PM5000 series Technical Datasheet

The PowerLogic PM5000 series power meters are the new benchmark in affordable, precision metering. The value you want, the precision you need. Compact, affordable power meters with high-end cost capabilities and basic mobile energy management.

Applications

Capable of essential cost management:

Also ideal for electrical network management:

The solution for

Markets that can benefit from a solution that includes PowerLogic PM5000 series meters:

Benefits

System integrators' benefit

Panel builders' benefit

End users' benefit

Competitive advantages

Conformity of standards

PM5000 series

The PowerLogic PM5000 power meter is the ideal fit for cost management applications. Designed for use in both energy management systems and building management systems, it provides the measurement capabilities needed to allocate energy usage, perform tenant metering and sub-billing, pinpoint energy savings, optimize equipment efficiency and utilization, and perform a high-level assessment of the power quality of the electrical network.

In a single 96 x 96 mm unit, with a graphical display (plus optional remote display), all three phases, neutral, and ground can be monitored simultaneously.

The bright, anti-glare display features large characters and powerful backlighting for easy reading even in extreme lighting conditions and viewing angles. Easy to understand menus, text in 8 selectable languages, icons and graphics create a friendly environment to learn about your electrical network. Ethernet gateway and enhanced cyber security. These are highly accurate devices with global billing certifications.

Applications

Cost management:

Cost saving opportunities become clear once you understand how and when your facility uses electricity. The PowerLogic PM5000 series meters are ideal for:

Network management:

Improving the reliability of the electrical network is key for success in any business. Monitoring values such as voltage levels, harmonics distortions, voltage unbalance, residual current, voltage sag and swell will help you to ensure proper operation and maintenance of your electrical network and equipment. PowerLogic PM5000 series meters are the perfect tool for:

Main characteristics

Easy to install

Mounts using two clips, in a standard cut-out for DIN 96 x 96 mm, no tools required. Compact meter with 72 mm (77 mm for PM5500) depth, connectable up to 690 V L-L without voltage transformers for installations compliant with category III. Optional remote display (PM5563). Ethernet gateway functionality via RS-485 port.

Easy to operate

Intuitive navigation with self-guided, language-selectable menus, six lines, four concurrent values. Two LEDs on the meter face help the user confirm normal operation: a green LED for heartbeat/communications indicator, and an amber LED for customizable alarms or energy pulse outputs. Onboard web pages (PM5500) show real-time and logged information, and verify communications.

Easy circuit breaker monitoring and control

The PM5300 provides two relay outputs (high-performance Form A type) with the capability to command most of the circuit breaker coils directly. For Digital Inputs, monitored switches can be wired directly to the meter without external power supply by using a whetting output voltage. PM5500 series have 4 status inputs (digital) and 2 digital outputs (solid state) to use for WAGES monitoring, control, and alarm annunciation.

Accurate energy measurement for precise cost allocation:

PM5100 PM5300 PM5500 PM5600 PM5700
IEC 62053-22 (Active Energy) Class 0.5S Class 0.5S Class 0.2S Class 0.2S Class 0.2S

Native multi-protocol support

The PM55/PM56/PM5700 is now easier than ever to integrate into new and existing BMS systems. With native BACnet/IP protocol support, meters can simultaneously communicate via BACnet and Modbus in applications where multiple software systems are used (building management and energy management systems).

The PM55/PM56/PM5700 series has been tested and certified in accordance with BACnet Testing Laboratories (BTL) requirements.

Direct metering of neutral current

The PM55/PM56/PM5700 has a fourth CT for measuring neutral current. In demanding IT applications, where loads are non-linear (i.e., switching power supplies on computers/servers), measuring neutral current is essential to avoid overload and resulting outages.

Power Quality analysis

The PM5000 offers Total Harmonic Distortion (THD/thd), Total Demand Distortion (TDD) measurements, and individual harmonics (odd) magnitudes and angles for voltage and current:

PM5100 PM5300 PM55/56/5700
Individual Harmonics magnitudes up to 15th magnitudes up to 31st magnitudes & angles up to 63rd

These types of power quality parameters help to identify the source of harmonics that can harm transformers, capacitors, generators, motors, and electronic equipment.

Load management

Peak demands with time stamping are provided. Predicted demand values can be used in combination with alarms for basic load shedding applications.

