UL 67 Compliant Load Centers and Panelboards

Service entrance barrier changes to meet new enhanced safety requirements

What is UL 67?

Beginning January 1, 2017, enhanced UL 67 safety requirements will take effect, applying to all panelboards and load centers with service equipment applications. To comply, any single service disconnect panelboard or load center must have provisions such that, when the service disconnect is opened, no person in the field servicing the equipment load side can make accidental contact to live circuit parts. Barriers to protect against unintended contact shall be constructed in such a way that they are easily installable and removable without contacting or damaging bare or insulated live parts.

In addition to meeting new UL 67 requirements, these enhancements will meet the new requirements in Section 408.3(A)(2) of the 2017 National Electric Code. Although these new service barrier requirements enhance the safety of working on panelboards, Siemens recommends turning off and locking all power supplying these panelboards before working inside to avoid any potential hazards. Electrical equipment should always be placed in an electrically safe condition prior to working inside. Installation and maintenance of this equipment should only be done by a qualified person. Appropriate personal protective equipment (PPE) must be worn and safe work practices must be followed. See NFPA 70E for information on PPE and safe work practices.

A close-up view of a Siemens panelboard interior, showing a main breaker with a clear plastic service entrance barrier installed. The barrier is positioned to prevent accidental contact with live circuit parts when the breaker is open.

Lighting Panels and Power Panels

Panels are factory labeled suitable for use as service entrance equipment when NEC requirements are met. Factory installed and field installable Service Entrance Barrier kits are now available as required by UL 67.

A Siemens main breaker, identified as 'ND Main Breaker', with a UL 67 compliant service entrance barrier installed on its line side. The barrier is a clear shield.

Type P1 Service Entrance Barriers

Catalog numberDescription
SEBKRP1V1FD, QJ, QR Service Entrance Barrier Kit (Revised P1)
SEBKRP1V2ED Service Entrance Barrier Kit (Revised P1)
SEBKRP1V3BQD Service Entrance Barrier Kit (Revised P1) back-fed
SEBKRP1V4xGB Service Entrance Barrier Kit (Revised P1) back-fed
SEBKRP1P2P3V1JD, LD Service Entrance Barrier Kit (RP1, P2, P3)

Type P2 Service Entrance Barriers

Catalog numberDescription
SEBKP2V1BL, BQD Main Service Entrance Barrier (P2 only)
SEBKP2V2xGB Main Service Entrance Barrier (P2 only)
SEBKP2V3FD, QJ, QR Horizontal Main Service Entrance Barrier (P2, P2 with SEM3, P3)
SEBKP2V4FD, QJ, QR Vertical Main Service Entrance Barrier (P2, P2 with SEM3)
SEBKP2V5ED Horizontal Main Service Entrance Barrier (P2, P2 with SEM3)
SEBKP2V6ED Vertical Main Service Entrance Barrier (P2, P2 with SEM3)
SEBKP1P2P3V1D, LD Service Entrance Barrier Kit (RP1, P2, P3)

Type P3 Service Entrance Barriers

Catalog numberDescription
SEBP3V1Service Entrance Barrier Kit CFD, FD (P3 only)
SEBKP1P2P3V1JD, LD Service Entrance Barrier Kit (RP1, P2, P3)

Type P4 Service Entrance Barriers

Catalog numberBreaker type
SEBP4V1(S)JD, (S)LD, MG
SEBP4V2CJD, CLD
SEBP4V3JG, LG

Type P5 Service Entrance Barriers

Catalog numberBreaker type
SEBP5V1(S)MD, (S)ND without shield
SEBP5V2(S)MD, (S)ND without shield
SEBP5V3Vacu-Break Switches
SEBP5V4HCP Switches

Load Centers and Meter Combos

Touchsafe barriers are required for any single main service entrance application for a panel covered under UL 67. Line Terminal Barriers will be included in Main Breaker Load Centers and Single Main Meter Combos manufactured after January 1, 2017.

Single phase and 3-phase main breaker kits will include a barrier. Field installable kits are being created for replacements if needed and line terminal barriers are being added to hold down kits that can be used in back-fed applications. The barriers are designed to have minimal interference during load center installation, and can be removed and reattached as necessary.

