INSTALLATION INSTRUCTIONS

ECB47 Series Units

ELECTRIC HEAT SECTIONS

Model Number: 508508-01

Date: 4/2025

Important Safety Information

⚠️ WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.

⚠️ CAUTION

As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.

Shipping and Packing List

Package 1 of 1 contains:

Check equipment for shipping damage; if found, immediately contact the last carrier.

General Warnings and Information

⚠️ WARNING

Maximum Altitude of application is 3200m above sea level.

Partial units shall only be connected to an appliance suitable for the same refrigerant.

⚠️ WARNING

Electric shock hazard! - Disconnect all power supplies before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.

The ECB47 series electric heat section provides field-installed electric heat for various air handler units. These electric heat sections are available in either single- or three-phase. Single-phase heat sections are equipped with either terminal blocks or circuit breakers. Refer to the model-specific air handler product specification bulletin for heat section applications.

These instructions are a general guide and do not supersede local codes. Local authorities having jurisdiction should be consulted before installation. Read these instructions thoroughly before starting installation. Be sure to disconnect all power to the unit before you install and service this equipment. Use proper tools and protective equipment during installation and service. Installation of air handler with or without optional electric heat must conform with standards in the National Fire Protection Association (NFPA) Standard for Installation of Air Conditioning and Ventilation Systems NFPA No. 90A, and Standard for Installation of Resident Type Warm Air Heating and Air Conditioning System, No. 90B, the manufacturer's installation instructions, and local municipal building codes.

⚠️ WARNING

Every working procedure that affects safety means shall only be carried out by competent persons. This appliance is not to be used by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure they do not play with the appliance.

Heat Section Installation

Before installing the electric heat section, check the unit rating plate to ensure that the unit meets the job requirements, that proper electrical power is available, and that proper duct clearances are maintained.

Figure 1: Air Handler Electric Heat Knockouts

Description: Diagram showing knockout locations on an air handler for electric heat installation. It indicates an extended width knockout is used when installing 20kW or 25kW electric heat.

NOTE: It is easier to install the electric heat section inside the air handler unit before the unit is set and the plenum is attached.

  1. Shut off all power to the air handler. More than one disconnect may be required.
  2. Remove air handler access panel.
  3. Remove the electric heat knockout from the air handler vestibule panel to accommodate the heater being used. Remove the extended width knockout to allow for installation of 20kW or 25kW heater (see figure 1).
  4. Slide the electric heat section into the air handler. Be careful that the heating elements do not rub against the sheet metal opening when they slide into the air handler. The hole(s) on each side of the heater line up with holes in the air handler control box. Secure the electric heater into place with the screws that are provided in the bag assembly.

Cabinet Modifications for 460 Volt, 3 Ton Models

Modifications are necessary when an ECB47-10F-G / 15F-G voltage (460 volt) electric heat section is installed in a 460 volt, 3 ton air handler (see figure 2).

Issue:

Tabs on a 460 volt, 3 ton air handler prevent proper installation of the ECB47-10F-G / 15F-G voltage (460 volt) electric heat section.

Solution:

Remove the tabs identified below.

Figure 2: Cabinet Modifications

Description: Image showing tabs on the air handler cabinet that restrict electric heat section installation, with an arrow pointing to them.

Circuit Breaker Installation

⚠️ WARNING

Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes. Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.

  1. Install the circuit breaker on the air handler deck flange. Use the provided six screws to secure the circuit breaker (see figure 3).

NOTE: When applied in the downflow position, the circuit breakers must be rotated to the UP position. See figure 3 and follow the procedure below:

  1. Disconnect power to the unit if present.
  2. Remove the screw and slide the breakers off the mounting rail. NOTE: You may need to remove the wire tie closest to the circuit breaker to allow rotation.
  3. Rotate the circuit breaker 180 degrees.
  4. Slide the circuit breaker back on the rail and secure in place with previously removed screw.

2. The air handler access panels are factory supplied. There is a patch plate over the circuit breaker opening. Remove the circuit breaker patch plate from the air handler access panel. See figure 4.

3. Replace the air handler access door.

4. Choose the appropriately sized adhesive-backed circuit breaker seal and remove any perforated sections (if needed). Apply the seal to the outside of the air handler access panel so that the seal is snug around the circuit breakers.