Alarming with time stamping

A different combination of set point driven alarms and digital alarms with 1s time stamping are available in the PM5000 family:

Set point driven alarms PM5100 PM5300 PM55/56/5700
Unary 29 29 29 or 33*
Digital 4 4 4
Boolean / Logic - 2 4 or 2
Custom defined - - 10

*Applicable in specific meter models. 2 alarms for disturbance (Sag/Swell).

Alarms can be visualized as Active (the ones that have picked up and did not drop out yet) or Historical (the ones that happened in the past). Alarms can be programmed and combined to trigger digital outputs and mechanical relays (PM5300). The PM5000 series keeps an alarm log with the active and historical alarms with date and time stamping. SMTP protocol for receiving alarm conditions via email and text. SNTP protocol for date/time network synchronization.

Load timer

A load timer can be set to count load running hours based on a minimum current withdrawal, adjustable to monitor and advise maintenance requirements on the load.

High Performance and accuracy

IEC 61557-12 Performance measuring and monitoring devices (PMD). Defines the performance expectation based on classes. It defines the allowable error in the class for real and reactive power and energy, frequency, current, voltage, power factor, voltage unbalance, voltage and current harmonics (odds), voltage THD, current THD, as well as ratings for temperature, relative humidity, altitude, start-up current, and safety. It makes compliant meters readings comparable – they will measure the same values when connected to the same load.

Legal billing compliance

MID compliance is compulsory for billing applications across Europe. In addition to billing applications, for facility managers responsible for energy cost, MID means the same level of quality as a billing meter.

PM5000 series feature selection

PM5100 PM5110 PM5310 PM5310R PM5320 PM5320R PM5330 PM5340
Installation
Fast installation, panel mount with integrated display
Fast installation, DIN rail mountable - - - - - - - -
Accuracy CL 0.5S CL 0.5S CL 0.5S CL 0.5S CL 0.5S CL 0.5S CL 0.5S CL 0.5S
Display
Backlit LCD, multilingual, bar graphs, 6 lines, 4 concurrent values
Power and energy metering
3-ph voltage, current, power, demand, energy, frequency, power factor
Multi-tariff 4 4 4 4 4 4 4 4
MID ready compliance, EN50470-1/3, Annex B & Annex D Class C
Power quality analysis
THD, thd, TDD
Harmonics, individual (odd) up to 15th 15th 31st 31st 31st 31st 31st 31st
Waveform capture & sag/swell detection
I/Os and relays
I/Os 1DO 1DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO
Relays 0 0 0 0 0 0 2 2
Analog inputs - - - - - - - -
Residual Current inputs - - - - - - - -
Alarms and control
Alarms 33 33 35 35 35 35 35 35
Set point response time, seconds 1 1 1 1 1 1 1 1
Single and multi-condition alarms
Boolean alarm logic
Memory for data logging 256KB 256KB 256KB 256KB 256KB 256KB 256KB 256KB
Communications
Serial ports with Modbus protocol 1 1 1 1 1 1 1 1
Ethernet port with Modbus TCP protocol - - 1 1 1 1 1 1
BACnet/IP protocol - -
EtherNet/IP protocol - -
DNP3.0 over Ethernet - -
Onboard web server with web pages - -
Serial to Ethernet gateway - -
Short ref. numbers PM5100 PM5110 PM5310 PM5310R PM5320 PM5320R PM5330 PM5340

NOTE: PM5310R and PM5320R must be used with Schneider Electric's "Quick Click" 3-in-1 LVCTs.

