Product Descriptions
The Class 9013 Type F line of pressure switches are UL Listed and CSA Certified as commercial control equipment. The Class 9013 Type G line of pressure switches are UL Listed and CSA Certified as commercial/light industrial control equipment.
Type FHG - PUMPTROL® Compressor Pressure Switch
The Type FHG - PUMPTROL® Compressor Pressure Switch is used to control electrically driven air compressors. It is diaphragm actuated and has contacts that open on rising pressure.
[Image: A grey, rectangular pressure switch with a diaphragm housing and electrical conduit connections.]
Type FSG, FYG, FRG - PUMPTROL® Water Pump Pressure Switches
The Type FSG, FYG, FRG - PUMPTROL® Water Pump Pressure Switches are used to control electrically driven water pumps and have the following features:
- The Type FSG is the standard water pump switch, suitable for all types of pumps: jets, submersible, reciprocating, etc.
- The Type FYG is designed to meet higher horsepower and pressure requirements.
- The Type FRG is reverse acting: the contacts open on falling pressure.
- All are diaphragm actuated.
[Image: A grey, square-ish pressure switch with a clear cover showing internal components and conduit connections.]
Type G - PUMPTROL® Commercial/Light Industrial Pressure Switch
The Type G - PUMPTROL® Commercial/Light Industrial Pressure Switch is used to control electrically driven water pumps and air compressors. It has higher electrical ratings for direct control of motors in pump and compressor applications. The Type G switch is diaphragm actuated and has contacts that open on rising pressure.
[Image: A grey, box-like pressure switch with a diaphragm housing and conduit connections, shown with an optional release valve.]
Technical Overview
Operating Points (Settings)
Every pressure switch has two operating points: one on rising pressure and one on falling pressure. The operating point on rising pressure is referred to as the TRIP POINT or cut-out for pumps and compressors, and the operating point on falling pressure is referred to as the RESET POINT or cut-in for pumps and compressors. These operating points are called the SETTINGS of the switch.
- TRIP POINT (rising pressure)
- RESET POINT (falling pressure)
Differential
The differential is the difference in pressure between the trip point (cut-out) and the reset point (cut-in). It can be adjustable or nonadjustable (fixed). Example:
Cut-in: 30 psi
Cut-out: 50 psi
Differential: 20 psi (50-30 psi)
Range
The range is the pressure limits within which the operating points (settings) can be adjusted. The range of the Class 9013 pressure switch is referenced to the operating point on rising pressure (trip point). The differential subtracts from the trip point setting.
During the normal operating cycle, system pressure should never exceed the upper limit of the range when using a diaphragm actuated switch. This will greatly reduce the life of the diaphragm.
Maximum Allowable Pressure
Maximum allowable pressure is the pressure to which a switch can be subjected without causing a change in operating characteristics, shift in settings, or damage to the device.
Pressure surges may occur in a system during the start-up of a machine or from valve operation. Surges are not normally detrimental to the life of a switch if the surge is within the maximum allowable pressure rating of the switch. Diaphragm actuated switches should not be subjected to more than 10 surges per day. More frequent surges will greatly reduce the life of the diaphragm.
Specifications
Electrical Ratings
Switch Type | Voltage | Single Phase AC (Hp) | Polyphase AC (Hp) | DC (Hp) | Control Circuit Rating |
---|---|---|---|---|---|
FHG2, 3, 4, 9, 12 13, 14, 19, 42, 44, 49 | 115 230 460/575 | 1 1/2 2 1 | 2 3 1 | 1/4 1/4 -- | A600 |
FHG22, 24, 29, 32, 33 34, 39, 52, 54, 59 FYG, FYW | 115 230 460/575 | 2 3 1 | 3 5 1 | 1/2 1/2 -- | |
FRG One Pole All Form H | 115 230 | 1 1 | 1/4 1/4 | -- -- | A300 |
FRG Two Pole | 115 230 | 1 1 | 1 1 | 1/4 1/4 | |
All 9013G Form H | 115 230 460/575 | 1 2 2 | 1/2 1/2 1 | -- -- -- | A600 |
All 9013G Except Form H | 115 230 460/575 | 2 3 5 | 1 1 5 | -- -- -- |
Note: DC Rating does not apply to Form M4. 600 volt DC rating does not apply. See 1993 NEC Article 430-84.
