PM5000 series Technical Datasheet
The PowerLogic PM5000 series power meters are the new benchmark in affordable, precision metering. The value you want, the precision you need. Compact, affordable power meters with high-end cost capabilities and basic mobile energy management.
Applications
Capable of essential cost management:
- Sub-billing/tenant metering
- Equipment sub-billing
- Energy cost allocation
Also ideal for electrical network management:
- Track real-time power conditions
- Monitor control functions
- Provide basic power quality values
- Detect and capture voltage sag and swell events
- Monitor residual current
- Analyze equipment and network status
- BACnet/IP, EtherNet/IP, and DNP3.0 protocol support
The solution for
Markets that can benefit from a solution that includes PowerLogic PM5000 series meters:
- Buildings
- Industry
- Healthcare
- Data Center and networks
- Infrastructure
Benefits
System integrators' benefit
- Ease of integration
- Ease of setup
- Cost effectiveness
Panel builders' benefit
- Ease of installation
- Cost effectiveness
- Aesthetically pleasing
- Simplified ordering
End users' benefit
- Ease of use
- Precision metering & sub-billing
- Billing flexibility
- Comprehensive, consistent and superior performance
- Maximize uptime, eliminate faults, and enhance safety
Competitive advantages
- Easy to install and operate
- Easy for circuit breaker monitoring and control
- Data logging up to 16 parameters
- Power quality analysis
- Load management combined with alarm and timestamping
- High performance and accuracy
- Residual Current Monitoring
- Voltage sag and swell detection with waveform capture
- MID ready compliance for legal billing application
- BACnet/IP, EtherNet/IP, and DNP3.0 protocol support
Conformity of standards
- IEC 61557-12
- IEC 62053-22
- IEC 62053-24
- IEEE 802.3
- EN 50470-1
- EN 50470-3
- IEC/UL/EN 61010-1
- IEC 62052-11
- FCC part 15 Class B
- EN 55022 Class B
- ODVA certification
- ANSI C12.1-2008 (PM55xx)
- ANSI C12.20 Class 0.2 & 0.5
- Align with cyber security guidelines as per IEC 62443
PM5000 series
The PowerLogic PM5000 power meter is the ideal fit for cost management applications. Designed for use in both energy management systems and building management systems, it provides the measurement capabilities needed to allocate energy usage, perform tenant metering and sub-billing, pinpoint energy savings, optimize equipment efficiency and utilization, and perform a high-level assessment of the power quality of the electrical network.
In a single 96 x 96 mm unit, with a graphical display (plus optional remote display), all three phases, neutral, and ground can be monitored simultaneously.
The bright, anti-glare display features large characters and powerful backlighting for easy reading even in extreme lighting conditions and viewing angles. Easy to understand menus, text in 8 selectable languages, icons and graphics create a friendly environment to learn about your electrical network. Ethernet gateway and enhanced cyber security. These are highly accurate devices with global billing certifications.
Applications
Cost management:
Cost saving opportunities become clear once you understand how and when your facility uses electricity. The PowerLogic PM5000 series meters are ideal for:
- Sub-billing / tenant metering: allows a landlord, property management firm, condominium association, homeowners association, or other multi-tenant property to bill tenants for individual measured utility (electricity) usage. MID approved meters for billing applications across Europe.
- Cost allocation: allocate energy costs between different departments (HVAC, indoor and outdoor lighting, refrigeration, etc.), different parts of an industrial process, or different cost centers. Cost allocation systems can help you save money by making changes to your operation, better maintaining your equipment, taking advantage of pricing fluctuations, and managing your demand.
Network management:
Improving the reliability of the electrical network is key for success in any business. Monitoring values such as voltage levels, harmonics distortions, voltage unbalance, residual current, voltage sag and swell will help you to ensure proper operation and maintenance of your electrical network and equipment. PowerLogic PM5000 series meters are the perfect tool for:
- Basic Power Quality monitoring: power quality phenomena can cause undesirable effects such as heating in transformers, capacitors, motors, generators, and misoperation of electronic equipment and protection devices.
- Min/Max monitoring (with timestamp): understanding when electrical parameters, such as voltage, current, and power demand, reach maximum and minimum values will give you the insight to correctly maintain your electrical network and assure equipment will not be damaged.
- Alarming: alarms help you to be aware of any abnormal behavior on the electrical network in the moment it happens.
- WAGES monitoring: take advantage of the input metering on PM5000 meters to integrate measurements from third party devices such as water, air, gas, electricity, or steam meters.
- Residual current monitoring: measures leakage current flowing in TN & TT network systems.
- Voltage sags and swells: measures and captures waveform in the event of voltage sags and swells in the network.
Main characteristics
Easy to install
Mounts using two clips, in a standard cut-out for DIN 96 x 96 mm, no tools required. Compact meter with 72 mm (77 mm for PM5500) depth, connectable up to 690 V L-L without voltage transformers for installations compliant with category III. Optional remote display (PM5563). Ethernet gateway functionality via RS-485 port.
Easy to operate
Intuitive navigation with self-guided, language-selectable menus, six lines, four concurrent values. Two LEDs on the meter face help the user confirm normal operation: a green LED for heartbeat/communications indicator, and an amber LED for customizable alarms or energy pulse outputs. Onboard web pages (PM5500) show real-time and logged information, and verify communications.