PM5000 series feature selection

PM5500 PM5560 PM5561 PM5562 PM5562MC PM5563 PM5563RD PM5570 PM5580 PM5600 PM5650 PM5660 PM5700 PM5760 PM5761
Installation
Fast installation, panel mount with integrated display - -
Fast installation, DIN rail mountable - - - - - - - - - - - - -
Accuracy CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S
Display
Backlit LCD, multilingual, bar graphs, 6 lines, 4 concurrent values -
Power and energy metering
3-ph voltage, current, power, demand, energy, frequency, power factor
Multi-tariff 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
MID ready compliance, EN50470-1/3, Annex B & Annex D Class C - - - - - - - - - - - -
Power quality analysis
THD, thd, TDD
Harmonics, individual (odd) up to 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd
Waveform capture & sag/swell detection - - - - - 8 cycles @ 128 samples/cycle - 8 cycles @ 128 samples/cycle - - - - - - -
I/Os and relays
I/Os 4DI/2DO 4DI/2DO 4DI/2DO 2DI/2DO 4DI/2DO 4DI/2DO 2DI/2DO 2DI/2DO 4DI/2DO 4DI/2DO 2DI/2DO 2DI/2DO 4DI/2DO 4DI/2DO 4DI/2DO
Relays 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Analog inputs 0 0 0 2 0 0 0 0 0 0 0 0 0 0 0
Residual Current inputs 0 0 0 0 0 0 2 2 0 0 2 2 0 0 0
Alarms and control
Alarms 52 52 52 50 52 54 54 56 52 52 52 52 52 52 52
Set point response time, seconds 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Single and multi-condition alarms
Boolean alarm logic
Memory for data logging 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB
Communications
Serial ports with Modbus protocol 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Ethernet port with Modbus TCP protocol 2g 2g 2g 2g 2g 2g 2g 2g 2g 2g 2g 2g 2g 2g 2g
BACnet/IP protocol
EtherNet/IP protocol
DNP3.0 over Ethernet
Onboard web server with web pages
Serial to Ethernet gateway
Short ref. numbers PM5500 PM5560 PM5561 PM5562 PM5562MC PM5563 PM5563RD PM5570 PM5580 PM5600 PM5650 PM5660 PM5700 PM5760 PM5761

PM5000 technical specifications

PM5100 PM5300 PM5500 PM5600 PM5700
Use on LV and MV systems
Basic metering with THD and min/max readings
Instantaneous rms values
Current
Voltage
Frequency
Real, reactive, and apparent power
True Power Factor
Displacement PF
% Unbalanced I, V L-N, V L-L
Energy values
Accumulated Active, Reactive and Apparent Energy Received/Delivered; Net and absolute; Time Counters Received/Delivered; Net and absolute; Time Counters Received/Delivered; Net and absolute; Time Counters Received/Delivered; Net and absolute; Time Counters Received/Delivered; Net and absolute; Time Counters
Demand value
Current average Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time
Active power Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time
Reactive power Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time
Apparent power Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time
Peak demand with timestamping D/T for current and powers
Demand calculation Sliding, fixed and rolling block, thermal methods
Synchronisation of the measurement window to input, communication command or internal clock
Settable Demand intervals
Demand synchronization with pulse input
Other measurements
I/O timer
Operating timer
Load timer
Alarm counters and alarm logs
Power quality measurements
THD, thd (Total Harmonic Distortion) I, VLN, VLL
TDD (Total Demand Distortion)
Individual harmonics (odds) 15th (PM5110) 31st 63rd 63rd 63rd
Neutral Current metering with ground current calculation
Waveform capture and sag/swell detection 8 cycles @ 128 samples/cycle 8 cycles @ 128 samples/cycle
Data recording
Min/max of instantaneous values, plus phase identification★
Alarms with 1s timestamping★
Data logging
Min/max log 2 fixed parameters 2 fixed parameters Up to 14 selectable parameters with configurable interval and duration (e.g. 6 parameters for 90 days at 15-minute intervals) Up to 14 selectable parameters with configurable interval and duration (e.g. 6 parameters for 90 days at 15-minute intervals) Up to 14 selectable parameters with configurable interval and duration (e.g. 6 parameters for 90 days at 15-minute intervals)
Maintenance, alarm and event logs
Customisable data logs

