DUCTED WATER COOLED PACKAGED AIR CONDITIONERS

HWP models (c/w UC8)

Installation & Maintenance

1. GENERAL

1.1 Introduction

Follow these instructions to ensure the optimum performance, reliability and durability.

Units must be installed in accordance with all national and regional regulations and bylaws.

2. INSTALLATION

2.1 Positioning & Mounting

HWP units are designed to be used with simple, short duct layouts. Units should be located as close to the space to be air conditioned as acoustic criteria allows.

When determining the position of the air conditioner, allow adequate space around the unit to facilitate water pipe/hose connections, future servicing and maintenance. Ensure there is enough working space in front of the electrical access panel. Allow adequate clearance for the filter to be withdrawn to its full length.

Mount the unit using the spring mount system supplied (Fig. 1). This system minimises transfer of vibration into the building structure.

Figure 1: Spring Mounting
Diagram shows a spring mounting system. Components include: M8 Threaded Rod (recommended, not supplied), Isolating Sleeve (12 ID x 16 OD x 100mm long, supplied in Spring Kit bag), PVC hose (non-toxic clear, supplied in Spring Kit bag), Spring Mount Support (supplied fitted to unit), Spring Retainer (Ø19mm Hole, supplied in Spring Kit bag), Spring (supplied in Spring Kit bag), Spring Retainer (Ø10mm Hole, supplied in Spring Kit bag), M8 Washer (recommended, not supplied), M8 Nut (x2) (recommended, not supplied).

If a more rigid installation can be tolerated, then suspend the unit from four threaded rods using locknuts (not supplied), as shown in Fig. 2. When finally positioned, tighten the lock nuts on the mounting rods to give a firm installation. Alternatively, bolt the unit directly to the ceiling's substructure.

Figure 2: Solid Mounting
Diagram shows a solid mounting method. Components include: Mounting rod, Spring mount support (supplied), Tighten locknuts for strength, Use 30x30 flat washers supplied.

2.2 Condensate Drain & Optional Lift-Pump

Mount the unit level as it comes with a sloping drain tray. This tray is reversible (i.e., the drain exit can be at either end of the unit), unless fitting the optional Condensate Lift-Pump, in which case the exit must be at the opposite end to the compressor (i.e., standard orientation).

The drain line must not be piped to a level above the drain tray.

The drain line must be maintained at least 19 mm ID along its full length. A vent pipe is recommended for drain pipes longer than 4 m (refer Figure 3). Check drain by pouring water into the drain tray and ensuring that it clears (with the unit operating). Failure to adhere to these instructions could cause flooding.

Figure 3: Condensate Drain
Diagram shows condensate drain configuration. Includes: UNIT (100 mm APPROX.), 50 mm MINIMUM, 'U' TRAP OPEN DRAIN, VENT PIPE FOR LONG CONDENSATE DRAIN RUNS, MINIMUM SLOPE 20 mm PER m (1 IN 50).

2.3 Air Ducts, Filters and Grilles

Rigid Ducting:

3. WATER CONNECTION

3.1 General

The HWP unit's IN and OUT water connections are male BSP pipe threaded. The unit can be piped directly or using two temperzone flexible high pressure water hoses (supplied) which have female pipe threaded connections at each end. Refer Table 2, p.8, for minimum bend radius.

Poor quality water supply must be pre-filtered and it is essential that adequate water treatment is maintained, particularly where open cooling towers are used.

Note: It is recommended that the water supply system be fitted with a water flow switch and water flow verification circuit. These items prevent the HWP units from going into fail safe lockout status due to a loss of water flow. Failure to install the above items could require the resetting of all HWP units in the system – by breaking the power supply to each unit or by Modbus command.

3.2 Circuit Balancing Valve

It is recommended that a circuit balancing valve be fitted to maintain water flow at a constant rate. The minimum water flow rates in litres per second (l/s) are stated in the supplied Specifications Data sheet.

The HWP unit controller will protect the refrigeration system of the unit under severe operating conditions. On heating cycle it protects to ensure the evaporating temperature does not drop below freezing for an extended period. The extreme lowest leaving water temperature needs to be such that the unit does not cut-out on protection and will be above approx. 4°C. This can be achieved by a combination of the Entering Water Temperature (EWT) and the reduced flow rate. Water flow needs to be balanced to suit the system design. Refer Technical Data for acceptable water flow rates and pressure drop data.