5. Break the patch plate for the specific size of electric heat section that you are installing. Discard the unused piece of patch plate (see figures 5 and 6).

6. Secure the patch plate on the air handler access door.

Figure 3: Electric Heat Section with Circuit Breakers

Description: Diagram illustrating circuit breaker installation on an air handler deck. It shows the rotation of circuit breakers to the UP position for downflow applications and includes instructions for removing and re-securing them.

Figure 4: Circuit Breaker Seal and Patch Plate Installation

Description: Diagram showing the installation of a circuit breaker seal and patch plate onto the air handler access panel. It indicates where to break the patch plate and advises discarding unused pieces. A note recommends using a separate circuit breaker cover (Catalog # 82W01).

Circuit Breaker and Patch Plate Configuration

Figure 5: Circuit Breaker and Patch Plate Configuration (Select Cases in Air Handlers with Small Cabinets)

Description: Diagrams illustrating patch plate and circuit breaker seal configurations for various ECB47 models (ECB47-4CB to ECB47-15CB) in air handlers with small cabinets. It shows how to orient and install the patch plate and seal, with instructions to discard unused parts.

Figure 6: Circuit Breaker Heater and Patch Plate Configuration (Common Configurations)

Description: Diagrams illustrating patch plate and circuit breaker seal configurations for common ECB47 models, including single-phase (ECB47-4CB to ECB47-25CB) and three-phase (ECB47-10CB 3 Ph to ECB47-25CB 3 Ph). It shows how to orient and install the patch plate and seal, with instructions to discard unused parts.

Circuit Breaker Cover Installation

If the air handler is installed in an unconditioned space the provided circuit breaker cover must be installed.

  1. Use isopropyl alcohol to clean the surface that the circuit breaker cover will be attached to.
  2. Remove paper backing from foam seal around perimeter of circuit breaker cover (figure 8).
  3. Run a bead of clear silicone around the perimeter of the circuit breaker cover to seal any gaps between the cabinet access door and the circuit breaker cover.
  4. Position the breaker cover over the air handler circuit breaker opening (figure 9).

ℹ️ IMPORTANT

Confirm airtight seal between breaker cover and air handler access panel. Apply a thin silicone bead to the adhesive back seat to ensure airtight seal. Failure to seal circuit breaker cover will allow warm moist air to be pulled into control panel which can create condensation to form on the circuit breaker and other electrical components within the control panel.

Figure 7: Circuit Breaker Location

Description: Image showing the location of the circuit breaker within the air handler.

Figure 8: Remove Paper Backing

Description: Diagram illustrating the removal of paper backing from the foam seal on the circuit breaker cover.

Figure 9: Circuit Breaker Cover Installation

Description: Image showing the circuit breaker cover positioned over the air handler circuit breaker opening.

Electrical Connections

ℹ️ IMPORTANT

USE COPPER CONDUCTORS ONLY

NOTE: Refer to the nameplate on the air handler unit for minimum circuit ampacity and maximum over-current protection size.

The air handler units are provided with openings to be used with 1-1/2 inch trade size (1-31/32 inch diameter) conduit. A conduit reducer washer has been provided if you are installing a smaller sized conduit.

For single-point power supply, refer to the nameplate on the single-point power supply accessory for minimum circuit ampacity and maximum over-current protection size. Select the proper supply circuit conductors in accordance with tables 310-16 and 310-17 in the National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1. Refer to figure 11 for typical air conditioner applications and figure 12 for typical heat pump applications with an air handler unit and electric heat section. Refer to figure 13 for typical system diagram for air handlers with electric heat sections.

Make wiring connections

  1. Disconnect the interface harness from the air handler unit. Connect the plug from the heater to the matching plug inside the air handler.

NOTE: 575V, 3-Phase, 60Hz heaters are shipped with a line-voltage-to-460V transformer. This transformer provides 460V power to the air handler motor and transformer only. Disconnect the 2-wire connector from the air handler interface harness and the air handler transformer. Connect the 575V to 460V transformer between these connections. See figure 10 for installation location.

