Temperzone ISD 211LYX and OSA 211RLTFH Air Conditioner Specifications and Wiring
Specifications
Feature | Indoor Unit (ISD 211LYX) | Outdoor Unit (OSA 211RLTFH) |
---|---|---|
Cooling capacity range (gross) | 9.4 ~ 25.3 kW | |
Cooling capacity (net) to AS/NZS 3823 T1 | 19.0 kW | |
Heating capacity range | 8.4 ~ 25.6 kW | |
Heating capacity H1 | 20.8 kW | |
Electrical input - cooling | 6.0 kW | |
Electrical input - heating | 5.8 kW | |
EER / AEER (cooling) | 3.15 / 3.13 | |
COP / ACOP (heating) | 3.57 / 3.54 | |
Unit Controllers | UC8 / IUC | |
Refrigerant | R32 | |
Refrigerant precharge for 15 m | 5.2 kg | |
Minimum floor area (@2.4m below ceiling diffuser) | 14.4 m² | |
Additional charge req'd for over 15 m | 60 g/m | |
Maximum line length | 60 m | |
Max. charge / Min. floor area (below ceiling diffuser) | 7.9 kg / 33.2 m² | |
Separation limit: OSA above ISD | 20 m | |
Separation limit: OSA below ISD | 20 m | |
Suction line | 19 mm OD | |
Liquid line | 9.5 mm OD | |
Compressor oil type | POE-46 (NXG5020 or equivalent) | |
Additional oil charge over 40 m length | 10 ml/m | |
Compressor type | inverter scroll | |
Power supply via OSA | 3 ph. 400V ac 50Hz | |
Compressor (3ph.) run amps at rating cond. | 9.0 A | |
Indoor fan motor size | 1250 W | |
Rated indoor fan speed | 6.5 V | |
Indoor fan motor (1ph.) - full load | 6 A | |
Outdoor fan motor (1ph.) - full load | 1 A (x2) | |
Outdoor fan capacitor size | 5 μfd (x2) | |
Control circuit breaker (internal) | 10 A | |
Running amps (total system) | 13.0 / 9.0 / 10.0 A | |
Max. running amps (total system) | 23.0 / 14.5 / 15.5 A | |
RCD type recommended | type B, 30mA | |
Net weight ISD / OSA | 86 / 129 kg |
Accessories
- ISD Spring mounting kit: 307-161-101
- ISD Spigot plate adaptor Ø450 x 2 (NZ only): 525-311-715
- ISD Filter box c/w EU2/G2 filter (NZ only): 493-000-006
- ISD Replacement filter (NZ only): 119-000-082
- ISD Supply air plenum Ø400 x 3 (NZ only): 492-000-005
- ISD Return air plenum Ø400 x 3 (NZ only): 492-100-005
- ISD Fresh air inlet spigot Ø150 (NZ only): 325-000-051
- OSA Drain connection adaptor 25/13mm: 060-000-039
- OSA Anti-vibration mounts - rubber (x4): 060-000-170
- OSA Wall mounting kit: 526-061-007
Optional Controls
- SAT-3 Room temperature controller: 201-000-146
- Six Zone Control kit for SAT-3: 201-000-073
- TZT-100 Room temperature controller: 201-000-350
Refer to Temperzone for other options, e.g., remote sensors, connection wires.
Tested in accordance with AS/NZS 3823.
Dimensions and Load Points
ISD 211LYX Indoor Unit Dimensions:
The diagram illustrates the unit's overall dimensions, including width (W), depth (X), height (Y), and mounting center dimensions (Z). It indicates clearance requirements (e.g., 500mm minimum clearance) and the location of access panels and optional filter boxes.
Indoor Unit Point Loads (kg):
Point | W | X | Y | Z |
---|---|---|---|---|
Load | 21 | 24 | 21 | 20 |
Note: The fan motor can be accessed from panels above, below, or on the sides, with a maximum of two panels used at once.
OSA 211RLTF Outdoor Unit Dimensions:
This diagram shows the outdoor unit's overall dimensions, including width (W), depth (X), height (Y), and mounting center dimensions (Z). It highlights clearance requirements (e.g., 150mm, 750mm minimum clearances), refrigerant connections, electrical box location, drain holes (25mm diameter), and optional filter box access.
Outdoor Unit Point Loads (kg):
Point | W | X | Y | Z |
---|---|---|---|---|
Load | 21 | 40 | 37 | 31 |
Recommended Connecting Pipe Sizes:
- Suction: 19 mm OD
- Liquid: 9.5 mm OD
Note: Specifications are subject to change without notice due to the manufacturer's ongoing research and development program.
Indoor Unit Wiring
This section details the internal wiring of the indoor unit and its connection to the outdoor unit. Key elements include:
- Indoor Unit Controller (IUC): The central control board for the indoor unit.
- Connections to Outdoor Unit: Primarily via ETH1, often with ferrite passes [??] to ensure signal integrity.
- Temperature Sensors: Connections for Coil 1 (Yellow), Line 1 (Red), Supply Air (Black), and Return Air (Black) are specified.
- Optional Controls: Connections for SAT-3 and TZT-100 room controllers, and a Six Zone Control kit are shown.
- Remote On/Off Option: A dry contact connection is indicated, with a note to remove a link if this option is fitted.
- DIP Switch Settings (DS1, DS2): These switches configure various unit parameters, including output voltage and voltage range settings. Factory default settings and site commissioning options are provided.
- IUC Board Jumper Selection (J1, J2): Jumpers are used to configure settings based on cable length and termination.
Note: Refer to the 'Installation & Maintenance' pamphlet for detailed indoor-outdoor connection wiring.
Outdoor Unit Wiring
This section outlines the external wiring and internal connections of the outdoor unit. Key components and connections include:
- Power Supply: Connections for L1, L2, L3, and N from the external protection and isolation unit.
- Indoor Unit Connection: Multiple ETH connections (ETH1, ETH2, ETH3, ETH4, ETH5, ETH6) link the outdoor unit to the indoor unit's UC8 board. Ferrite passes [??] are used on various signal lines.
- Variable Speed Drive (VSD): The outdoor unit utilizes a VSD for motor control, with specific connections and DIP switch settings for its configuration.
- Sensors and Transducers: Connections for various sensors are detailed, including:
- Discharge Temp (S, Grey)
- Suction Temp (S, White)
- Ambient Temp (S, Black)
- O/D Coil Temp (S, N/A)
- I/D Coil Temp (S, N/A)
- Low Pressure (T, Fitted)
- High Pressure (T, Fitted)
- Key Components: Electronic Expansion Valve (EEV), Control Circuit Breaker (CCB), Crankcase Heater (CCH), Compressor Motor (CM), Outdoor Fan Motor (OFM), Reversing Valve (RV).
- DIP Switch Settings: Configuration options for TFC, VSD, and UC8 are provided, along with jumper settings for UC8.
- Customer Notes: Instructions on passing wires through ferrites are included.
Note: Refer to the 'Installation & Maintenance' pamphlet for detailed indoor-outdoor connection wiring and alternative thermostat or BMS options.