Easy circuit breaker monitoring and control
The PM5300 provides two relay outputs (high-performance Form A type) with the capability to command most of the circuit breaker coils directly. For Digital Inputs, monitored switches can be wired directly to the meter without external power supply by using a whetting output voltage. PM5500 series have 4 status inputs (digital) and 2 digital outputs (solid state) to use for WAGES monitoring, control, and alarm annunciation.
Accurate energy measurement for precise cost allocation:
PM5100 | PM5300 | PM5500 | PM5600 | PM5700 | |
---|---|---|---|---|---|
IEC 62053-22 (Active Energy) | Class 0.5S | Class 0.5S | Class 0.2S | Class 0.2S | Class 0.2S |
Native multi-protocol support
The PM55/PM56/PM5700 is now easier than ever to integrate into new and existing BMS systems. With native BACnet/IP protocol support, meters can simultaneously communicate via BACnet and Modbus in applications where multiple software systems are used (building management and energy management systems).
The PM55/PM56/PM5700 series has been tested and certified in accordance with BACnet Testing Laboratories (BTL) requirements.
Direct metering of neutral current
The PM55/PM56/PM5700 has a fourth CT for measuring neutral current. In demanding IT applications, where loads are non-linear (i.e., switching power supplies on computers/servers), measuring neutral current is essential to avoid overload and resulting outages.
Power Quality analysis
The PM5000 offers Total Harmonic Distortion (THD/thd), Total Demand Distortion (TDD) measurements, and individual harmonics (odd) magnitudes and angles for voltage and current:
PM5100 | PM5300 | PM55/56/5700 | |
---|---|---|---|
Individual Harmonics | magnitudes up to 15th | magnitudes up to 31st | magnitudes & angles up to 63rd |
These types of power quality parameters help to identify the source of harmonics that can harm transformers, capacitors, generators, motors, and electronic equipment.
Load management
Peak demands with time stamping are provided. Predicted demand values can be used in combination with alarms for basic load shedding applications.
Alarming with time stamping
A different combination of set point driven alarms and digital alarms with 1s time stamping are available in the PM5000 family:
Set point driven alarms | PM5100 | PM5300 | PM55/56/5700 |
---|---|---|---|
Unary | 29 | 29 | 29 or 33* |
Digital | 4 | 4 | 4 |
Boolean / Logic | - | 2 | 4 or 2 |
Custom defined | - | - | 10 |
*Applicable in specific meter models. 2 alarms for disturbance (Sag/Swell).
Alarms can be visualized as Active (the ones that have picked up and did not drop out yet) or Historical (the ones that happened in the past). Alarms can be programmed and combined to trigger digital outputs and mechanical relays (PM5300). The PM5000 series keeps an alarm log with the active and historical alarms with date and time stamping. SMTP protocol for receiving alarm conditions via email and text. SNTP protocol for date/time network synchronization.
Load timer
A load timer can be set to count load running hours based on a minimum current withdrawal, adjustable to monitor and advise maintenance requirements on the load.
High Performance and accuracy
IEC 61557-12 Performance measuring and monitoring devices (PMD). Defines the performance expectation based on classes. It defines the allowable error in the class for real and reactive power and energy, frequency, current, voltage, power factor, voltage unbalance, voltage and current harmonics (odds), voltage THD, current THD, as well as ratings for temperature, relative humidity, altitude, start-up current, and safety. It makes compliant meters readings comparable – they will measure the same values when connected to the same load.
- Meets IEC 61557-12 PMD/[SD|SS]/K70/0.5 for PM5100 and PM5300
- Meets IEC 61557-12 PMD/[SD|SS]/K70/0.2 for PM5500
Legal billing compliance
MID compliance is compulsory for billing applications across Europe. In addition to billing applications, for facility managers responsible for energy cost, MID means the same level of quality as a billing meter.
PM5000 series feature selection
PM5100 | PM5110 | PM5310 | PM5310R | PM5320 | PM5320R | PM5330 | PM5340 | |
---|---|---|---|---|---|---|---|---|
Installation | ||||||||
Fast installation, panel mount with integrated display | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Fast installation, DIN rail mountable | - | - | - | - | - | - | - | - |
Accuracy | CL 0.5S | CL 0.5S | CL 0.5S | CL 0.5S | CL 0.5S | CL 0.5S | CL 0.5S | CL 0.5S |
Display | ||||||||
Backlit LCD, multilingual, bar graphs, 6 lines, 4 concurrent values | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Power and energy metering | ||||||||
3-ph voltage, current, power, demand, energy, frequency, power factor | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Multi-tariff | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 |
MID ready compliance, EN50470-1/3, Annex B & Annex D Class C | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Power quality analysis | ||||||||
THD, thd, TDD | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Harmonics, individual (odd) up to | 15th | 15th | 31st | 31st | 31st | 31st | 31st | 31st |
Waveform capture & sag/swell detection | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
I/Os and relays | ||||||||
I/Os | 1DO | 1DO | 2DI/2DO | 2DI/2DO | 2DI/2DO | 2DI/2DO | 2DI/2DO | 2DI/2DO |
Relays | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 2 |
Analog inputs | - | - | - | - | - | - | - | - |
Residual Current inputs | - | - | - | - | - | - | - | - |
Alarms and control | ||||||||
Alarms | 33 | 33 | 35 | 35 | 35 | 35 | 35 | 35 |
Set point response time, seconds | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Single and multi-condition alarms | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Boolean alarm logic | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Memory for data logging | 256KB | 256KB | 256KB | 256KB | 256KB | 256KB | 256KB | 256KB |
Communications | ||||||||
Serial ports with Modbus protocol | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Ethernet port with Modbus TCP protocol | - | - | 1 | 1 | 1 | 1 | 1 | 1 |
BACnet/IP protocol | - | - | ■ | ■ | ■ | ■ | ■ | ■ |
EtherNet/IP protocol | - | - | ■ | ■ | ■ | ■ | ■ | ■ |
DNP3.0 over Ethernet | - | - | ■ | ■ | ■ | ■ | ■ | ■ |
Onboard web server with web pages | - | - | ■ | ■ | ■ | ■ | ■ | ■ |
Serial to Ethernet gateway | - | - | ■ | ■ | ■ | ■ | ■ | ■ |
Short ref. numbers | PM5100 | PM5110 | PM5310 | PM5310R | PM5320 | PM5320R | PM5330 | PM5340 |
NOTE: PM5310R and PM5320R must be used with Schneider Electric's "Quick Click" 3-in-1 LVCTs.