Service Entrance Barriers

Catalog numberDescription
ECLTB1For EQ Main Breakers / MBK kits 100A-125A
ECLTB2For EQ Main Breakers / MBK kits 150A-225A
ECLTB3For QN / QNR type breakers
ECLTB4For QR 3 phase breakers
ECMBR1For 2 Pole QP / MP-T type breakers for EQIII (extruded basepan) and Line 5 Load Centers
ECMBR2For 2 Pole QP / MP-T type breakers to be used with Ultimate LCs (now ES / PL), Murray or Rock Solid
ECMBR3For 3 Pole QP / MP-T type breakers to be used with PL, ES 3 phase load centers
ECLX387HDFor 2 Pole MP-T type breakers in legacy Murray load centers

Questions and Clarifications

Q: When is the COMPAS launch?

A: COMPAS Launch is set for week of Oct. 24. Click the check box to include a service entrance barrier kit in BOM.

Q: What if a job has already been ordered, but is shipping after Jan. 1, 2017?

A: Please contact the plant directly or customer service to coordinate a service entrance barrier kit to be shipped to the job site.

Q: Does UL 67 apply to any other Siemens products?

A: Switchboards, Motor Control Centers and Low Voltage Switchgear are not affected by UL 67 because they already have their own service entrance requirements.

Q: What about panelboards and load centers already installed in the field that do not have service entrance barrier provisions?

A: According to the standard, existing field sites/jobs do not need to be retrofitted.

Q: How do I work with and around the barrier when it is installed?

A: Instruction sheets will come with every kit. Sheets can also be downloaded online in case they are lost.

PDF preview unavailable. Download the PDF instead.

sie-br-lc-ul67 Adobe InDesign CS6 (Macintosh) Adobe PDF Library 10.0.1

Related Documents

Preview Siemens EUSERC Compliant Meter-Load Center Combinations - Product Catalog
Explore Siemens' range of EUSERC compliant meter-load center combinations, including side-by-side, over/under, and back-to-back configurations. Find detailed specifications on amperage, circuit capacity, dimensions, and features for electrical distribution.
Preview Siemens TCJ2/TCJ3 Plug-In Adapter Installation Instructions
Detailed installation guide for Siemens TCJ2 and TCJ3 plug-in adapters, compatible with JD, JM, LD, LM, JF, and LF frame Siemens circuit breakers. Includes safety precautions, compatible breaker types, step-by-step assembly instructions, and torque specifications.
Preview Siemens Safety Switches: General Duty, Heavy Duty, and Special Application Guide
Comprehensive guide to Siemens safety switches, covering General Duty, Heavy Duty, and Special Application types. Details specifications, features, enclosure options, and catalog numbering systems for various models.
Preview Siemens Revised P1 Unassembled Panelboards: Features, Specifications, and Ordering
Comprehensive guide to Siemens Revised P1 Unassembled Panelboards, detailing features, benefits, technical specifications, and ordering information for various configurations.
Preview Siemens Meter Centers: EUSERC Compliant Load Center Combinations
Explore Siemens' range of EUSERC compliant side-by-side meter-load center combinations. This document details various models for 1-phase, 3-wire 120/240V AC applications, including 100-125amp, 200-225amp, and 200amp with subfeed provision options. Features include UL listing, high AIC ratings, and various configuration choices.
Preview Siemens MBKVA41A/MBKVA41B Main/Subfeed Breaker Kit Installation Instructions for P1 Panelboards
Detailed installation instructions for Siemens MBKVA41A and MBKVA41B Main/Subfeed Breaker Kits, designed for use with Siemens P1-250 and P1-400 Panelboards. Covers installation as a main breaker or subfeed breaker.
Preview Siemens Generator Ready Load Centers - NEMA 1 & 3R Enclosures
Siemens Generator Ready Load Centers provide cost-effective solutions for connecting standby or portable generators. This document details NEMA 1 and NEMA 3R enclosure features, specifications, and catalog numbers for 1-Phase, 3-Wire SN, 120/240 Volt AC systems.
Preview Siemens General Duty Safety Switches Selection Guide - Catalog GDSS
Comprehensive selection guide for Siemens General Duty Safety Switches. Features detailed specifications for indoor Type 1 and outdoor Type 3R fusible and non-fusible models, including catalog numbers, weights, and horsepower ratings. Part of the SPEEDFAX™ 2017 Product Catalog.