3.3 Air / Water Flow

Refer to HWP Technical Data pamphlets at www.temperzone.biz for detailed information on air handling performance and water flow rates.

3.4 Water Circulating Pump & Flow Verification Option

In order to promote efficiency and avoid running the water circulation pump unnecessarily, the unit's UC8 Controller can be used to control the activation of the pump prior to running the compressor. After activation of the external water circulating pump, the UC8 waits for the flow verification contact to close before energising the compressor contactor and therefore starting the compressor (refer wiring diagram, p.7). The UC8 also de-activates the pump when the compressor stops.

3.5 Water Regulating Valve Control Option

A 0-10V signal is available on output V1 for the control of a water flow control valve (optional; not supplied by temperzone); refer wiring diagram. When used, the valve is closed (0V signal) when the compressor is off. When the unit is cooling the signal will control the valve to obtain an optimum condensing temperature. When the unit is heating (reverse cycle units) the valve is directed fully open (10V signal).

3.6 Water Shut-Off Valve Option

This will ensure the water is not flowing through the unit when it is not operational for a long period of time, thereby reducing the overall central pump power usage. The water shut-off relay on the HWP can be used to activate a water shut-off valve (supplied and fitted by others).

4. WIRING

4.1 General

Electrical power wiring must be fitted and certified by persons with appropriate qualifications and certification. A signed 'Certificate of Compliance' must be left with the unit for insurance purposes.

4.2 Power to Unit

All power wiring is to be done to the appropriate electrical standard of the country in which the unit is being installed. The person installing the wiring is responsible for the correct selection of wiring size and auxiliary components. See the Specification Sheet for supply voltage range, frequency, phase and maximum operating current.

Wire the unit directly from the Electrical Distribution Board. The unit should have its own dedicated circuit breaker on the Distribution Board and an isolator switch should be installed in accordance with the applicable wiring regulations.

4.3 Control

Room Temperature Controller (Reverse Cycle Models)

The thermostat should be set within the recommended operating range of between 19°C and 30°C.

Various options are available to control the air conditioning unit operation.

Note: HWP units are supplied with SAT-3 compatible Return Air temperature sensors pre-installed in each unit. To activate the sensor: (i) place the SAT-3 in Installer mode by holding down 'mode' and '6' buttons together for 3 seconds, (ii) scroll to option 'rt', then select option number '4', (iii) press the 'mode' button to save setting.

Additional Control Options

5. UNIT PROTECTION

5.1 General

Unit protection is incorporated in the UC8 Controller board. A high pressure lockout protects the unit in the event of either water flow failure in cooling mode, fan failure in heating mode, or a loss of refrigerant. Units include an anti rapid cycle timer for compressor on/off protection.

On HWP*R units the unit's controller (UC8) protects against freezing of the water within the unit on heating mode. There are optional relay boards available for both a generic fault output and a status indicator.

Refer to UC8 Controller label on the unit for operation & fault diagnostics information, or visit www.temperzone.biz.

Note: Lockout protection can be reset by switching the unit's power supply off and on. Lockout protection can also be reset by Modbus connection. For detailed information about control via Modbus RTU refer to document UC8 Modbus communications available at www.temperzone.biz; model search 'UC8'.

5.2 UC8 Controller Options

For more information on the functions, operation and options provided by the UC8 Controller (e.g., thermostat options, remote on/off, BMS control via modbus over RS485, condensate lift-pump control, DRED, data logging), refer www.temperzone.biz; model search 'UC8'.

6. START-UP PROCEDURE

6.1 Power

6.2 Fan

6.3 Models with EC Fan Motors (Y Series only)

Various options are available if either High speed or Low speed need adjusting:

6.4 Starting the Compressor

6.3 General Checks

7. CONTROLS

7.1 TZT-100 and SAT-3 wall thermostat

To connect the thermostat to the unit it is recommended to use shielded twisted pair type cable, suitable for RS485 communications. Signals A and B should form one twisted pair. Note: The cable shield should connect to terminal '0V' on the UC8 controller only. Do not connect at both ends. Refer page 6 for Client Wiring Schematic.

TZT-100 has a set of DIP switches that must be set as follows:

Fault code 36 will appear on the UC8 if the DIP switch settings are incorrect.

7.2 Communications format for TZT-100 and SAT-3.

Communications format must be set as per recommended Modbus RTU:

TZT-100: The procedure to check and adjust these settings is: 1. Press and hold the O/RIDE button until the display shows the PIN. 2. Use the UP & DOWN buttons to select PIN code 88:21, then press O/RIDE in installer mode. 3. Use the O/RIDE and PROG buttons to cycle through the various installer settings. If necessary, refer TZT-100 User Manual for more detail.