Temperature Ratings
Minimum | Maximum | |
---|---|---|
Media | -22 °F (-30 °C) | +257 °F (+125 °C) |
Ambient | -22 °F (-30 °C) | +158 °F (+70 °C) |
Note: FSG and FYG have a 32 °F (0 °C) minimum ambient temperature rating.
Maximum Allowable Pressure
Type | Pressure (psig) |
---|---|
FHG, FSG, FYG, FSW, FYW | 220 |
FRG, GHB, GHG, GSB, GSG | 300 |
GMG, GSR, GSW | 100 |
GHR, GHW | 250 |
Certifications
Type FHG - PUMPTROL® Compressor Pressure Switch: UL Listed (File E12158 CCN NKPZ), CSA Certified (File LR 25490 Class 3211 06).
Type FSG, FYG, FRG - PUMPTROL® Water Pump Pressure Switch: UL Listed (File E12158 CCN NKPZ), CSA Certified (File LR 25490 Class 3211 06).
Type G - PUMPTROL® Commercial/Light Industrial Pressure Switch: UL Listed (File E12158 CCN NKPZ, Except GHR and GSR), CSA Certified (File LR 25490 Class 3211 06, Except GHR and GSR). Also UL Listed (File E12443 CCN NOWT, For GHR and GSR), CSA Certified (File LR 26817 Class 3218 05, For GHR and GSR).
Dimensions
Type F - PUMPTROL® Compressor and Water Pump Pressure Switch Dimensions
[Diagram showing dimensions for Type F switches. Key measurements include overall height, width, depth, port size, and hex size. A table lists specific switch types and their 'A' dimension.]
Type F Dimensions:
- Overall Height: 3.76 in (96 mm)
- Width: 2.78 in (71 mm)
- Depth: 2.34 in (59 mm)
- Port Size: 1/2-14 STRAIGHT PIPE THREAD
- Hex Size: 15/16
Switch Type | Inches | A Dimension (mm) |
---|---|---|
FSG1, FYG1 | 1 1/32 | 26 |
FHG2, 12, 22, 32, 42, 52, FRG2, FSG2, FYG2 | 29/32 | 23 |
FHG3, 13, 33, FRG3, FSG3, FYG3 | 1 9/32 | 33 |
FHG9, 19, 29, 39, 49, 59, FSG9, FYG9 | 1 3/32 | 28 |
Type G - PUMPTROL® Commercial/Light Industrial Pressure Switch Dimensions
[Diagrams showing dimensions for Type G switches, including different enclosure types and mounting brackets. Key measurements include overall height, width, depth, port sizes, and hole dimensions. Tables list specific switch types and their dimensions.]
Type G Dimensions (Example for GHG, GSG):
- Overall Height: 6.17 in (157 mm)
- Width: 3.85 in (98 mm)
- Depth: 2.50 in (64 mm)
- Main Port Thread: 1/4-18 NPSF Pipe Thread
- Mounting Bracket: Shown is available as a Class 9049 Type A-52 Kit.
- Net Weight: 2 1/4 Pounds
[Diagram for Type GMG showing similar dimensions and mounting bracket details.]