PM5000 series feature selection
PM5500 | PM5560 | PM5561 | PM5562 | PM5562MC | PM5563 | PM5563RD | PM5570 | PM5580 | PM5600 | PM5650 | PM5660 | PM5700 | PM5760 | PM5761 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Installation | |||||||||||||||
Fast installation, panel mount with integrated display | ■ | - | - | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Fast installation, DIN rail mountable | - | ■ | ■ | - | - | - | - | - | - | - | - | - | - | - | - |
Accuracy | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S | CL 0.2S |
Display | |||||||||||||||
Backlit LCD, multilingual, bar graphs, 6 lines, 4 concurrent values | ■ | - | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Power and energy metering | |||||||||||||||
3-ph voltage, current, power, demand, energy, frequency, power factor | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Multi-tariff | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 |
MID ready compliance, EN50470-1/3, Annex B & Annex D Class C | ■ | - | - | - | - | - | - | - | - | ■ | - | ■ | - | - | - |
Power quality analysis | |||||||||||||||
THD, thd, TDD | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Harmonics, individual (odd) up to 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd | 63rd |
Waveform capture & sag/swell detection | - | - | - | - | - | 8 cycles @ 128 samples/cycle | - | 8 cycles @ 128 samples/cycle | - | - | - | - | - | - | - |
I/Os and relays | |||||||||||||||
I/Os | 4DI/2DO | 4DI/2DO | 4DI/2DO | 2DI/2DO | 4DI/2DO | 4DI/2DO | 2DI/2DO | 2DI/2DO | 4DI/2DO | 4DI/2DO | 2DI/2DO | 2DI/2DO | 4DI/2DO | 4DI/2DO | 4DI/2DO |
Relays | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Analog inputs | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Residual Current inputs | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 2 | 0 | 0 | 2 | 2 | 0 | 0 | 0 |
Alarms and control | |||||||||||||||
Alarms | 52 | 52 | 52 | 50 | 52 | 54 | 54 | 56 | 52 | 52 | 52 | 52 | 52 | 52 | 52 |
Set point response time, seconds | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Single and multi-condition alarms | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Boolean alarm logic | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Memory for data logging | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB | 1.1 MB |
Communications | |||||||||||||||
Serial ports with Modbus protocol | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Ethernet port with Modbus TCP protocol | 2g | 2g | 2g | 2g | 2g | 2g | 2g | 2g | 2g | 2g | 2g | 2g | 2g | 2g | 2g |
BACnet/IP protocol | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
EtherNet/IP protocol | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
DNP3.0 over Ethernet | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Onboard web server with web pages | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Serial to Ethernet gateway | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ |
Short ref. numbers | PM5500 | PM5560 | PM5561 | PM5562 | PM5562MC | PM5563 | PM5563RD | PM5570 | PM5580 | PM5600 | PM5650 | PM5660 | PM5700 | PM5760 | PM5761 |
PM5000 technical specifications
PM5100 | PM5300 | PM5500 | PM5600 | PM5700 | |
---|---|---|---|---|---|
Use on LV and MV systems | ■ | ■ | ■ | ■ | ■ |
Basic metering with THD and min/max readings | ■ | ■ | ■ | ■ | ■ |
Instantaneous rms values | |||||
Current | |||||
Voltage | |||||
Frequency | |||||
Real, reactive, and apparent power | |||||
True Power Factor | |||||
Displacement PF | |||||
% Unbalanced I, V L-N, V L-L | ■ | ■ | ■ | ■ | ■ |
Energy values | |||||
Accumulated Active, Reactive and Apparent Energy | Received/Delivered; Net and absolute; Time Counters | Received/Delivered; Net and absolute; Time Counters | Received/Delivered; Net and absolute; Time Counters | Received/Delivered; Net and absolute; Time Counters | Received/Delivered; Net and absolute; Time Counters |
Demand value | |||||
Current average | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time |