SAT-3: The procedure to check and adjust these settings is: 1. Press and hold the MODE and 6 button until the display shows the 'i' symbol. 2. Use the UP & DOWN buttons to cycle through the various installer settings. 3. Press MODE button to save any new setting. If necessary, refer SAT-3 Installation Guide for more detail.

7.3 Control via Modbus RTU communications

Single or multiple HWP units can be fully monitored and controlled via Modbus RTU serial communications. The following is typical for most installations:

It is recommended to 'daisy-chain' the A&B connections using shielded twisted pair type cable, suitable for RS485 communications. Signals A and B should form one twisted pair. The cable shield should connect to terminal '0V' on the UC8 controller.

To avoid collisions of messages on the RS485 serial communications cable it is necessary to ensure each connected UC8 controller has a unique Modbus device address. Refer to section 7.4 for the procedure.

For detailed information about monitoring and control via Modbus RTU refer to document "UC8 Modbus communications" available at www.temperzone.biz; model search 'UC8'.

7.4 Setting the UC8 Modbus device address

To view or change the Modbus device address of a UC8 follow these steps:

7.5 Run Status / Fault monitoring

UC8 includes a Run Status monitoring output signal. The output is active when one of the following conditions apply:

A non-specific Fault monitoring output signal is also available. Refer Troubleshooting (9.7) regarding fault codes.

8. MAINTENANCE

8.1 Weekly For First Four Weeks

8.2 Monthly

Check air conditioning system air filters; vacuum or wash clean, or replace as necessary.

8.3 Six Monthly

8.4 Yearly

9. TROUBLESHOOTING

9.1 Room temperature varies significantly from its setting

9.2 Air conditioner does not seem to deliver the heating when most needed

9.3 In a new building, why does it take some days before the air conditioning heat pump unit seems to work properly

Many new buildings, especially commercial buildings, have a large amount of concrete and other structural materials that are generally cold and full of moisture. This is most evident in the winter when trying to heat the building from scratch.

9.4 HWP unit is spitting or leaking water

9.5 Air conditioner runs excessively – the temperature remains too hot in summer or too cold in winter.

9.7 Unit displays an error code:

Refer to UC8 Controller label on the unit for operation & fault diagnostics information; or visit www.temperzone.biz and model search 'UC8 Controller'. Here you will also find a 'UC8 Troubleshooting Guide'. For repeated faults, check the unit is operating within the specified water temperature range and conditions outlined in the Specification Sheet.

10. WARRANTY

Please refer to the separate warranty document supplied with the unit, or visit www.temperzone.biz for details.

Australia:
warranty@temperzone.com.au
spares@temperzone.com.au
Telephone: 1800 21 1800

New Zealand:
customerservices@temperzone.co.nz
Telephone: 0800 TZWARRANTY (899 2777)

NOTE: Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.

APPENDIX I – PROTECTION FUNCTIONS

The UC8 implements system protection functions such as indoor coil frost, extreme high and low pressures, rapid on/off cycling of the compressors, loss of refrigerant and more.

The following applies to all protection functions except where otherwise indicated:

More detailed information about protection functions and troubleshooting refer to document "UC8 troubleshooting information", available for free download from the temperzone internet website.

1 High pressure protection (HP)

Some HWP units may be fitted with high pressure switches. These switches connect to UC8 inputs IN#1. When a high pressure switch activates (the electrical circuit opens) then the compressor is stopped.

Some HWP units are fitted with high pressure transducers connected to UC8 input HPT. A compressor is switched off when the discharge line pressure reading exceeds 4238 kPa.

The display shows the letters 'HP' when protection is active.

2 Low pressure protection (LP)

Some HWP units may be fitted with low pressure switches. These switches connect to UC8 inputs IN#2. When a low pressure switch activates (the electrical circuit opens) then the compressor is stopped.

Some HWP units are fitted with low pressure transducers connected to UC8 input LPT. A compressor is switched off when the suction line pressure reading falls below 228 kPa.

The display shows the letters 'LP' when protection is active.

3 Indoor coil frost protection

When the unit is cooling the evaporating temperature in the indoor coil should remain above -8°C. If this temperature falls below -8°C then ice (frost) likely will form on the indoor coil. If the low temperature persists for longer than 6 minutes then the protection function activates.