Selection and Modifications
Type FHG – Selection and Modifications
Type FHG PUMPTROL® Compressor Pressure Switches
Adjustable Cut-Out Range Increasing Pressure (PSIG) | Approximate Differential (PSIG) | Non-Adjustable (PSIG) | Poles | Pressure Connection | Lower HP NEMA Type 1 Enclosure Type | Higher HP NEMA Type 1 Enclosure Type |
---|---|---|---|---|---|---|
40-100 | 20 | 2 | 1/4" NPSF (Internal) 3/8" NPSF (Internal) 1/4" Four Way 1/4" NPT (External) | FHG2 FHG3 FHG4 FHG9 | FHG22 FHG33 FHG24 FHG29 | |
70-150 | 30 | 2 | 1/4" NPSF (Internal) 3/8" NPSF (Internal) 1/4" Four Way 1/4" NPT (External) | FHG12 FHG13 FHG14 FHG19 | FHG32 FHG33 FHG34 FHG39 | |
100-200 | 40 | 2 | 1/4" NPSF (Internal) 1/4" Four Way 1/4" NPT (External) | FHG42 FHG44 FHG49 | FHG52 FHG54 FHG59 |
Pressure Code (fixed differential)
Below is the pressure code table for fixed differential action devices. Existence of a code does not imply that the code is available for any or all devices.
Settings | Code |
---|---|
Off at 100 PSI | J27 |
Off at 110 PSI | J37 |
Off at 115 PSI | J38 |
Off at 120 PSI | J69 |
Off at 125 PSI | J52 |
Off at 135 PSI | J39 |
Off at 140 PSI | J68 |
Off at 150 PSI | J55 |
Off at 155 PSI | J40 |
Off at 175 PSI | J59 |
Specify other pressure | J99 |
Special Features And Modifications For Type FHG
Description | Form Letter |
---|---|
Standard Pack of 20 Switches | C2O |
Addition of a Second Ground Screw | G4★ |
Maintained Manual Cut-Out Lever (AUTO-OFF) | M1 |
Pulsation Plug | P |
1/2" Conduit Bushing - 1/2" Long Thread - On Left | T |
1/2" Conduit Bushing - 1/2" Long Thread - on Right | T1 |
Slip-On Connectors (Load Side Terminals Only) | U |
Slip-On Connectors (Line and Load Terminals) | U2 |
Factory Sealed Range Stud | W |
Two-Way Pressure Release Valve | X |
Quick Connect Two-Way Pressure Release Valve (for use with Polyflow Tubing) | X1 |
Black Cover | Z22 |
★ Can be field installed. Nameplate should then be marked with the Form letter and maintenance and ordering records corrected.
Ordering Information (Type FHG)
- Specify Class 9013 Type FHG.
- Select pressure code from Pressure Code Table and add code designation to end of type number. Be sure that pressure code falls within the limits of the device as shown in the device listings.
- If special features are desired, add the appropriate Form letter to the Class and Type. Arrange Form letters in alphabetical sequence when ordering more than one special feature.
- Place packaging code at end of sequence with other forms when ordering.
For standard pack of 20 devices per box: C20
For individual packaged devices: leave blank
Example: 9013FHG19J52MIXC20
NOTE: If no packaging code is indicated, devices will be shipped individually packaged.
Types FSG, FYG PUMPTROL® Water Pump Pressure Switches – Selection and Modifications
Standard Action: Contacts Open On Rising Pressure
Cut-Out Range (PSIG) | Approximate Adjustable Differential (PSIG) | Cut-in Range (PSIG) | Pressure Connection | 2 Pole NEMA Type 1 | 2 Pole NEMA Type 3R |
---|---|---|---|---|---|
20-65 | 15-30 | 5-45 | 1/8" NPSF Internal 1/4" NPSF Internal 1/4" NPT External 1/4" Bayonet (barbed) 90° Elbow 1/4" Bayonet | FSG1 FSG2 FSG9 FSG10 FSG20 | FSW1 FSW2 FSW9 FSW10 FSW20 |
20-50 | 10-30 | 10-30 | 1/4" NPSF Internal 1/4" NPT External | FSG22 FSG29 | FSW22 FSW29 |
9-30 | 6-20 | 3-10 | 1/4" NPSF Internal 1/4" NPT External | FSG42 FSG49 | FSW42 FSW49 |
34-65 | 15-30 | 19-45 | 1/8" NPSF Internal 1/4" NPSF Internal 1/4" NPT External 1/4" Bayonet (barbed) 90° Elbow 1/4" Bayonet | FYG1 FYG2 FYG9 FYG10 FYG20 | FYW1 FYW2 FYW9 FYW10 FYW20 |
25-80 | 20-30 | 5-60 | 1/4" NPSF Internal 1/4" NPT External | FYG22 FYG29 | FYW22 FYW29 |
9-40 | 6-20 | 3-10 | 1/4" NPSF Internal 1/4" NPT External | FYG42 FYG49 | FYW42 FYW49 |
Note: Must be mounted in vertical position to maintain enclosure rating.