★Stored in non-volatile memory

PM5000 technical specifications

Inputs / Outputs / Mechanical Relays PM5100 PM5300 PM5500 PM5600 PM5700
Digital inputs 2 2 4 x (PM5560, PM5563, PM5580, PM5650) 2 x (PM5570, PM5660, PM5760) 4 x (PM5560, PM5563, PM5580, PM5650) 2 x (PM5570, PM5660, PM5760) 4 x (PM5560, PM5563, PM5580, PM5650) 2 x (PM5570, PM5660, PM5760)
Digital outputs 1 (kWh only) 2 2 2 2
Form A Relay outputs - - 2 for PM5570 2 for PM5570 2 for PM5760
Analog inputs - - - - -
Residual Current inputs - - - 2 for PM5660 2 for PM5760
Timestamp resolution in seconds 1 1 1 1 1
Whetting source 24 V DC, 8 mA 24 V DC, 8 mA 24 V DC, 8 mA 24 V DC, 8 mA 24 V DC, 8 mA
Type of measurement: True rms on three-phase (3P, 3P + N) 64 samples per cycle 64 samples per cycle 128 samples per cycle 128 samples per cycle 128 samples per cycle
IEC 61557-12 PMD/[SD|SS]/K70/0.5 PMD/[SD|SS]/K70/0.5 PMD/[SD|SS]/K70/0.2 PMD/[SD|SS]/K70/0.2 PMD/[SD|SS]/K70/0.2
Active Energy Class 0.5S as per IEC 62053-22 Class 0.5S as per IEC 62053-22 Class 0.2S as per IEC 62053-22 Class 0.2S as per IEC 62053-22 Class 0.2S as per IEC 62053-22
Reactive Energy Class 2 as per IEC 62053-23 Class 2 as per IEC 62053-23 Class 2 as per IEC 62053-23 Class 2 as per IEC 62053-23 Class 2 as per IEC 62053-23
Active Power Class 0.5 as per IEC 61557-12 Class 0.5 as per IEC 61557-12 Class 0.5 as per IEC 61557-12 Class 0.5 as per IEC 61557-12 Class 0.5 as per IEC 61557-12
Apparent Power Class 0.5 as per IEC 61557-12 ±0.15% Class 0.5 as per IEC 61557-12 ±0.15% Class 0.5 as per IEC 61557-12 ±0.1% Class 0.5 as per IEC 61557-12 ±0.1% Class 0.5 as per IEC 61557-12 ±0.1%
Measurement accuracy
Input-voltage (up to 1.0 MV AC max, with voltage transformer) Current, Phase Class 0.5 as per IEC 61557-12 ±0.1% Class 0.5 as per IEC 61557-12 ±0.1% Class 0.5 as per IEC 61557-12 ±0.1% Class 0.5 as per IEC 61557-12 ±0.1% Class 0.5 as per IEC 61557-12 ±0.1%
Input-voltage Voltage, L-N ±0.005% ±0.005% ±0.005% ±0.005% ±0.005%
Frequency ±0.005 count ±0.005 count ±0.005 count ±0.005 count ±0.005 count
Power Factor ±0.005 count ±0.005 count ±0.005 count ±0.005 count ±0.005 count
MID Directive EN50470-1, EN50470-3 Annex B and Annex D (Optional model references) Class C Annex B and Annex D (Optional model references) Class C Annex B and Annex D (Optional model references) Class C Annex B and Annex D (Optional model references) Class C Annex B and Annex D (Optional model references) Class C
Nominal Measured Voltage range 20 V L-N/35 V L-L to 400 V L-N /690 V L-L absolute range 35 V L-L to 760 V L-L 20 V L-N/20 V L-L to 400 V L-N /690 V L-L absolute range 20 V L-L to 828 V L-L 20 V L-N/20 V L-L to 400 V L-N /690 V L-L absolute range 20 V L-L to 828 V L-L 20 V L-N/20 V L-L to 400 V L-N /690 V L-L absolute range 20 V L-L to 828 V L-L 20 V L-N/20 V L-L to 400 V L-N /690 V L-L absolute range 20 V L-L to 828 V L-L
Input-current (configurable for 1 or 5 A secondary CTs)
Current, Phase 50 or 60 Hz ±5% 50 or 60 Hz ±5% 50 or 60 Hz ±10% 50 or 60 Hz ±10% 50 or 60 Hz ±10%
Withstand 5 A 5 A 5 A 5 A 5 A
Impedance Starting current: 5 mA Operating range: 50 mA to 8.5 A Starting current: 5 mA Operating range: 50 mA to 10 A Starting current: 5 mA Operating range: 50 mA to 10 A Starting current: 5 mA Operating range: 50 mA to 10 A Starting current: 5 mA Operating range: 50 mA to 10 A
Frequency nom Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ
I nom
Measured Amps with over range and Crest Factor
AC control power
Operating range 100-277 V AC L-N/415 VL-L +/-10% CAT III 300V class per IEC 61010 100-480 V AC ±10% CAT III 600V class per IEC 61010 100-480 V AC ±10% CAT III 600V class per IEC 61010 100-480 V AC ±10% CAT III 600V class per IEC 61010 100-480 V AC ±10% CAT III 600V class per IEC 61010
Burden <5 W,11 VA at 415V L-L <0.026 VA at 8.5 A <5W/16.0 VA at 480 V AC <5W/16.0 VA at 480 V AC <5W/16.0 VA at 480 V AC <5W/16.0 VA at 480 V AC
Frequency 45 to 65 Hz 50 or 60 Hz ±10% 50 or 60 Hz ±10% 50 or 60 Hz ±10% 50 or 60 Hz ±10%
AC control power
Operating range 100-277 V AC L-N/415 VL-L +/-10% CAT III 300V class per IEC 61010 100-480 V AC ±10% CAT III 600V class per IEC 61010 100-480 V AC ±10% CAT III 600V class per IEC 61010 100-480 V AC ±10% CAT III 600V class per IEC 61010 100-480 V AC ±10% CAT III 600V class per IEC 61010
Burden 4.1 W max. 4.1 W max. 4.1 W max. 4.1 W max. 4.1 W max.
Ride-through time 80 mS typical at 120V AC and maximum burden. 100 mS typical at 230 V AC and maximum burden 100 mS typical at 415 V AC and maximum burden 35 ms typical at 120 V L-N and maximum burden 129 ms typical at 230 V L-N and maximum burden 35 ms typical at 120 V L-N and maximum burden 129 ms typical at 230 V L-N and maximum burden 35 ms typical at 120 V L-N and maximum burden 129 ms typical at 230 V L-N and maximum burden 35 ms typical at 120 V L-N and maximum burden 129 ms typical at 230 V L-N and maximum burden
DC control power
Operating range 20-60 V DC ±10% CAT III Burden 4.1 W max. 20-60 V DC ±10% CAT III Burden 4.1 W max. 20-60 V DC ±10% CAT III Burden 4.1 W max. 20-60 V DC ±10% CAT III Burden 4.1 W max. 20-60 V DC ±10% CAT III Burden 4.1 W max.
Burden 4.1 W max. 4.1 W max. 4.1 W max. 4.1 W max. 4.1 W max.
Ride-through time
LV DC control power 20-60 V DC ±10% CAT III Burden 4.1 W max. 20-60 V DC ±10% CAT III Burden 4.1 W max. 20-60 V DC ±10% CAT III Burden 4.1 W max. 20-60 V DC ±10% CAT III Burden 4.1 W max. 20-60 V DC ±10% CAT III Burden 4.1 W max.