Active power | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time |
Reactive power | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time |
Apparent power | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time | Present, Last, Predicted, Peak, and Peak Date Time |
Peak demand with timestamping D/T for current and powers | ■ | ■ | ■ | ■ | ■ |
Demand calculation Sliding, fixed and rolling block, thermal methods | ■ | ■ | ■ | ■ | ■ |
Synchronisation of the measurement window to input, communication command or internal clock | ■ | ■ | ■ | ■ | ■ |
Settable Demand intervals | ■ | ■ | ■ | ■ | ■ |
Demand synchronization with pulse input | ■ | ■ | ■ | ■ | ■ |
Other measurements | |||||
I/O timer | ■ | ■ | ■ | ■ | ■ |
Operating timer | ■ | ■ | ■ | ■ | ■ |
Load timer | ■ | ■ | ■ | ■ | ■ |
Alarm counters and alarm logs | ■ | ■ | ■ | ■ | ■ |
Power quality measurements | |||||
THD, thd (Total Harmonic Distortion) I, VLN, VLL | ■ | ■ | ■ | ■ | ■ |
TDD (Total Demand Distortion) | ■ | ■ | ■ | ■ | ■ |
Individual harmonics (odds) | 15th (PM5110) | 31st | 63rd | 63rd | 63rd |
Neutral Current metering with ground current calculation | ■ | ■ | ■ | ■ | ■ |
Waveform capture and sag/swell detection | ■ | ■ | ■ | 8 cycles @ 128 samples/cycle | 8 cycles @ 128 samples/cycle |
Data recording | |||||
Min/max of instantaneous values, plus phase identification★ | ■ | ■ | ■ | ■ | ■ |
Alarms with 1s timestamping★ | ■ | ■ | ■ | ■ | ■ |
Data logging | |||||
Min/max log | 2 fixed parameters | 2 fixed parameters | Up to 14 selectable parameters with configurable interval and duration (e.g. 6 parameters for 90 days at 15-minute intervals) | Up to 14 selectable parameters with configurable interval and duration (e.g. 6 parameters for 90 days at 15-minute intervals) | Up to 14 selectable parameters with configurable interval and duration (e.g. 6 parameters for 90 days at 15-minute intervals) |
Maintenance, alarm and event logs | ■ | ■ | ■ | ■ | ■ |
Customisable data logs | ■ | ■ | ■ | ■ | ■ |
★Stored in non-volatile memory
PM5000 technical specifications
Inputs / Outputs / Mechanical Relays | PM5100 | PM5300 | PM5500 | PM5600 | PM5700 | |
---|---|---|---|---|---|---|
Digital inputs | 2 | 2 | 4 x (PM5560, PM5563, PM5580, PM5650) 2 x (PM5570, PM5660, PM5760) | 4 x (PM5560, PM5563, PM5580, PM5650) 2 x (PM5570, PM5660, PM5760) | 4 x (PM5560, PM5563, PM5580, PM5650) 2 x (PM5570, PM5660, PM5760) | |
Digital outputs | 1 (kWh only) | 2 | 2 | 2 | 2 | |
Form A Relay outputs | - | - | 2 for PM5570 | 2 for PM5570 | 2 for PM5760 | |
Analog inputs | - | - | - | - | - | |
Residual Current inputs | - | - | - | 2 for PM5660 | 2 for PM5760 | |
Timestamp resolution in seconds | 1 | 1 | 1 | 1 | 1 | |
Whetting source | 24 V DC, 8 mA | 24 V DC, 8 mA | 24 V DC, 8 mA | 24 V DC, 8 mA | 24 V DC, 8 mA | |
Type of measurement: True rms on three-phase (3P, 3P + N) | 64 samples per cycle | 64 samples per cycle | 128 samples per cycle | 128 samples per cycle | 128 samples per cycle | |
IEC 61557-12 | PMD/[SD|SS]/K70/0.5 | PMD/[SD|SS]/K70/0.5 | PMD/[SD|SS]/K70/0.2 | PMD/[SD|SS]/K70/0.2 | PMD/[SD|SS]/K70/0.2 | |
Active Energy | Class 0.5S as per IEC 62053-22 | Class 0.5S as per IEC 62053-22 | Class 0.2S as per IEC 62053-22 | Class 0.2S as per IEC 62053-22 | Class 0.2S as per IEC 62053-22 | |
Reactive Energy | Class 2 as per IEC 62053-23 | Class 2 as per IEC 62053-23 | Class 2 as per IEC 62053-23 | Class 2 as per IEC 62053-23 | Class 2 as per IEC 62053-23 | |
Active Power | Class 0.5 as per IEC 61557-12 | Class 0.5 as per IEC 61557-12 | Class 0.5 as per IEC 61557-12 | Class 0.5 as per IEC 61557-12 | Class 0.5 as per IEC 61557-12 | |
Apparent Power | Class 0.5 as per IEC 61557-12 ±0.15% | Class 0.5 as per IEC 61557-12 ±0.15% | Class 0.5 as per IEC 61557-12 ±0.1% | Class 0.5 as per IEC 61557-12 ±0.1% | Class 0.5 as per IEC 61557-12 ±0.1% | |
Measurement accuracy | ||||||
Input-voltage (up to 1.0 MV AC max, with voltage transformer) | Current, Phase | Class 0.5 as per IEC 61557-12 ±0.1% | Class 0.5 as per IEC 61557-12 ±0.1% | Class 0.5 as per IEC 61557-12 ±0.1% | Class 0.5 as per IEC 61557-12 ±0.1% | Class 0.5 as per IEC 61557-12 ±0.1% |