  1. If using a two-stage thermostat—Remove the jumper between terminals W2 and R of TB1 terminal block and connect the second-stage heat bulb lead to W2.
  2. If using an outdoor thermostat—Remove the jumper between terminals W2 and R of TB1 terminal block and connect leads to W2 and R.

4. Make wiring connections as follows:

Figure 10: Installing Fuse Block and Transformer (575V only)

Description: Image showing the installation of a fuse block and a 575V to 460V transformer.

Unit Start-Up

  1. Replace the air handler access cover.
  2. Restore power to the unit.
  3. Set the thermostat heat anticipator to 0.4 amps.
  4. Align the provided wiring diagram sticker with the air handler diagram on the blower housing. Remove the backing and affix the sticker to the housing.
  5. Set the thermostat above room temperature.
  6. Check the system for normal operation.
  7. Set the thermostat to desired setting.

Air Handler Blower Speed Connections

When using ECB47 heat section, adjust the blower speed according to the size of electric heat and air handler unit. The minimum blower setting for each air handler size with any heat sections in any application is HIGH. See specific air handler installation instructions for blower speed adjustment procedure.

Label Installation

  1. Verify that air handler access door panel has a Unit Accessory label marked ECB47.
  2. If not, (or if R-410A air handler), per table 1 below, choose the applicable Accessory Kit Label per voltage as installed.
  3. Peel label backing and apply correct Accessory Kit Label on the air handler access door panel.

Electric Heat Accessory Kit Label Cross Reference

The following table provides a cross-reference for Accessory Kit labels for each unit.

Unit TypeAccessory Kit Label #
240V - P581273-01
240V - Y581276-01
460/575V - G/J581279-01

Typical Unit Applications

Refer to figures 11 and 12 for typical field wiring for cooling and heat pump applications including an air handler with electric heat.

Unit Field Wiring Diagrams

Figure 11: Typical Unit Diagram – Air Handlers with Constant Torque Motors (P Voltage – 208-230V, 1-Phase, 60Hz)

Description: This diagram illustrates the field wiring for units with and without circuit breakers, for air handlers with constant torque motors operating on P Voltage (208-230V, 1-Phase, 60Hz). It includes component keys, blower speed tap settings, and notes on wiring practices and jumpers. It depicts connections for blower, transformer, relays, and thermostat signals (R, Y1, Y2, W1, W2, G, C).

Figure 12: Typical Unit Diagram – Air Handlers with Constant Torque Motors – RDS Controller (P Voltage – 208-230V, 1-Phase, 60Hz)

Description: This diagram shows the field wiring for units with and without circuit breakers, specifically for air handlers with constant torque motors and an RDS controller, operating on P Voltage (208-230V, 1-Phase, 60Hz). It details component connections, blower speed tap settings, and important notes regarding wiring, jumpers, and specific application references.

Figure 13: Typical Unit Diagram – Air Handlers with Constant Torque Motors (G Voltage – 460V, 3-Phase, 60Hz)

Description: This diagram illustrates the field wiring for units with and without circuit breakers for air handlers with constant torque motors operating on G Voltage (460V, 3-Phase, 60Hz). It includes a component key, blower speed tap settings, and notes on wiring practices, circuit variations, and jumper configurations. It covers connections for blower, transformer, relays, and thermostat signals.

Figure 14: Typical Unit Diagram – Air Handlers with Constant Torque Motors – RDS Controller (G Voltage – 460V, 3-phase, 60Hz)

Description: This diagram depicts the field wiring for units with and without circuit breakers, for air handlers with constant torque motors and an RDS controller, operating on G Voltage (460V, 3-phase, 60Hz). It details component connections, blower speed tap settings, and important notes regarding wiring, jumpers, and specific application references.

Electric Heat Wiring Diagram Cross Reference

The following table provides a cross-reference for diagrams for specific electric heat models.

