Homeline™ Combination Service Entrance Devices Circuit Breaker Installation Guide

Circuit Breaker Installation for Homeline™ Combination Service Entrance Devices

Instruction Bulletin

Document Number: 40270-308-05 Rev. 02, 04/2018

Replaces: 40270-308-05 Rev. 01, 02/2014

Introduction

Retain for future use.

Homeline™ Combination Service Entrance Devices are designed to restrict the installation of more overcurrent devices than that number for which it was designed. Be advised that the plug-on connection arrangement for HOMT circuit breakers is different from HOM circuit breakers.

⚠ DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462 or NOM-029-STPS.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors and covers before turning on power to this equipment.

Failure to follow these instructions will result in death or serious injury.

Double Row Bus Construction

Tandem circuit breaker type HOMT may be installed in combination service entrance devices where the bus bar connector has a slot at the centerline of the desired pole space. See Figure 1.

⚠ NOTICE

HAZARD OF EQUIPMENT DAMAGE

Do not use excessive force to install a HOMT tandem circuit breaker where no connector slot is provided. See Figure 1.

Failure to follow this instruction can result in damage to the circuit breaker case.

Figure 1: HOM or HOMT Circuit Breaker

Diagram showing a circuit breaker angled for connection. It features plug-on jaws at the top, a wire terminal, and a bus bar connection at the bottom. The bus bar connection is labeled as 'Rejects HOMT' for the HOM type, and has a 'Connection Slot' for the HOMT type. A mounting hook is also visible.

Figure 2: HOM Circuit Breaker

Diagram showing a HOM circuit breaker angled for connection. It features a wire terminal and a bus bar connection at the bottom, with a mounting hook. The bus bar connection is explicitly labeled as having 'No Connection Slot for HOMT'.

Note: Tighten all electrical connections to specifications. See lug torque data chart on combination service entrance device wiring diagram for torque specifications. See circuit breaker marking for lug torque specifications.

Single Row Bus Construction

Tandem circuit breaker type HOMT may only be installed in combination service entrance devices where the bus bar connector has a configuration as shown in Figure 3.

Failure to follow this instruction can result in equipment damage.

⚠ NOTICE

HAZARD OF EQUIPMENT DAMAGE

Tandem circuit breaker type HOMT may only be installed in combination service entrance devices where the bus bar connector has a configuration as in Figure 3.

Failure to follow this instruction can result in equipment damage.

Figure 3: HOM or HOMT Circuit Breaker

Diagram showing a circuit breaker angled for connection. It features plug-on jaws at the top, a wire terminal, and a bus bar connection at the bottom. The bus bar connection is labeled as 'Rejects HOMT' for the HOM type, and has a 'Connection Slot' for the HOMT type. A mounting hook is also visible.

Figure 4: HOM Circuit Breaker

Diagram showing a HOM circuit breaker angled for connection. It features a wire terminal and a bus bar connection at the bottom, with a mounting hook. The bus bar connection is explicitly labeled as having 'No Connection Slot for HOMT'.

Note: Tighten all electrical connections to specifications. See lug torque data chart on combination service entrance device wiring diagram for torque specifications. See circuit breaker marking for lug torque specifications.

Figure 5: HOM Circuit Breaker Dimensions

Diagrams illustrating the dimensions of HOM circuit breakers in inches (mm). The HOM one-pole breaker is approximately 1.98 inches (50mm) high and 0.99 inches (25mm) wide. The HOM two-pole breaker is approximately 1.98 inches (50mm) high and 1.73 inches (44mm) wide.

Figure 6: HOMT Circuit Breaker Dimensions

Diagrams illustrating the dimensions of HOMT circuit breakers in inches (mm). The HOMT Tandem breaker is approximately 1.55 inches (39mm) high and 0.98 inches (25mm) wide. The HOMT Quad breaker is approximately 1.55 inches (39mm) high and 1.97 inches (50mm) wide.

Remove Cover Twistouts

  • Remove only those twistouts which match installed circuit breakers by twisting out with pliers at the center of twistout.
  • Close unused circuit breaker openings with filler plates.
  • Order catalog number HOMFP for filler plates. Each filler plate closes one-pole branch circuit breaker opening.

Figure 7: Remove Cover Twistouts

Illustration showing a hand using pliers to twist and remove a knockout tab from an electrical panel cover.

Prepare for Installation

  1. Remove knockouts. Appropriate to knockout pattern, drive center knockout inward or outward. Alternately pry up or drive in outer rings one at a time to opening required.
  2. Figure 8: Remove Knockouts

    Sequence of illustrations demonstrating the removal of knockouts from an electrical enclosure. The first shows a knockout tab. The second shows a tool (like a screwdriver) being used to pry it. The third shows the knockout removed, creating an opening.

