FRONT, REAR AND SIDE ADVANCED WIND BAFFLE WB-PA/WB-SD/WB-RE
Application
The Wind Baffles are used to extend the cooling temperature operation range of the PUY, PUZ, MXZ and PUMY models.
The information below outlines which wind baffles to utilize per required operation range.
Please refer to the installation manual of the appropriate outdoor unit for correct installation requirements.
Cooling Temperature Operation Range With Wind Baffles
Model Series | Operation Range Without Wind Baffles | Front Wind Baffles | Front + Advanced Side + Advanced Rear Wind Baffles |
---|---|---|---|
PUZ-7 | 23° F - 115° F | 0° F | N/A |
PUY-7 | 23° F - 115° F | 0° F | -40° F |
PUMY* | 23° F - 115° F | 5° F | N/A |
MXZ | 23° F - 115° F | 5° F | N/A |
*Operation range varies based on indoor unit connected, refer to service manual for applicable indoor units.
**If unit is exposed without wall surfaces surrounding for protection from wind, then side and rear wind baffles will be required. Please refer to installation dimensions and outdoor unit installation manual for appropriate requirements.
Model Compatibility and Quantity
Models | Front Wind Baffles WB-PA3 WB-PA4 WB-PA5 |
Advanced Side Wind Baffles WB-SD4 WB-SD5 WB-SD6 |
Advanced Rear Wind Baffles WB-RE4 WB-RE5 WB-RE6 |
---|---|---|---|
PUY-A12NKA7 | 1 | ||
PUY-A18NKA7 | 1 | 1 | 1 |
PUY-A24NHA7 | 1 | 1 | 1 |
PUY-A30NHA7 | 1 | 1 | 1 |
PUY-A36NKA7 | 2 | 1 | 1 |
PUY-A42NKA7 | 2 | 1 | 1 |
PUZ-A12NKA7 | 1 | ||
PUZ-A18NKA7 | 1 | 1 | 1 |
PUZ-A24NHA7 | 1 | 1 | 1 |
PUZ-A30NHA7 | 1 | 1 | 1 |
PUZ-A36NKA7 | 2 | 1 | 1 |
PUZ-A42NKA7 | 2 | 1 | 1 |
MXZ-8C48NA | 2 | ||
MXZ-8C60NA | 2 | ||
MXZ-4C36NAHZ | 2 | ||
MXZ-5C42NAHZ | 2 | ||
MXZ-8C48NAHZ | 2 | ||
PUMY-P36NKMU2 | 2 | ||
PUMY-P48NKMU2 | 2 | ||
PUMY-P60NKMU2 | 2 | ||
PUMY-HP36NKMU | 2 | ||
PUMY-HP48NKMU | 2 |
Front Wind Baffles (WB-PA3 / WB-PA4 / WB-PA5)
General Features
- Front Wind Baffles allow outdoor units to operate at full capacity down to the temperature ranges shown in the table above.
- Prevents wind from reversing outdoor fan rotation when unenergized.
- Durable and low maintenance construction.
Please Note
- Install outdoor units with the back surface facing wall side to eliminate the effects of external wind.
- Outdoor units should not be installed in an orientation or site where the wind blows directly at the back of the unit.
- Wind baffle should not be used where there is any obstacle at either side or above the outdoor unit as the discharged air will be blocked.
- Refer to outdoor unit for detailed installation instructions.
Image Description: Two images are shown. The first is of the WB-PA3 baffle, a simple, open-frame structure. The second image shows the WB-PA4 / WB-PA5 baffles, which are larger and have multiple horizontal shelves.
Advanced Wind Baffles (WB-SD / WB-RE)
General Features
- Advanced Side and Rear Wind Baffles allow outdoor units to operate at full capacity down to the temperature ranges shown in the table above.
- Prevents wind from reversing outdoor fan rotation when unenergized.
- Durable and low maintenance construction.
Please Note
- Installation location will dictate Advanced wind baffle requirements.
- Refer to the installation manual for additional details.
- Advanced Wind Baffles should be installed to prevent any wind blowing directly into the unit.
- Front Wind Baffle (WB-PA3, WB-PA4, WB-PA5) is also required for -40° F operation of PUY models.
Image Description: Six images are shown: WB-SD4, WB-SD5, WB-SD6 (side baffles) and WB-RE4, WB-RE5, WB-RE6 (rear baffles). These depict various configurations of side and rear panels designed to protect the outdoor unit from wind.
Wind Baffle Specifications
Models | Color | Exterior Surface Treatment | Material | Weight |
---|---|---|---|---|
WB-PA3 | Matches P-Series Outdoor Unit (Ivory Munsell 3Y 7.8/1.1) |
Polyester Powder Coating | Alloy Hot-Dip Zinc Coated | 8 Lbs. 8 Oz. |
WB-PA4 | 7 Lbs. 7.9 Oz. | |||
WB-PA5 | 8 Lbs. 8 Oz. | |||
WB-SD4 | Polyester Powder Coating | Carbon Steel Sheet | 6 Lbs. | |
WB-SD5 | 10 Lbs. | |||
WB-SD6 | 15 Lbs. | |||
WB-RE4 | Polyester Powder Coating | Carbon Steel Sheet | 11 Lbs. | |
WB-RE5 | 18 Lbs. | |||
WB-RE6 | 35 Lbs. |
Dimensions (WB-PA3)
Installation Space Requirements
Diagram Description: The diagrams illustrate required clearances for installing the WB-PA3 baffle. For single unit installation, it shows a wall surface and the baffle placement with minimum clearances of 6 to 16 inches and 20 inches or more in various directions. For multiple unit installation in series (up to five units), similar clearance requirements are shown.
Detailed Dimensions
Diagram Description: Detailed dimension drawings for the WB-PA3 baffle are provided, showing lengths, widths, and heights in inches. Key dimensions include 22.4 inches, 25 inches, 25.6 inches, 23 inches, and 21 inches. Hole dimensions (Φ.25, 4 PLCS) are also indicated. All dimensions are in inches with a tolerance of ±1/32".