PM5000 technical specifications

Outputs PM5100 PM5300 PM5500 PM5600 PM5700
Relay
Max output frequency 0.5 Hz maximum (1 second ON/1 second OFF - min times) 0.5 Hz maximum (1 second ON/1 second OFF - min times) 0.5 Hz maximum (1 second ON/1 second OFF - min times) 0.5 Hz maximum (1 second ON/1 second OFF - min times) 0.5 Hz maximum (1 second ON/1 second OFF - min times)
Switching current 250 V AC at 8.0 Amps, 25 k cycles, resistive 30 V DC at 2.0 Amps, 75 k cycles, resistive 30 V DC at 5.0 Amps, 12.5 k cycles, resistive 30 V AC/40 V DC PM5570, PM5560, PM5561, PM5760, PM5761 30 V AC/40 V DC PM5570, PM5560, PM5561, PM5760, PM5761
Isolation 2.5 kV rms 5 kV rms 2.5 kV rms 2.5 kV rms 2.5 kV rms
Max load voltage 40 V DC 40 V DC 40 V DC 30 V AC/60 V DC max 30 V AC/60 V DC max
Max load current 20 mA 20 mA 20 mA 125 mA 125 mA
On Resistance 50 Ω max 50 Ω max 50 Ω max 8 Ω 8 Ω
Meter constant from 1 to 9,999,999 pulses per kWh from 1 to 9,999,999 pulses per kWh from 1 to 9,999,999 pulses per kWh from 1 to 9,999,999 pulses per kWh from 1 to 9,999,999 pulses per kWh
Pulse width for Digital Output 50% duty cycle 50% duty cycle 50% duty cycle 50% duty cycle 50% duty cycle
Pulse frequency for Digital Output 25 Hz max. 25 Hz max. 25 Hz max. 25 Hz max. 25 Hz max.
Leakage current 0.03 micro Amps 1 micro Amps 1 micro Amps 1 micro Amps 1 micro Amps
Optical outputs
Pulse width (LED) 2.5 kV rms 2.5 kV rms 2.5 kV rms 2.5 kV rms 2.5 kV rms
Pulse frequency 2.5 kHz. max 2.5 kHz. max 2.5 kHz. max 2.5 kHz. max 2.5 kHz. max
Meter constant from 1 to 9,999,999 pulses per kWh from 1 to 9,999,999 pulses per kWh from 1 to 9,999,999 pulses per kWh from 1 to 9,999,999 pulses per kWh from 1 to 9,999,999 pulses per kWh
Status Inputs
ON Voltage 18.5 to 36 V DC 18.5 to 36 V DC 30 V AC/60 V DC max 30 V AC/60 V DC max 30 V AC/60 V DC max
OFF Voltage 0 to 4 V DC 0 to 4 V DC 0 to 4 V DC 0 to 4 V DC 0 to 4 V DC
Input Resistance 110 Κ Ω 100 Κ Ω 100 Κ Ω 100 Κ Ω 100 Κ Ω
Maximum Frequency 2 Hz (T ON min = T OFF min = 250 ms) 25 Hz (T ON min = T OFF min = 20 ms) 25 Hz (T ON min = T OFF min = 20 ms) 25 Hz (T ON min = T OFF min = 20 ms) 25 Hz (T ON min = T OFF min = 20 ms)
Response Time 20 ms 20 ms 20 ms 20 ms 20 ms
Opto Isolation 5 kV rms 2.5 kV rms 2.5 kV rms 2.5 kV rms 2.5 kV rms
Whetting output 24 V DC/ 8 mA max 24 V DC/ 8 mA max 24 V DC/ 8 mA max 24 V DC/ 8 mA max 24 V DC/ 8 mA max
Input Burden 2mA @24V DC 2mA @24V DC 2mA @24V AC/DC 2mA @24V AC/DC 2mA @24V AC/DC
Analog inputs
Residual Current inputs 4-20 mA DC (nominal) Accuracy: 1% of full-scale reading < 20 ohm Operating voltage: 24 V DC max 4-20 mA DC (nominal) Accuracy: 1% of full-scale reading < 20 ohm Operating voltage: 24 V DC max 5 uA to 1,200 uA (nominal), 1,500 uA max (continuous) Input type: AC 45 to 65 Hz Burden: 150 ohms Default toroid: 1000 turns 5 uA to 1,200 uA (nominal), 1,500 uA max (continuous) Input type: AC 45 to 65 Hz Burden: 150 ohms Default toroid: 1000 turns 5 uA to 1,200 uA (nominal), 1,500 uA max (continuous) Input type: AC 45 to 65 Hz Burden: 150 ohms Default toroid: 1000 turns
Mechanical characteristics
Product weight 380 g 430 g 450 g 450 g 450 g
IP degree of protection (IEC 60529) IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF.
Dimensions W x H x D [protrusion from cabinet] 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm]
Mounting position Vertical Vertical Vertical Vertical Vertical
Panel thickness 6 mm maximum 6 mm maximum 6 mm maximum 6 mm maximum 6 mm maximum