Input-voltage | Voltage, L-N | ±0.005% | ±0.005% | ±0.005% | ±0.005% | ±0.005% |
Frequency | ±0.005 count | ±0.005 count | ±0.005 count | ±0.005 count | ±0.005 count | |
Power Factor | ±0.005 count | ±0.005 count | ±0.005 count | ±0.005 count | ±0.005 count | |
MID Directive EN50470-1, EN50470-3 | Annex B and Annex D (Optional model references) Class C | Annex B and Annex D (Optional model references) Class C | Annex B and Annex D (Optional model references) Class C | Annex B and Annex D (Optional model references) Class C | Annex B and Annex D (Optional model references) Class C | |
Nominal Measured Voltage range | 20 V L-N/35 V L-L to 400 V L-N /690 V L-L absolute range 35 V L-L to 760 V L-L | 20 V L-N/20 V L-L to 400 V L-N /690 V L-L absolute range 20 V L-L to 828 V L-L | 20 V L-N/20 V L-L to 400 V L-N /690 V L-L absolute range 20 V L-L to 828 V L-L | 20 V L-N/20 V L-L to 400 V L-N /690 V L-L absolute range 20 V L-L to 828 V L-L | 20 V L-N/20 V L-L to 400 V L-N /690 V L-L absolute range 20 V L-L to 828 V L-L | |
Input-current (configurable for 1 or 5 A secondary CTs) | ||||||
Current, Phase | 50 or 60 Hz ±5% | 50 or 60 Hz ±5% | 50 or 60 Hz ±10% | 50 or 60 Hz ±10% | 50 or 60 Hz ±10% | |
Withstand | 5 A | 5 A | 5 A | 5 A | 5 A | |
Impedance | Starting current: 5 mA Operating range: 50 mA to 8.5 A | Starting current: 5 mA Operating range: 50 mA to 10 A | Starting current: 5 mA Operating range: 50 mA to 10 A | Starting current: 5 mA Operating range: 50 mA to 10 A | Starting current: 5 mA Operating range: 50 mA to 10 A | |
Frequency nom | Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ | Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ | Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ | Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ | Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A < 0.3 MΩ | |
I nom | ||||||
Measured Amps with over range and Crest Factor | ||||||
AC control power | ||||||
Operating range | 100-277 V AC L-N/415 VL-L +/-10% CAT III 300V class per IEC 61010 | 100-480 V AC ±10% CAT III 600V class per IEC 61010 | 100-480 V AC ±10% CAT III 600V class per IEC 61010 | 100-480 V AC ±10% CAT III 600V class per IEC 61010 | 100-480 V AC ±10% CAT III 600V class per IEC 61010 | |
Burden | <5 W,11 VA at 415V L-L <0.026 VA at 8.5 A | <5W/16.0 VA at 480 V AC | <5W/16.0 VA at 480 V AC | <5W/16.0 VA at 480 V AC | <5W/16.0 VA at 480 V AC | |
Frequency | 45 to 65 Hz | 50 or 60 Hz ±10% | 50 or 60 Hz ±10% | 50 or 60 Hz ±10% | 50 or 60 Hz ±10% | |
AC control power | ||||||
Operating range | 100-277 V AC L-N/415 VL-L +/-10% CAT III 300V class per IEC 61010 | 100-480 V AC ±10% CAT III 600V class per IEC 61010 | 100-480 V AC ±10% CAT III 600V class per IEC 61010 | 100-480 V AC ±10% CAT III 600V class per IEC 61010 | 100-480 V AC ±10% CAT III 600V class per IEC 61010 | |
Burden | 4.1 W max. | 4.1 W max. | 4.1 W max. | 4.1 W max. | 4.1 W max. | |
Ride-through time | 80 mS typical at 120V AC and maximum burden. 100 mS typical at 230 V AC and maximum burden 100 mS typical at 415 V AC and maximum burden | 35 ms typical at 120 V L-N and maximum burden 129 ms typical at 230 V L-N and maximum burden | 35 ms typical at 120 V L-N and maximum burden 129 ms typical at 230 V L-N and maximum burden | 35 ms typical at 120 V L-N and maximum burden 129 ms typical at 230 V L-N and maximum burden | 35 ms typical at 120 V L-N and maximum burden 129 ms typical at 230 V L-N and maximum burden | |
DC control power | ||||||
Operating range | 20-60 V DC ±10% CAT III Burden 4.1 W max. | 20-60 V DC ±10% CAT III Burden 4.1 W max. | 20-60 V DC ±10% CAT III Burden 4.1 W max. | 20-60 V DC ±10% CAT III Burden 4.1 W max. | 20-60 V DC ±10% CAT III Burden 4.1 W max. | |
Burden | 4.1 W max. | 4.1 W max. | 4.1 W max. | 4.1 W max. | 4.1 W max. | |
Ride-through time | ||||||
LV DC control power | 20-60 V DC ±10% CAT III Burden 4.1 W max. | 20-60 V DC ±10% CAT III Burden 4.1 W max. | 20-60 V DC ±10% CAT III Burden 4.1 W max. | 20-60 V DC ±10% CAT III Burden 4.1 W max. | 20-60 V DC ±10% CAT III Burden 4.1 W max. |