Pressure Codes (Standard action)
Below is the pressure code table for standard action devices. Existence of a code does not imply that the code is available for any or all devices.
Settings | Code |
---|---|
5-21 PSI | J15 |
8-20 PSI | J16 |
20-40 PSI | J20 |
20-50 PSI | J18 |
30-50 PSI | J21 |
40-60 PSI | J24 |
50-70 PSI | J33 |
55-85 PSI | J34 |
60-80 PSI | J25 |
Specify other pressure | J99 |
Special Features And Modifications For Type FSG, FYG & FRG Devices
Description | Applies to | Form Letter |
---|---|---|
Standard Pack of 20 Devices per box | All Type F | C2O |
Pilot Light - Indicates Switch Contacts Closed | FSG, FYG | G5★ |
One Normally Open-One Normally Closed Contact | FRG 2 Pole Only | H |
Maintained Manual Cut-Out Lever (AUTO-OFF) | FSG, FYG | M1 |
Momentary Manual Cut-In Lever (AUTO-START) | FRG2-59 Only | M3 |
Low Pressure Cut-Off (AUTO-START-OFF) Operates at Approximately 10 PSIG Below Cut-in and will turn off the pump | FSG, FYG (Types 1-20 only) | M4 |
Maintained Manual Cut-in Lever (AUTO-ON) | FRG2-59 Only | M5 |
Pulsation Plug (Standard on FSG-4 and FYG-4) | FRG, FSG, FYG | P |
Salt Water Flange (1/4 NPSF Internal Only) | All Type F | Q |
Plastic Flange (max. temp. 120°F) (max. pressure 80 psi) | FRG, FSG, FYG | Q8 |
1/2" Conduit Bushing - 1/2" Long Thread - on Left | 1/4" NPSF Internal Only | T |
1/2" Conduit Bushing - 1/2" Long Thread - on Right | All Type F | T1 |
Slip-On Connectors (Load Side Terminals Only) | FSG, FYG | U |
Slip-On Connectors (Line and Load Terminals) | FSG, FYG | U2 |
Black Cover | FSG, FYG | Z22 |
★ Can be field installed. Nameplate should then be marked with the Form letter and maintenance and ordering records corrected. f Nylon pulsation plug can be field installed on types having 1/4" NPSF Internal connector. Part number 1530-S6-G1 is one bag of 50 plugs.
Ordering Information (Type FSG, FYG)
- Specify Class 9013 Type FSG, FYG, or FYG.
- Select pressure code from Pressure Code Table and add code designation to end of type number. Be sure that pressure code falls within the limits of the device as shown in the device listings.
- If special features are desired, add the appropriate Form letter to the Class and Type. Arrange Form letters in alphabetical sequence when ordering more than one special feature.
- Place packaging code at end of sequence with other forms when ordering.
For standard pack of 20 devices per box: C20
For individual packaged devices: leave blank
Example: 9013FSG2J21MPU2C20
NOTE: If no packaging code is indicated, devices will be shipped individually packaged.
