Summit Wall Mounted
Compact, stylish designs with high seasonal efficiency and low noise. Hitachi's range of Room Air Conditioning products are designed to complement the interior of any residential or commercial space. Ideal for offices, hotels and restaurants, galleries and museums, Healthcare and Domestic properties.
[Operating Temperature Indicator: +21°C to -15°C] [Operating Temperature Indicator: +43°C to -10°C] [DC Inverter Technology] [ErP Active Compliance]
Features and Benefits
- Cooling capacities from 0.9kW to 8.0kW
- Heating capacities from 0.9kW to 9.2kW
- Low noise levels courtesy of Super Low fan speed
- Nano Titanium Wasabi filters for high air quality
- All Hitachi's RAC units offer high seasonal efficiencies, with models in the Summit range achieving up to SEER A++ 6.8/SCOP A+ 4.4
- Wasabi air filter for high air quality
- NEW 24-hour, 7-day infra red remote controller with 'view energy usage' option as standard
- Connects to Hitachi's H-LINK II system via PSC-6RAD adapter providing compatibility with CS Net web
- 35vdc power supply to the indoor unit.
Product Overview Table
Features | Hitachi Summit Wall Mounted Series | |||||
---|---|---|---|---|---|---|
RAK-18PPA / RAC-18WPA | RAK-25PPA / RAC-25WPA | RAK-35PPA / RAC-35WPA | RAK-50PPA / RAC-50WPA | RAK-60PPA / RAC-60WPA | RAK-70PPA / RAC-70WPA | |
Energy Label | A+ | A+ | A+ | A++ | A+ | A++ |
Auto Restart by Previous Mode | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ |
Auto Changeover | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ |
LED Self Diagnosis | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ |
Nano Stainless Pre-filter (Option) | SPX-SPF2 | SPX-SPF2 | SPX-SPF2 | SPX-SPF2 | SPX-SPF3 | SPX-SPF3 |
Air Purifying Filter Type | SPX-CFH11 | SPX-CFH11 | SPX-CFH11 | SPX-CFH11 | SPX-CFH5 | SPX-CFH5 |
Anti-bacterial Tangential Fan | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ |
Remote Controller Type | Infra Red (Std) - Simple | Infra Red (Std) - Simple | Infra Red (Std) - Simple | Infra Red (Std) - Simple | Infra Red (Std) - Simple | Infra Red (Std) - Simple |
Remote Control Timer | Wired or Wired inc. 7-day timer (Option) | Wired or Wired inc. 7-day timer (Option) | Wired or Wired inc. 7-day timer (Option) | Wired or Wired inc. 7-day timer (Option) | Wired or Wired inc. 7-day timer (Option) | Wired or Wired inc. 7-day timer (Option) |
24hr or 7-day option | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ |
H-LINK Compatible | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ | ✔️ |
ErP-compliant products
[ErP Logo] The Eco-Design of Energy-related products (ErP) Directive provides consistent EU-wide rules for improving the environmental performance of energy-related products (ErP) - ensuring reduced energy consumption to benefit both businesses and consumers. Hitachi has always engineered the most environmentally-friendly heating and cooling products from its factories, and is delighted that its new product ranges already exceed the 2014 ErP Lot 10 standards.
Remote Controllers
NEW RAR-5E2
24-hour, 7-day infra red Remote Controller
- ECO operation energy saving function
- Leave Home Function - set temperature at 10°C automatically when no one is at home for up to 99 days
- Weekly Timer - 2 patterns
- Heating/Cooling Only operation - 2 ways of setting
- Room temperature display.