When indoor coil frost protection is activated the compressor is stopped for 6 minutes, after which it is allowed to restart.

4 High discharge line temperature protection

The controller monitors the compressor discharge line temperature via a sensor connected to input 'DL' (red wires). The compressor is stopped when:

The display shows the message 'Hi-t' when protection is active.

5 High discharge superheat protection

Discharge superheat is defined as the difference between the compressor discharge gas temperature and the condensing temperature. When this temperature differential becomes very high it is an indication that the compressor is being starved of refrigerant gas. Common reasons for this could be a lack of refrigerant (under-charged or loss-of-charge) or a problem with the expansion device (for example a stuck accurator or loose wiring to an EEV).

The protection is activated when discharge superheat exceeds 45K for longer than 30 minutes.

The display shows the message 'Hi-dSH' when protection is active.

6 Low discharge superheat protection

Discharge superheat is defined as the difference between the compressor discharge gas temperature and the condensing temperature. When this temperature differential stays very low it can be an indication that the compressor is being flooded with liquid refrigerant. Common reasons for this could be an excess of refrigerant (over-charged) or a problem with the expansion device (for example a stuck accurator or loose wiring to an EEV).

The protection is activated when discharge superheat remains below the threshold for longer than 15 minutes. The threshold varies linearly from 0K at standard mode minimum capacity (40%) to 10K at nominal capacity (100%).

This protection function is disabled when a compressor operates at less than standard mode minimum capacity (<40%).

The threshold for a variable speed compressor operated in boost mode (capacity above 100%) is fixed at 10K.

The display shows the message 'LO-dSH' when protection is active.

7 High evaporation temperature / high suction line temperature protection

When the unit has a low pressure transducer connected to the compressor suction line then the controller calculates the evaporating temperature from the suction line pressure reading. If the unit does not have a low pressure transducer then the controller finds the evaporating temperature via a coil temperature sensor (input IC when the unit is cooling, input OC when the unit is heating, yellow wires). Additionally the controller monitors the compressor suction line temperature via a sensor connected to input 'SL' (white wires).

The protection function stops the compressor when:

The display shows the message 'Hi-SL' when protection is active.

8 Other alarms

The controller performs many other protection functions. For example:

APPENDIX I – CONT'D

9 Lock-out

Each protection function has a trip counter. A trip counter is reset to 0 whenever the compressor run request is removed. Any trip that has occurred more than 12 hours ago is removed from the trip count.

For some protection functions, when the trip counter reaches value 3 (i.e. three consecutive trips occur) then the unit is "locked out".

When a unit is locked out the compressor is not allowed to start. Lock-out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician.

The display shows the code of the fault that caused the lock-out condition.

A unit that is locked out can be unlocked using any one of the following methods:

APPENDIX II – UNIT CONTROLLER

Diagram Description: The diagram illustrates the UC8 Unit Controller and its various input/output connections for power supply, thermostats (SAT-3, TZT-100), optional components (water flow verification, pump control, flow valve, lift-pump, float switch, remote on/off, external fault alarm), BMS communication (RS485), and fan output relays.

Display Messages (Normal Operation):

Faults: Lists various fault codes (LP, HP, HI-t, LO-t, nO-FLO, FLOOD, FROST, HI-SL, Hi-dSH, OL, F11-F43) and their descriptions.

Monitoring of pressures and temperatures: Press the push button to cycle through the following options (round robin fashion):

How to activate Special Modes

Thermostat and compressor must be OFF.

Press and hold pushbutton until the display shows the letter that corresponds to the special mode. Note: depending on the model some special modes may not be available. Available special modes are: t - Test mode, H - Indoor fan high speed selection, E - Compressor model selection, c - Commissioning mode, L - Indoor fan low speed selection, A - Modbus address selection. Release the push button as soon as the display shows the correct letter.

COMMISSIONING CHECK LIST

This checklist is to be completed by the installer.

Site Details: Site Name/address, Installing Company, Serviceman, Date, Tel, Model, Serial No, Unit Site Ref.

Installation Checks:

UC8 Dip Switch Settings: Mark positions with an 'X'.

