 A power output. DC 5V Output - Toggle to enable or disable the 5V_Out power output. When enabled, it provides a 5 V / 0.5 A power output.

Documentation Center
Figure 44: System information overview
Figure 45: System information overview
Reboot
Simply press the Reboot button under the Firmware Upgrade section.

Documentation Center
Figure 46: Reboot button
Figure 47: Successful reboot
Factory Reset
To restore the device to factory settings, press the Reset button under the Firmware Upgrade section and wait for the process to be completed.
Figure 48: Reset Button

Documentation Center
Figure 49: Reset progress
Figure 50: Successful reset
Firmware Update
Normal Firmware Update
1. After downloading the latest firmware, click Browse.

Documentation Center

2. Select the correct file.

Figure 51: Browse button

Figure 52: Selecting the file
3. Click Upgrade and wait for the procedure to finish.

Documentation Center
Figure 53: Upgrading procedure
Figure 54: Successful upgrade
Manual Firmware Update
Follow this procedure if the upgrade process fails unexpectedly, or to upgrade the damaged device in boot mode.
Figure 55: upgrade fail

Documentation Center
1. Open the IO.Box application and click Connect Device.

2. Select Connect Manually.

Figure 56: IOBox application

Figure 57: No device found
3. Manually input the port and device model.

Figure 58: Manually selecting the device

Documentation Center
4. Follow the steps of the normal upgrade procedure above by browsing and selecting the firmware file and so on.
Figure 59: Normal upgrade procedure
Last Updated: 10/18/2024, 2:12:32 PM