Type FRG PUMPTROL® Water Pump Pressure Switches – Selection and Modifications
Reverse Action: Contacts Open On Falling Pressure
Cut-in Range (PSIG) | Approximate Adjustable Differential (PSIG) | Cut-Out Range (PSIG) | Pressure Connection | 1 Pole Type | 2 Pole Type |
---|---|---|---|---|---|
23-65 | 15-30 | 8-45 | 1/4" NPSF Internal 3/8" NPSF Internal 1/4" Flare 1/4" NPT External | FRG12 FRG13 FRG18 FRG19 | FRG2 FRG3 FRG8 FRG9 |
10-45 | 6-20 | 4-25 | 1/4" NPSF Internal 3/8" NPSF Internal 1/4" Flare 1/4" NPT External | FRG32 FRG33 FRG38 FRG39 | FRG22 FRG23 FRG28 FRG29 |
6-14 | 5 Non-Adjustable | 1-11 | 1/4" NPSF Internal 3/8" NPSF Internal 1/4" Flare 1/4" NPT External | FRG52 FRG53 FRG58 FRG59 | FRG42 FRG43 FRG48 FRG49 |
40-100 | 20-30 | 20-75 | 1/4" NPSF Internal 3/8" NPSF Internal 1/4" Flare 1/4" NPT External | FRG72 FRG73 FRG78 FRG79 | FRG62 FRG63 FRG68 FRG69 |
65-150 | 30-45 | 35-120 | 1/4" NPSF Internal 3/8" NPSF Internal 1/4" Flare 1/4" NPT External | FRG92 FRG93 FRG98 FRG99 | FRG82 FRG83 FRG88 FRG89 |
Pressure Codes (Reverse action)
Below is the pressure code table for reverse action devices. Existence of a code does not imply that the code is available for any or all devices.
Settings | Code |
---|---|
8.5-5.5 PSI | J17 |
10-5 PSI | J36 |
22-12 PSI | J22 |
22-16 PSI | J19 |
35-20 PSI | J70 |
40-20 PSI | J23 |
50-30 PSI | J35 |
80-60 PSI | J32 |
100-80 PSI | J51 |
150-120 PSI | J64 |
Specify other pressure | J99 |
Special Features And Modifications For Type FSG, FYG & FRG Devices
(Table already included in FSG/FYG section, as it applies to all three)
Ordering Information (Type FRG)
(Ordering information is similar to FSG/FYG, but specific examples might differ. The general structure is the same.)
- Specify Class 9013 Type FRG.
- Select pressure code from Pressure Code Table and add code designation to end of type number. Be sure that pressure code falls within the limits of the device as shown in the device listings.
- If special features are desired, add the appropriate Form letter to the Class and Type. Arrange Form letters in alphabetical sequence when ordering more than one special feature.
- Place packaging code at end of sequence with other forms when ordering.
For standard pack of 20 devices per box: C20
For individual packaged devices: leave blank
NOTE: If no packaging code is indicated, devices will be shipped individually packaged.
Type G PUMPTROL® Commercial/Light Industrial Pressure Switch – Selection and Modifications
Cut-Out Range (PSIG) | Approximate Adjustable Differential (PSIG) | Cut-In Range (PSIG) | Enclosure | Poles | NPSF Internal Pressure Connection | Type |
---|---|---|---|---|---|---|
10-35 | 4-8 | 5½-30½ | NEMA Type 1 General Purpose | 2 | 1/4 | GMG2 |
20-80 | 15-30 | 5-60 | NEMA Type 3R Rainproof | 2 | 1/4 | GSB2 |
NEMA Type 1 General Purpose | 2 | 1/8 1/4 3/8 | GSG1 GSG2 GSG3 | |||
20-80 | 20-40 | 5-50 | NEMA Type 7 & 9 Hazardous Locations | 2 | 1/8 1/4 3/8 | GSR1 GSR2 GSR3 |
NEMA Type 4 Watertight | 2 | 1/8 1/4 3/8 | GSW1 GSW2 GSW3 | |||
65-200 | 20-40 | 40-170 | NEMA Type 3R Rainproof | 2 | 1/4 | GHB2 |
NEMA Type 1 General Purpose | 2 | 1/8 1/4 3/8 | GHG1 GHG2 GHG3 | |||
65-200 | 20-40 | 40-170 | NEMA Type 7 & 9 Hazardous Locations | 2 | 1/8 1/4 3/8 | GHR1 GHR2 GHR3 |
NEMA Type 4 Watertight | 2 | 1/8 1/4 3/8 | GHW1 GHW2 GHW3 | |||
80-250 | 25-45 | 32-215 | NEMA Type 3R Rainproof | 2 | 1/4 | GHB5 |
NEMA Type 1 General Purpose | 2 | 1/8 1/4 3/8 | GHG4 GHG5 GHG6 | |||
80-250 | 24-45 | 32-215 | NEMA Type 7 & 9 Hazardous Locations | 2 | 1/8 1/4 3/8 | GHR4 GHR5 GHR6 |
NEMA Type 4 Watertight | 2 | 1/8 1/4 3/8 | GHW4 GHW5 GHW6 | |||
80-250 | 40-60 | 30-190 | NEMA Type 7 & 9 Hazardous Locations | 2 | 1/8 1/4 3/8 | GHR4 GHR5 GHR6 |
NEMA Type 4 Watertight | 2 | 1/8 1/4 3/8 | GHW4 GHW5 GHW6 |
Note: Must be mounted in vertical position to maintain enclosure rating.