PM5000 series commercial reference numbers

Comm ref numbers Description
METSEPM5100 Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 15th harmonic, no communication, 1DO
METSEPM5110 Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 15th harmonic, RS-485 Modbus, 1DO
METSEPM5111 Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 15th harmonic, RS-485 Modbus, 1DO, MID certified.
METSEPM5310 Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 31st harmonic, 256 kB, RS-485 Modbus, 2DI/2DO
METSEPM5310R Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 31st harmonic, 256 kB, RJ45 LVCT, RS-485 Modbus, 2DI/2DO
METSEPM5320 Power Meter range 72 mm depth, control power to 415 VAC, CI 0.5S, 31st harmonic, 256 kB, Ethernet, 2DI/2DO
METSEPM5320R Power Meter range 72 mm depth, control power to 415 VAC, CI 0.5S, 31st harmonic, 256 kB, RJ45 LVCT, Ethernet, 2DI/2DO
METSEPM5330 Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 31st harmonic, 256 kB, RS-485 Modbus, 2DI/2DO, 2Relay
METSEPM5331 Power Meter range 72 mm depth, control power to 415 VAC, CI 0.5S, 31st harmonic, 256 kB, RS-485 Modbus, 2DI/2DO, 2Relay, MID certified.
METSEPM5340 Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 31st harmonic, 256 kB, Ethernet, 2DI/2DO, 2Relay
METSEPM5341 Power Meter range 72 mm depth, control power to 415 VAC, CI 0.5S, 31st harmonic, 256 kB, Ethernet, 2DI/2DO, 2Relay, MID certified.
METSEPM5560 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 4DI/2DO
METSEPM5561 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, MID certified.
METSEPM5562 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, RMICAN approved, HW lockable, 4DI/2DO
METSEPM5562MC Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, RMICAN approved, factory sealed, 4DI/2DO
METSEPM5563 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, DIN mount, no display, 4DI/2DO
METSEPM5563RD Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, DIN mount, remote display, 4DI/2DO
METSEPM5570 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 2DI/2DO/2AI
METSEPM5580 Power Meter range 77 mm depth, control power 24-60 VDC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 4DI/2DO
METSEPM5650 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, waveform capture and sag/swell, 1.1 MB, Modbus and Ethernet, 2DI/2DO
METSEPM5660 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 2DI/2DO, RCM
METSEPM5661 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 2DI/2DO, RCM, MID certified.
METSEPM5760 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, waveform capture and sag/swell, 1.1 MB, Modbus and Ethernet, 2DI/2DO, RCM, MID certified.
METSEPM5761 Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, waveform capture and sag/swell, 1.1 MB, Modbus and Ethernet, 2DI/2DO, RCM, MID certified.
Residual Current Monitoring Toroids (Vigirex)
Closed Toroids, A Type
50437 TA30 - 30 mm inside diameter, Ie (A) 65, 1000 turns
50438 PA50 - 50 mm inside diameter, Ie (A) 85, 1000 turns