Electric Heat Section ModelWiring Diagram #
ECB47-4(CB)-P538453-01
ECB47-5(CB)-P538453-01
ECB47-6(CB)-P538453-01
ECB47-8(CB)-P538454-01
ECB47-9CB-P538455-01
ECB47-12.5CB-P538456-01
ECB47-15CB-P538456-01
ECB47-20CB-P538457-01
ECB47-25CB-P538458-01
ECB47-8-Y538459-01
ECB47-10-Y538459-01
ECB47-15CB-Y538459-01
ECB47-20CB-Y538460-01
ECB47-25CB-Y538460-01
ECB47-10-G538461-01
ECB47-15-G538461-01
ECB47-20-G538461-01
ECB47-25-G538461-01
ECB47-20-J538461-01
ECB47-25-J538461-01

Replacement Electric Heater Applications

When the ECB47 electric heat kit is used as a replacement electric heater in an older, out of production air handling unit with a variable speed blower and a communicating air handler control, special steps may be required to configure the electric heat to ensure all stages of electric heat will operate. If the system does not recognize all the stages of electric heat during configuration and if you need assistance contact Technical Support.

Electric Heat Circuit Breaker/Fuse Ratings

Single Phase Circuit Breaker

Heat SizeVoltageBreaker Size
4 kW208/240V - 1 Phase30A
5 kW208/240V - 1 Phase35A
6 KW208/240V - 1 Phase40A
8 kW208/240V - 1 Phase50A
9 KW208/240V - 1 Phase60A
12.5 kW208/240V - 1 Phase30A
15 kW208/240V - 1 Phase45A
20 kW208/240V - 1 Phase35A
25 kW208/240V - 1 Phase60A

Three Phase Circuit Breaker

Heat SizeVoltageBreaker Size
15 kW208/240V - 3 Phase50A
20 kW208/240V - 3 Phase35A
25 kW208/240V - 3 Phase45A

Three Phase Fused

Heat SizeVoltageFuse Size
10 KW460V - 3 Phase(3) 20A
15 kW460V - 3 Phase(3) 25A
20 kW460V - 3 Phase(3) 35A
25 kW460V - 3 Phase(3) 40A
20 kW575V - 3 Phase(3) 25A
25 kW575V - 3 Phase(3) 35A
Models: ECB47 Series Electric Heat Sections, ECB47 Series, Electric Heat Sections, Heat Sections

File Info : application/pdf, 12 Pages, 1.41MB

PDF preview unavailable. Download the PDF instead.

508508-01a Adobe PDF Library 17.0

Related Documents

Preview Storage Box Instruction Manual
Comprehensive instruction manual for assembling a Storage Box closet system, detailing parts, hardware, and step-by-step assembly instructions.
Preview Obblighi di Pubblicazione Contributi Ricevuti - Anni 2018-2020
Dettaglio degli obblighi di pubblicazione relativi ai contributi ricevuti dalla Provincia Autonoma di Bolzano negli anni 2018, 2019 e 2020. Include informazioni su ente erogante, norma, tipologia, atto, numero e data del provvedimento, e importo lordo.
Preview 30" Electric Drop-In Range Installation Instructions
Comprehensive installation guide for a 30-inch electric drop-in range, covering safety precautions, electrical requirements, wiring, and installation steps.
Preview Bakery Cases Installation and Operation Manual: DDM Series Refrigerated Display Units
This manual provides comprehensive instructions for the installation, operation, and maintenance of the DDM series bakery cases and refrigerated display units. It includes essential safety precautions, detailed specifications, electrical requirements, defrost system explanation, and cleaning guidelines.
Preview Aberrant Behavior of Great Hornbill and Rhinoceros Hornbill in Singapore
An observational study detailing the unusual courtship feeding and nesting behaviors of a female Great Hornbill (Buceros bicornis) and a female Rhinoceros Hornbill (Buceros rhinoceros) in Singapore's Eng Neo Avenue.
Preview KAO-5 Waterproof Push Button Switch Wiring Diagrams
Detailed wiring diagrams for KAO-5 waterproof push button switches, covering single-phase 220V and three-phase 380V connections. Explains fireline (red) and zeroline (blue) wiring for stable and durable operation.
Preview FIPS 140-2 Consolidated Validation Certificate
Official FIPS 140-2 validation certificate listing cryptographic modules validated by the National Institute of Standards and Technology (NIST) and the Communications Security Establishment (CSE) of Canada. It outlines the security requirements, validation levels, and lists specific modules with their vendors and version information.
Preview LED T8 Tube Specifications and Models | AN-DG Series
Detailed specifications for AN-DG series LED T8 tubes, including power, color temperature (6500K), CRI, input voltage, dimensions, and warranty information.