SPX-RCDB Wired Remote Controller
Technical Specifications
RAK-18PPA | RAK-25PPA | RAK-35PPA | RAK-50PPA | RAK-60PPA | RAK-70PPA | |
---|---|---|---|---|---|---|
Indoor Unit | ||||||
Nominal Cooling Capacity (min - max) | 2.00 (0.90-2.50) kW | 2.50 (0.90-3.10) kW | 3.50 (0.90 - 4.00) kW | 5.0(0.9 - 5.2) kW | 6.10 (0.9 - 6.5) kW | 7.00 (1.5 - 8.00) kW |
Cooling Sensible Capacity | 1.9 kW | 2.1 kW | 3.2 kW | 3.5 kW | 4.4 kW | 5.4 kW |
UK Cooling Capacity (sensible) | 1.9 (1.7) kW | 2.4 (2.0) kW | 3.3 (2.5) kW | 4.2 (3.1) kW | 5.3 (4.0) kW | 6.5 (4.8) kW |
Nominal Heating Capacity (min-max) | 2.50 (0.90-3.20) kW | 3.40 (0.90-4.40) kW | 4.20 (0.90 - 5.00) kW | 6.00 (0.9 - 8.1) kW | 6.80 (0.9-8.5) kW | 8.00 (1.5 - 9.2) kW |
Heating capacity at -7°C(1) | 1.6 kW | 2.2 kW | 2.7 kW | 4.2 kW | 4.2 kW | 5.6 kW |
Seasonal Efficiency SEER(3) | 5.8 | 5.8 | 5.9 | 6.1 | 6.0 | 6.8 |
Energy Efficiency Class | A+ | A+ | A+ | A++ | A+ | A++ |
Annual Energy Consumption kWh/yr | 121 | 151 | 210 | 290 | 350 | 360 |
Seasonal Efficiency SCOP(3) (Average Climate) | 4.2 | 4.2 | 4.3 | 4.3 | 4.0 | 4.4 |
Energy Efficiency Class | A+ | A+ | A+ | A+ | A+ | A+ |
Annual Energy Consumption kWh/yr | 609 | 823 | 1,003 | 1,520 | 1,670 | 2,060 |
Nominal Load Efficiency EER / COP(4) | 3.64/4.31 | 3.57/3.86 | 3.21/3.82 | 3.21/3.61 | 3.30/3.62 | 3.23/3.64 |
Energy Class (Cool/Heat) | A/A | A/A | A/A | A/A | A/A | A/A |
Dimensions (H x W x D) | 280 x 780 x 218 mm | 280 x 780 x 218 mm | 280 x 780 x 218 mm | 300X790X230 mm | 295x1030x207 mm | 333x1150x245 mm |
Weight | 7.5 Kg | 7.5 Kg | 7.5 Kg | 10.0 Kg | 12.0 Kg | 15.0 Kg |
Remote Control (standard) | Infra Red RAR-5E2 | Infra Red RAR-5E2 | Infra Red RAR-5E2 | Infra Red RAR-5E2 | Infra Red RAR-5E2 | Infra Red RAR-5E2 |
Outdoor Unit | RAC-18WPA | RAC-25WPA | RAC-35WPA | RAC-50WPA | RAC-60WPA | RAC-70WPA |
Noise level cooling (sound pressure) (night mode) | 46 dB(A) | 48 dB(A) | 49 dB(A) | 50 dB(A) | 50 dB(A) | 52 dB(A) |
Noise level heating (sound pressure) (night mode) | 47 dB(A) | 49 dB(A) | 50 dB(A) | 52 dB(A) | 53 dB(A) | 54 dB(A) |
Dimensions (H x W x D) | 505 x 700 x 258 mm | 505 x 700 x 258 mm | 548×750×288 mm | 650X850X298 mm | 650x850x298 mm | 800x850x298 mm |
Weight | 27.0 Kg | 27.0 Kg | 36.0 Kg | 45.0 Kg | 45.0 Kg | 55.0 Kg |
Working Range (cooling / heating) | -10°C~43°C / -15°C~21°C | -10°C~43°C / -15°C~21°C | -10°C~43°C / -15°C~21°C | -10°C~43°C / -15°C~21°C | -10°C~43°C / -15°C~21°C | -10°C~43°C / -15°C~21°C |
Piping diameter (Liquid / Gas) | 6.35-9.52 mm (1/4-3/8 Inch) | 6.35-9.52 mm (1/4 - 3/8 Inch) | 6.35-9.52 mm (1/4 - 3/8 Inch) | 6.35-12.70 mm (1/4 / 1/2 Inch) | 6.35-12.70 mm (1/4 / 1/2 Inch) | 6.35-15.88 mm (1/4 / 5/8 Inch) |
Power supply | 230V/1Ph/50Hz | 230V/1Ph/50Hz | 230V/1Ph/50Hz | 230V/1Ph/50Hz | 230V/1Ph/50Hz | 230V/1Ph/50Hz |
Recommended fuse size | 16 A | 16 A | 16 A | 16 A | 16 A | 20 A |
Starting current | 5.0 A | 5.0 A | 5.0 A | 10.0 A | 8.5 A | 10.0 A |
Running current (cooling / heating) | 2.65/2.84 A | 3.58/4.25 A | 5.00/5.03 A | 6.56/7.00 A | 7.80/7.90 A | 9.10/9.30 A |
Interconnecting Cables | 2 + E | 2 + E | 2 + E | 2 + E | 4 + E | 4 + E |
(1) Value includes the defrost ratio. (2) Sound power level is the A-weighted sound power level [dB(A)] measured at standard rated conditions for the "cooling" mode operation in accordance to EN12102 (3) Data calculated in accordance to prEN14825 and the Commission Communication 2012/C 172/01 (4) Nominal load efficiency (Cooling 35°C/27°C, Heating 7°C/20°C)