50439 IA80 - 80 mm inside diameter, Ie (A) 160, 1000 turns
50440 MA120 - 120 mm inside diameter, Ie (A) 250, 1000 turns
50441 SA200 - 200 mm inside diameter, Ie (A) 400, 1000 turns
50442 GA300 - 300 mm inside diameter, Ie (A) 630, 1000 turns
Accessories for Closed Toroids
56055 Magnetic ring for TA30 toroid
56056 Magnetic ring for PA50 toroid
56057 Magnetic ring for IA80 toroid
56058 Magnetic ring for MA120 toroid
Split Toroids, OA Type
50420 TOA80 - 80 mm inside diameter, Ie (A) 160, 1000 turns
50421 TOA120 - 120 mm inside diameter, Ie (A) 250, 1000 turns
56053 L1 280 x 115 mm inside diameter, Ie (A) 1600, 1000 turns
56054 L2 - 470 x 160 mm inside diameter, Ie (A) 3200, 1000 turns

PM5300R series commercial reference numbers

Comm. ref numbers Description
0.333V 3-in-1 CTs with RJ45 for PM53x0R
METSECTV25006 LVCT SolidC 3in1 RJ45 25mmCtr 60A:1/3V
METSECTV25010 LVCT SolidC 3in1 RJ45 25mmCtr 100A:1/3V
METSECTV25013 LVCT SolidC 3in1 RJ45 25mmCtr 125A:1/3V
METSECTV25016 LVCT SolidC 3in1 RJ45 25mmCtr 160A:1/3V
METSECTV35006 LVCT SolidC 3in1 RJ45 35mmCtr 60A:1/3V
METSECTV35010 LVCT SolidC 3in1 RJ45 35mmCtr 100A:1/3V
METSECTV35012 LVCT SolidC 3in1 RJ45 35mmCtr 120A:1/3V
METSECTV35013 LVCT SolidC 3in1 RJ45 35mmCtr 125A:1/3V
METSECTV35015 LVCT SolidC 3in1 RJ45 35mmCtr 150A:1/3V
METSECTV35016 LVCT SolidC 3in1 RJ45 35mmCtr 160A:1/3V
METSECTV35020 LVCT SolidC 3in1 RJ45 35mmCtr 200A:1/3V
METSECTV35025 LVCT SolidC 3in1 RJ45 35mmCtr 250A:1/3V
METSECTV45025 LVCT SolidC 3in1 RJ45 45mmCtr 250A:1/3V
METSECTV45030 LVCT SolidC 3in1 RJ45 45mmCtr 300A:1/3V
METSECTV45040 LVCT SolidC 3in1 RJ45 45mmCtr 400A:1/3V
METSECTV45050 LVCT SolidC 3in1 RJ45 45mmCtr 500A:1/3V
METSECTV45060 LVCT SolidC 3in1 RJ45 45mmCtr 600A:1/3V
METSECTV45063 LVCT SolidC 3in1 RJ45 45mmCtr 630A:1/3V
METSECTV29006 LVCT SolidC 3in1 RJ45 29mmCtr 60A:1/3V
METSECTV29010 LVCT SolidC 3in1 RJ45 29mmCtr 100A:1/3V
METSECTV29012 LVCT SolidC 3in1 RJ45 29mmCtr 120A:1/3V
METSECTV29013 LVCT SolidC 3in1 RJ45 29mmCtr 125A:1/3V
METSECTV29015 LVCT SolidC 3in1 RJ45 29mmCtr 150A:1/3V
METSECTV29016 LVCT SolidC 3in1 RJ45 29mmCtr 160A:1/3V
METSECTV29020 LVCT SolidC 3in1 RJ45 29mmCtr 200A:1/3V
METSECTV70080 LVCT SolidC 3in1 RJ45 70mmCtr 800A:1/3V
METSECTV70100 LVCT SolidC 3in1 RJ45 70mmCtr 1000A:1/3V
METSECTV70125 LVCT SolidC 3in1 RJ45 70mmCtr 1250A:1/3V
Cables
DCEPCURJX5GYM Category 5e, Patch Cord, UTP, 0.5 M, Grey
DCEPCURJ01GYM Category 5e, Patch Cord, UTP, 1 M, Grey
DCEPCURJ02GYM Category 5e, Patch Cord, UTP, 2 M, Grey
DCEPCURJ03GYM Category 5e, Patch Cord, UTP, 3M, Grey
DCEPCURJ05GYM Category 5e, Patch Cord, UTP, 5 M, Grey
DCEPCURJ10GYM Category 5e, Patch Cord, UTP, 10M, Grey
Other related products
METSEPM5RD Remote display for PM5563
METSEPM51HK Hardware kit for PM51xx
METSEPM53HK Hardware kit for PM53xx
METSEPM51_3RSK Revenue sealing kit for PM51XX & PM53XX
METSEPM55RSK Revenue sealing kit for PM55XX
METSEPM55HK Hardware kit for PM55xx
METSEPM5CAB3 Remote Display cable