SW112345678SW29 (1)10 (2)11 (3)12 (4)13 (5)14 (6)15 (7)16 (8)
OnXOn
OffXXXXXXXOffXXXXXXX

Record UC8 Monitored Conditions: (at least 10 minutes after compressor starts, using push button SW3, repeat to scroll through list)

Cool Cycle:

ParameterUnitValueParameterUnitValue
Low Pressure:SLPkPaReturn air temperature:°C
Evap temperature:Et°CSupply air temperature:°C
Suction Line temperature:SLt°CEntering Water temperature:°C
Suction Superheat:SSHKLeaving Water temperature:°C
Discharge Line Pressure:dLPkPaCompressor amps:A
Condensing temperature:Ct°CTotal amps:A
Discharge Line temperature:dLt°CInput voltage:A
Discharge Superheat:dSHK
De-ice Sensor temperature:ICEt°C
Required Capacity:CAP%
Expansion Valve 1:EE1%
Expansion Valve 2:EE2%

Heat Cycle:

ParameterUnitValueParameterUnitValue
Low Pressure:SLPkPaReturn air temperature:°C
Evaporating temperature:Et°CSupply air temperature:°C
Suction Line temperature:SLt°CEntering Water temperature:°C
Suction Superheat:SSHKLeaving Water temperature:°C
Discharge Line Pressure:dLPkPaCompressor amps:A
Condensing temperature:Ct°CTotal amps:A
Discharge Line temperature:dLt°CInput voltage:A
Discharge Superheat:dSHK
De-ice Sensor temperature:ICEt°C
Required Capacity:CAP%
Expansion Valve 1:EE1%
Expansion Valve 2:EE2%

Water temperature difference should be: Cooling: 5-7°C, Heating 3-5°C.

Branches

Distributors

Visit www.temperzone.biz for more information.

Models: UC8 Ducted Water Cooled Packaged Air Conditioners, UC8, Ducted Water Cooled Packaged Air Conditioners

File Info : application/pdf, 12 Pages, 1.09MB

PDF preview unavailable. Download the PDF instead.

HWP cw UC8 Generic IM 0422

References

Adobe PDF Library 16.0.7 Adobe InDesign 17.2 (Macintosh)

Related Documents

Preview Temperzone HWP-K Series: Ducted Water Cooled R410A Packaged Air Conditioners Product Review
An overview of the Temperzone HWP-K Series ducted, water-cooled, R410A packaged air conditioners, detailing features, specifications, and application considerations for commercial and industrial HVAC systems.
Preview Temperzone Water-Cooled Packaged Units: HWP & CWP Series - Features, Specifications, and Technology
Discover Temperzone's advanced HWP and CWP series of water-cooled packaged air conditioning units. This brochure details their innovative ThermoShell technology, flexible control options, comprehensive specifications, and applications for efficient climate control in commercial and residential buildings.
Preview Temperzone Water Cooled Packaged Units: Energy Efficient HVAC Solutions
Discover Temperzone's advanced Water Cooled Packaged Units (HWP and CWP series). Featuring innovative ThermoShell® technology, these units offer superior energy efficiency, design flexibility, and cost savings for commercial and high-rise building applications.
Preview Temperzone Water Cooled Packaged Units: Energy Efficient HVAC Solutions
Discover Temperzone's advanced Water Cooled Packaged Units, featuring energy-efficient ThermoShell® technology for superior performance and cost savings. Explore HWP and CWP series for flexible, reliable climate control solutions.
Preview temperzone CWP Ducted Water Cooled Packaged Air Conditioners Installation & Maintenance Manual
Comprehensive installation and maintenance guide for temperzone CWP series ducted water-cooled packaged air conditioners, featuring the UC8 controller. Includes setup, wiring, troubleshooting, and safety information for optimal performance and reliability.
Preview Temperzone and Hitachi Air Conditioning Warranty New Zealand
Comprehensive guide to the Temperzone and Hitachi air conditioning product warranty in New Zealand, detailing terms, conditions, coverage, exclusions, claim procedures, and recommended maintenance.
Preview Temperzone ISD 211LYX and OSA 211RLTFH Air Conditioner Specifications and Wiring
Detailed technical specifications, dimensions, and wiring diagrams for the Temperzone ISD 211LYX indoor unit and OSA 211RLTFH outdoor unit. Includes performance data, accessories, optional controls, and electrical connection schematics.
Preview Temperzone OPA 171/211 RLTFYD (Econex Pro) Installation and Maintenance Manual
Comprehensive installation and maintenance guide for Temperzone OPA 171/211 RLTFYD (Econex Pro) air-cooled packaged units. Covers general information, installation procedures, refrigeration system details, wiring, economiser function, start-up, operation, maintenance schedules, troubleshooting, warranty information, and control system setup.