PM5000 technical specifications
Outputs | PM5100 | PM5300 | PM5500 | PM5600 | PM5700 |
---|---|---|---|---|---|
Relay | |||||
Max output frequency | 0.5 Hz maximum (1 second ON/1 second OFF - min times) | 0.5 Hz maximum (1 second ON/1 second OFF - min times) | 0.5 Hz maximum (1 second ON/1 second OFF - min times) | 0.5 Hz maximum (1 second ON/1 second OFF - min times) | 0.5 Hz maximum (1 second ON/1 second OFF - min times) |
Switching current | 250 V AC at 8.0 Amps, 25 k cycles, resistive | 30 V DC at 2.0 Amps, 75 k cycles, resistive | 30 V DC at 5.0 Amps, 12.5 k cycles, resistive | 30 V AC/40 V DC PM5570, PM5560, PM5561, PM5760, PM5761 | 30 V AC/40 V DC PM5570, PM5560, PM5561, PM5760, PM5761 |
Isolation | 2.5 kV rms | 5 kV rms | 2.5 kV rms | 2.5 kV rms | 2.5 kV rms |
Max load voltage | 40 V DC | 40 V DC | 40 V DC | 30 V AC/60 V DC max | 30 V AC/60 V DC max |
Max load current | 20 mA | 20 mA | 20 mA | 125 mA | 125 mA |
On Resistance | 50 Ω max | 50 Ω max | 50 Ω max | 8 Ω | 8 Ω |
Meter constant | from 1 to 9,999,999 pulses per kWh | from 1 to 9,999,999 pulses per kWh | from 1 to 9,999,999 pulses per kWh | from 1 to 9,999,999 pulses per kWh | from 1 to 9,999,999 pulses per kWh |
Pulse width for Digital Output | 50% duty cycle | 50% duty cycle | 50% duty cycle | 50% duty cycle | 50% duty cycle |
Pulse frequency for Digital Output | 25 Hz max. | 25 Hz max. | 25 Hz max. | 25 Hz max. | 25 Hz max. |
Leakage current | 0.03 micro Amps | 1 micro Amps | 1 micro Amps | 1 micro Amps | 1 micro Amps |
Optical outputs | |||||
Pulse width (LED) | 2.5 kV rms | 2.5 kV rms | 2.5 kV rms | 2.5 kV rms | 2.5 kV rms |
Pulse frequency | 2.5 kHz. max | 2.5 kHz. max | 2.5 kHz. max | 2.5 kHz. max | 2.5 kHz. max |
Meter constant | from 1 to 9,999,999 pulses per kWh | from 1 to 9,999,999 pulses per kWh | from 1 to 9,999,999 pulses per kWh | from 1 to 9,999,999 pulses per kWh | from 1 to 9,999,999 pulses per kWh |
Status Inputs | |||||
ON Voltage | 18.5 to 36 V DC | 18.5 to 36 V DC | 30 V AC/60 V DC max | 30 V AC/60 V DC max | 30 V AC/60 V DC max |
OFF Voltage | 0 to 4 V DC | 0 to 4 V DC | 0 to 4 V DC | 0 to 4 V DC | 0 to 4 V DC |
Input Resistance | 110 Κ Ω | 100 Κ Ω | 100 Κ Ω | 100 Κ Ω | 100 Κ Ω |
Maximum Frequency | 2 Hz (T ON min = T OFF min = 250 ms) | 25 Hz (T ON min = T OFF min = 20 ms) | 25 Hz (T ON min = T OFF min = 20 ms) | 25 Hz (T ON min = T OFF min = 20 ms) | 25 Hz (T ON min = T OFF min = 20 ms) |
Response Time | 20 ms | 20 ms | 20 ms | 20 ms | 20 ms |
Opto Isolation | 5 kV rms | 2.5 kV rms | 2.5 kV rms | 2.5 kV rms | 2.5 kV rms |
Whetting output | 24 V DC/ 8 mA max | 24 V DC/ 8 mA max | 24 V DC/ 8 mA max | 24 V DC/ 8 mA max | 24 V DC/ 8 mA max |
Input Burden | 2mA @24V DC | 2mA @24V DC | 2mA @24V AC/DC | 2mA @24V AC/DC | 2mA @24V AC/DC |
Analog inputs | |||||
Residual Current inputs | 4-20 mA DC (nominal) Accuracy: 1% of full-scale reading < 20 ohm Operating voltage: 24 V DC max | 4-20 mA DC (nominal) Accuracy: 1% of full-scale reading < 20 ohm Operating voltage: 24 V DC max | 5 uA to 1,200 uA (nominal), 1,500 uA max (continuous) Input type: AC 45 to 65 Hz Burden: 150 ohms Default toroid: 1000 turns | 5 uA to 1,200 uA (nominal), 1,500 uA max (continuous) Input type: AC 45 to 65 Hz Burden: 150 ohms Default toroid: 1000 turns | 5 uA to 1,200 uA (nominal), 1,500 uA max (continuous) Input type: AC 45 to 65 Hz Burden: 150 ohms Default toroid: 1000 turns |
Mechanical characteristics | |||||
Product weight | 380 g | 430 g | 450 g | 450 g | 450 g |
IP degree of protection (IEC 60529) | IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. | IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. | IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. | IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. | IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF. |