See your Schneider Electric representative for complete ordering information.

PM5000 Series meter flush mounting

Diagram showing the flush mounting of the PM5000 series meters into a panel.

Diagram showing the dimensions of the PM5000 series meters.

PM5000 meter parts:

PM5500/PM5600 meter parts:

PM5100/PM5300 meter parts:

Please see the appropriate Installation Guide for accurate and complete information on the installation of this product.

PDF preview unavailable. Download the PDF instead.

PLSED310052EN (web) Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)

Related Documents

Preview Schneider Electric PowerLogic PM5560/PM5580/PM5650 Power and Energy Meter Installation Guide
This document provides installation, wiring, and safety information for the Schneider Electric PowerLogic PM5560, PM5580, and PM5650 power and energy meters. It includes details on product features, electrical specifications, mounting instructions, and wiring diagrams for various system configurations.
Preview Schneider Electric PowerLogic PM5560/PM5580/PM5650 Power and Energy Meter Installation Guide
This document provides installation instructions and technical specifications for the Schneider Electric PowerLogic PM5560, PM5580, and PM5650 power and energy meters. It covers safety precautions, dimensions, mounting, wiring, control power, terminal covers, descriptions of components and functions, basic setup, verification, and detailed specifications.
Preview Schneider Electric PowerLogic PM5500/PM5600/PM5700 User Manual
User manual for Schneider Electric's PowerLogic PM5500, PM5600, and PM5700 series power monitoring devices. This guide provides detailed instructions on installation, configuration, operation, and maintenance.
Preview PowerLogic PM5500/PM5600/PM5700 Series User Manual
User manual for the PowerLogic PM5500, PM5600, and PM5700 series power meters, providing installation, configuration, and operational guidance.
Preview Schneider Electric Meter Insights QR Code Feature Quick Start Guide
A quick start guide from Schneider Electric on using the QR code feature of PowerLogic PM5000 series meters for energy monitoring and data access, detailing steps for finding, scanning, and viewing meter data.
Preview Schneider Electric PowerLogic PM5350 Installation Guide
This document provides comprehensive installation instructions for the Schneider Electric PowerLogic PM5350 power meter. It details safety precautions, box contents, mounting procedures, wiring diagrams for various single-phase and three-phase systems, technical specifications, input/output connections, and communication capabilities.
Preview Schneider Electric Power and Energy Meters: PM, ION, and iEM Series Overview
Comprehensive overview of Schneider Electric's PowerLogic and Acti 9 energy and power quality meters, including PM2000, PM5000, PM8000, ION9000, and iEM3000 series. Features, specifications, applications, and software integration are detailed.
Preview PowerLogic ION8600 Energy and Power Quality Meter User Guide
Comprehensive user guide for the Schneider Electric PowerLogic ION8600 meter, detailing its advanced energy and power quality measurement capabilities, installation, configuration, and integration into enterprise energy management systems.