  3. Select the proper cable clamp, or use other approved methods for securing the cable or conduit to the enclosure.
  4. Install and wire branch circuit breakers.

⚠ CAUTION

HAZARD OF EQUIPMENT DAMAGE

Use only Homeline™ circuit breakers and replacement parts with this product. Use of other components voids the warranty, may void the UL listing and may result in personal injury or equipment damage. Refer to device markings for specific restrictions.

Failure to follow this instruction can result in personal injury or equipment damage.

Circuit Breaker Installation

  1. Turn off circuit breaker.
  2. Insert wire terminal end of circuit breaker into mounting hook.
  3. Push circuit breaker inward until plug-on jaws plug securely on to bus bar connector.
  4. Install wires.

Identify Circuits

Identify branch circuits on directory label or directory stickers.

Energize the Circuit

Note: Before energizing combination service entrance devices, turn main and branch circuit breakers to the OFF position.

  1. Turn on power to the combination service entrance device.
  2. Turn main circuit breaker ON.
  3. Turn on branch circuit breakers.

Handle at mid position indicates the circuit breaker is tripped. To reset, move handle to the off position and then to the on position.

Figure 9: Energize the Circuit

Diagrams of a circuit breaker handle showing three states: ON (up position), OFF (down position), and Tripped (middle position). A note indicates that to reset a tripped breaker, move the handle to OFF, then to ON.

Removal of Circuit Breakers

  1. Turn circuit breakers OFF.
  2. Remove wires.
  3. Disconnect plug-on jaws from bus bar connection by pulling circuit breaker outward until it disengages from mounting hook.
Models: HOM235, HOM235 Mini Circuit Breaker, Mini Circuit Breaker, Circuit Breaker, Breaker

File Info : application/pdf, 12 Pages, 538.53KB

PDF preview unavailable. Download the PDF instead.

HOM235 Installation Manual FrameMaker 2017 Acrobat Distiller 18.0 (Windows)

Related Documents

Preview QO™ and Homeline™ Load Centers Class 1100 Installation Instructions
Instruction bulletin detailing the safe installation and operation of Schneider Electric's QO™ and Homeline™ Load Centers Class 1100, including mounting, wiring, and circuit breaker procedures.
Preview Schneider Electric Square D™ Non-Metallic Enclosure for QO™ Circuit Breakers - Installation Guide
Comprehensive installation and safety guide for Schneider Electric's Square D™ non-metallic enclosures, compatible with QO™ circuit breakers, load centers, and molded case switches. Details preparation, mounting, wiring, installation, removal, and energizing procedures.
Preview QO® and Homeline® Outdoor Load Centers Installation Guide | Schneider Electric
Detailed installation and operation instructions for Schneider Electric's QO® and Homeline® outdoor load centers. Covers safety, wiring, breaker installation, and trim application.
Preview Schneider Electric QO/QOB Dual Function Circuit Breaker Installation and Testing Guide
This document provides essential information for the installation, testing, and removal of Schneider Electric QO and QOB Dual Function (AFCI/GFCI) circuit breakers. It includes detailed safety warnings, step-by-step instructions, and troubleshooting notes for proper operation and maintenance.
Preview Schneider Electric Class 9422 Type CMP Cable Operating Mechanisms Installation and Adjustment Guide
This document provides detailed instructions for installing and adjusting Schneider Electric's Class 9422 Type CMP cable operating mechanisms, designed for use with Square D PowerPacT circuit breakers. It includes essential safety warnings, component identification, step-by-step procedures, and technical specifications for proper operation.
Preview Schneider Electric GV3APN Series Installation and Safety Guide
Official installation and safety guide for Schneider Electric GV3APN series motor protection circuit breakers. Covers models GV3APN01, GV3APN02, GV3APN04, and accessories like GVAPK12 and GVAPP1, detailing safe installation procedures and electrical safety precautions.
Preview QO™ and Homeline™ Load Centers Instruction Bulletin - Schneider Electric
Comprehensive instruction bulletin for Schneider Electric's QO™ and Homeline™ Load Centers, Class 1100. Covers safety precautions, enclosure mounting (surface and flush), main circuit breaker/lug wiring, branch circuit breaker installation and removal, cover/trim installation, and energizing procedures. Includes detailed guidance for electricians and installers.
Preview Schneider Electric I-Line MCCB Installation and Product Selector Guide
This document provides installation instructions and a product selector table for Schneider Electric's I-Line Molded Case Circuit Breakers (MCCBs), detailing single-pole and triple-pole models with their specifications.