Dimensions W x H x D [protrusion from cabinet] | 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] | 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] | 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] | 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] | 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] |
Mounting position | Vertical | Vertical | Vertical | Vertical | Vertical |
Panel thickness | 6 mm maximum | 6 mm maximum | 6 mm maximum | 6 mm maximum | 6 mm maximum |
PM5000 series commercial reference numbers
Comm ref numbers | Description | ||||
---|---|---|---|---|---|
METSEPM5100 | Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 15th harmonic, no communication, 1DO | ||||
METSEPM5110 | Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 15th harmonic, RS-485 Modbus, 1DO | ||||
METSEPM5111 | Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 15th harmonic, RS-485 Modbus, 1DO, MID certified. | ||||
METSEPM5310 | Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 31st harmonic, 256 kB, RS-485 Modbus, 2DI/2DO | ||||
METSEPM5310R | Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 31st harmonic, 256 kB, RJ45 LVCT, RS-485 Modbus, 2DI/2DO | ||||
METSEPM5320 | Power Meter range 72 mm depth, control power to 415 VAC, CI 0.5S, 31st harmonic, 256 kB, Ethernet, 2DI/2DO | ||||
METSEPM5320R | Power Meter range 72 mm depth, control power to 415 VAC, CI 0.5S, 31st harmonic, 256 kB, RJ45 LVCT, Ethernet, 2DI/2DO | ||||
METSEPM5330 | Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 31st harmonic, 256 kB, RS-485 Modbus, 2DI/2DO, 2Relay | ||||
METSEPM5331 | Power Meter range 72 mm depth, control power to 415 VAC, CI 0.5S, 31st harmonic, 256 kB, RS-485 Modbus, 2DI/2DO, 2Relay, MID certified. | ||||
METSEPM5340 | Power Meter range 72 mm depth, control power to 415 V AC, CI 0.5S, 31st harmonic, 256 kB, Ethernet, 2DI/2DO, 2Relay | ||||
METSEPM5341 | Power Meter range 72 mm depth, control power to 415 VAC, CI 0.5S, 31st harmonic, 256 kB, Ethernet, 2DI/2DO, 2Relay, MID certified. | ||||
METSEPM5560 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 4DI/2DO | ||||
METSEPM5561 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, MID certified. | ||||
METSEPM5562 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, RMICAN approved, HW lockable, 4DI/2DO | ||||
METSEPM5562MC | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, RMICAN approved, factory sealed, 4DI/2DO | ||||
METSEPM5563 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, DIN mount, no display, 4DI/2DO | ||||
METSEPM5563RD | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, DIN mount, remote display, 4DI/2DO | ||||
METSEPM5570 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 2DI/2DO/2AI | ||||
METSEPM5580 | Power Meter range 77 mm depth, control power 24-60 VDC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 4DI/2DO | ||||
METSEPM5650 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, waveform capture and sag/swell, 1.1 MB, Modbus and Ethernet, 2DI/2DO | ||||
METSEPM5660 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 2DI/2DO, RCM | ||||
METSEPM5661 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 2DI/2DO, RCM, MID certified. | ||||
METSEPM5760 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, waveform capture and sag/swell, 1.1 MB, Modbus and Ethernet, 2DI/2DO, RCM, MID certified. | ||||
METSEPM5761 | Power Meter range 77 mm depth, control power to 480 V AC, CI 0.2S, 63rd harmonic, waveform capture and sag/swell, 1.1 MB, Modbus and Ethernet, 2DI/2DO, RCM, MID certified. | ||||
Residual Current Monitoring Toroids (Vigirex) | |||||
Closed Toroids, A Type | |||||
50437 | TA30 - 30 mm inside diameter, Ie (A) 65, 1000 turns | ||||
50438 | PA50 - 50 mm inside diameter, Ie (A) 85, 1000 turns | ||||
50439 | IA80 - 80 mm inside diameter, Ie (A) 160, 1000 turns | ||||
50440 | MA120 - 120 mm inside diameter, Ie (A) 250, 1000 turns | ||||
50441 | SA200 - 200 mm inside diameter, Ie (A) 400, 1000 turns | ||||
50442 | GA300 - 300 mm inside diameter, Ie (A) 630, 1000 turns | ||||
Accessories for Closed Toroids | |||||
56055 | Magnetic ring for TA30 toroid | ||||