Pressure Code Table (Type G)
Pressure Setting (Close-Open)
Code | Settings |
---|---|
J20 | 20-40 PSI |
J21 | 30-50 PSI |
J23 | 40-20 PSI |
J24 | 40-60 PSI |
J25 | 60-80 PSI |
J26 | 70-90 PSI |
J28 | 70-100 PSI |
J29 | 75-100 PSI |
J30 | 80-100 PSI |
J31 | 90-120 PSI |
J51 | 100-80 PSI |
J53 | 100-125 PSI |
J54 | 110-125 PSI |
J56 | 110-150 PSI |
J57 | 120-150 PSI |
J58 | 125-150 PSI |
J60 | 125-175 PSI |
J61 | 130-175 PSI |
J62 | 140-175 PSI |
J63 | 145-175 PSI |
J64 | 150-120 PSI |
J65 | 215-250 PSI |
J66 | 140-170 PSI |
J67 | 150-175 PSI |
J99 | Specify Setting Required |
Special Features And Modifications For Type G Devices
Description | Applies to | Form Letter |
---|---|---|
Standard Pack of 10 Devices per box | All Type G | C1O |
3-Way Lever (On-Auto-Off) (Not compatible with Form X) | GHG, GMG, GSG | E |
One Normally Open-One Normally Closed Contact | All Type G | H |
Pulsation Plug | All Type G | P |
Reverse Action | All Type G | R |
Slip-On Connectors (Load Side Terminals Only) | All Type G | U |
Slip-On Connectors (Line and Load Terminals) | All Type G | U2 |
Two-way Pressure Release Valve (Not compatible with Form E) | GHB, GMG, GSB, GHG, GSG | X |
GHR, GHW, GSR, GSW | X | |
1/4" Male Pipe Thread on Pressure Connection | All Type G | Z |
1/2"-14 NPT External | All Type G | Z16 |
1/4"-18 NPT Internal | All Type G | Z23 |
3/8" Male Pipe Thread on Pressure Connection | All Type G | Z23 |
Ordering Information (Type G)
- Specify Class 9013 Type G.
- Select pressure code from Pressure Code Table and add code designation to end of type number. Be sure that pressure code falls within the limits of the device as shown in the device listings below.
- If special features are desired, add the appropriate Form letter to the Class and Type. Arrange Form letters in alphabetical sequence when ordering more than one special feature.
- Place packaging code at end of sequence with other forms when ordering.
For standard pack of 10 devices per box: C10 (Available on GHB, GHG, GSB, and GSG)
For individual packaged devices: leave blank
NOTE: If no packaging code is indicated, devices will be shipped individually packaged.
Company Information
Square D Company
8001 Highway 64 East
Knightdale, NC 27545-9023, USA
(919) 266-3671
www.squared.com
Square D and [Square D logo symbol] are registered trademarks of Square D Company.
PUMPTROL® is a registered trademark of Square D Company.
SP is a registered trademark of the Canadian Standard Association.
UL is a registered trademark of Underwriters Laboratory.
Catalog No. 9013CT9701R8/98 September 1998 © 1998 Square D All Rights Reserved.
Replaces 9013CT9701 dated 6/98.