56056 | Magnetic ring for PA50 toroid | ||||
56057 | Magnetic ring for IA80 toroid | ||||
56058 | Magnetic ring for MA120 toroid | ||||
Split Toroids, OA Type | |||||
50420 | TOA80 - 80 mm inside diameter, Ie (A) 160, 1000 turns | ||||
50421 | TOA120 - 120 mm inside diameter, Ie (A) 250, 1000 turns | ||||
56053 | L1 280 x 115 mm inside diameter, Ie (A) 1600, 1000 turns | ||||
56054 | L2 - 470 x 160 mm inside diameter, Ie (A) 3200, 1000 turns |
PM5300R series commercial reference numbers
Comm. ref numbers | Description | ||||
---|---|---|---|---|---|
0.333V 3-in-1 CTs with RJ45 for PM53x0R | |||||
METSECTV25006 | LVCT SolidC 3in1 RJ45 25mmCtr 60A:1/3V | ||||
METSECTV25010 | LVCT SolidC 3in1 RJ45 25mmCtr 100A:1/3V | ||||
METSECTV25013 | LVCT SolidC 3in1 RJ45 25mmCtr 125A:1/3V | ||||
METSECTV25016 | LVCT SolidC 3in1 RJ45 25mmCtr 160A:1/3V | ||||
METSECTV35006 | LVCT SolidC 3in1 RJ45 35mmCtr 60A:1/3V | ||||
METSECTV35010 | LVCT SolidC 3in1 RJ45 35mmCtr 100A:1/3V | ||||
METSECTV35012 | LVCT SolidC 3in1 RJ45 35mmCtr 120A:1/3V | ||||
METSECTV35013 | LVCT SolidC 3in1 RJ45 35mmCtr 125A:1/3V | ||||
METSECTV35015 | LVCT SolidC 3in1 RJ45 35mmCtr 150A:1/3V | ||||
METSECTV35016 | LVCT SolidC 3in1 RJ45 35mmCtr 160A:1/3V | ||||
METSECTV35020 | LVCT SolidC 3in1 RJ45 35mmCtr 200A:1/3V | ||||
METSECTV35025 | LVCT SolidC 3in1 RJ45 35mmCtr 250A:1/3V | ||||
METSECTV45025 | LVCT SolidC 3in1 RJ45 45mmCtr 250A:1/3V | ||||
METSECTV45030 | LVCT SolidC 3in1 RJ45 45mmCtr 300A:1/3V | ||||
METSECTV45040 | LVCT SolidC 3in1 RJ45 45mmCtr 400A:1/3V | ||||
METSECTV45050 | LVCT SolidC 3in1 RJ45 45mmCtr 500A:1/3V | ||||
METSECTV45060 | LVCT SolidC 3in1 RJ45 45mmCtr 600A:1/3V | ||||
METSECTV45063 | LVCT SolidC 3in1 RJ45 45mmCtr 630A:1/3V | ||||
METSECTV29006 | LVCT SolidC 3in1 RJ45 29mmCtr 60A:1/3V | ||||
METSECTV29010 | LVCT SolidC 3in1 RJ45 29mmCtr 100A:1/3V | ||||
METSECTV29012 | LVCT SolidC 3in1 RJ45 29mmCtr 120A:1/3V | ||||
METSECTV29013 | LVCT SolidC 3in1 RJ45 29mmCtr 125A:1/3V | ||||
METSECTV29015 | LVCT SolidC 3in1 RJ45 29mmCtr 150A:1/3V | ||||
METSECTV29016 | LVCT SolidC 3in1 RJ45 29mmCtr 160A:1/3V | ||||
METSECTV29020 | LVCT SolidC 3in1 RJ45 29mmCtr 200A:1/3V | ||||
METSECTV70080 | LVCT SolidC 3in1 RJ45 70mmCtr 800A:1/3V | ||||
METSECTV70100 | LVCT SolidC 3in1 RJ45 70mmCtr 1000A:1/3V | ||||
METSECTV70125 | LVCT SolidC 3in1 RJ45 70mmCtr 1250A:1/3V | ||||
Cables | |||||
DCEPCURJX5GYM | Category 5e, Patch Cord, UTP, 0.5 M, Grey | ||||
DCEPCURJ01GYM | Category 5e, Patch Cord, UTP, 1 M, Grey | ||||
DCEPCURJ02GYM | Category 5e, Patch Cord, UTP, 2 M, Grey | ||||
DCEPCURJ03GYM | Category 5e, Patch Cord, UTP, 3M, Grey | ||||
DCEPCURJ05GYM | Category 5e, Patch Cord, UTP, 5 M, Grey | ||||
DCEPCURJ10GYM | Category 5e, Patch Cord, UTP, 10M, Grey | ||||
Other related products | |||||
METSEPM5RD | Remote display for PM5563 | ||||
METSEPM51HK | Hardware kit for PM51xx | ||||
METSEPM53HK | Hardware kit for PM53xx | ||||
METSEPM51_3RSK | Revenue sealing kit for PM51XX & PM53XX | ||||
METSEPM55RSK | Revenue sealing kit for PM55XX | ||||
METSEPM55HK | Hardware kit for PM55xx | ||||
METSEPM5CAB3 | Remote Display cable |
See your Schneider Electric representative for complete ordering information.
PM5000 Series meter flush mounting
Diagram showing the flush mounting of the PM5000 series meters into a panel.
Diagram showing the dimensions of the PM5000 series meters.
PM5000 meter parts:
- A: Menu selection buttons
- B: LED indicators
- C: Navigation or menu selections
- D: Maintenance and alarm notification area
PM5500/PM5600 meter parts:
- E: Voltage inputs
- F: RS-485 comms
- G: Digital inputs
- H: Current inputs
- I: Digital outputs
- J: Ethernet ports
- K: Control power
PM5100/PM5300 meter parts:
- E: Relay output (PM5300 only)
- F: Voltage inputs
- G: Control power
- H: Current inputs
- I: Status inputs/digital outputs
- J: Communications port: Ethernet (PM5300 only) or RS-485
Please see the appropriate Installation Guide for accurate and complete information on the installation of this product.