This document provides installation instructions for the Schneider Electric PowerLogic PM5350 power meter. For information on basic meter setup, refer to the PM5350 User Guide, available for download from www.se.com. For installation in multi-circuit applications, consult the PM5350 Series Multi-Circuit Installation Guide (part number EAV25860).
For California residents: The following warnings are provided in English, French, and Spanish, as required by California law regarding potential cancer and reproductive harm. Please visit www.P65Warnings.ca.gov for more information.
Safety Precautions
? DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices (e.g., NFPA 70E in the USA or applicable local standards).
- Only qualified electrical workers should install this equipment. Read all instructions before proceeding.
- Never work alone.
- Do not exceed the device's maximum ratings.
- Do not use this device for critical control or protection applications where human or equipment safety relies on its operation.
- Before performing inspections, tests, or maintenance, disconnect all sources of electric power. Assume all circuits are live until de-energized, tested, and tagged. Consider all power sources, including backfeeding.
- Turn off all power supplying this device before working on it.
- Always use a properly rated voltage sensing device to confirm power is off.
- Before closing covers and doors, inspect the work area for tools and objects.
- Use caution when removing or installing panels to avoid contact with energized busbars.
- Proper handling, installation, and operation are crucial for successful operation and to prevent personal injury or equipment damage.
- Never bypass external fusing.
- Never short the secondary of a PT or VT.
- Never open circuit a CT; use the shorting block to short circuit CT leads before removing connections.
- Before performing Dielectric (Hi-Pot) or Megger testing on equipment where the meter is installed, disconnect all input and output wires to the meter. High voltage testing may damage electronic components.
- Install the power meter in a suitable electrical enclosure.
- Always use grounded external CTs for current inputs.
- All external CTs and PTs should have reinforced insulation.
- Do not use water or liquid to clean the product; use a dry cloth. Contact technical support if dirt cannot be removed.
Failure to follow these instructions will result in death or serious injury.
Installation
Box Contents
- One (1) power meter with retainer clips attached
- One (1) set of installation guides
- One (1) RS-485 terminator (MCT2W)
- One (1) panel gasket
- One (1) certificate of calibration
- Two (2) screws (spare screws for CTs)
Mounting
- Remove retainer clips from the power meter and set aside.
- Insert the power meter through the panel cut-out (refer to Figure 2). Note: Remove adhesive backing from the panel gasket before inserting the power meter.
- Attach the retainer clips to the power meter (refer to Figure 2).
Installation Considerations
- Allow for easy access to all parts of the power meter, with extra space for wiring, fuse disconnects, shorting blocks, accessories, or other components.
- Route wires to avoid covering the back of the unit or cooling vents.
- Install the power meter on a flat surface within a protective enclosure (e.g., a Type 1 rated enclosure or better in the USA).
Wiring
Refer to the label inside the rear panel door for specific wiring connections. Terminal wiring should have a minimum temperature rating of 80 °C (176 °F).
Connector | Wire Size | Wire Strip Length | Torque |
---|---|---|---|
Control Power¹ and Voltage Inputs¹ | 14 AWG 1.91 mm² | 0.28 in. (7 mm) | 4.4-5.3 in-lbf (0.5 - 0.6 N·m) |
Current Inputs² | 14 AWG 1.91 mm² | -- | 4.4-5.3 in-lbf (0.5 - 0.6 N·m) |
RS-485 Communications, Digital Outputs¹, and Digital Inputs | 16 AWG 1.34 mm² | 0.24 in. (6 mm) | 4.4-5.3 in-lbf (0.5 - 0.6 N·m) |
Measurement Category:
- Voltage Inputs: UL: 20 to 300 Vac L-L, CAT III; IEC: 20 to 480 Vac L-L; 20 to 277 Vac L-N, CAT III; 20 to 690 Vac L-L; 20 to 400 Vac L-N, CAT II
- Control Power: CAT III, up to 265 Vac or 300 Vdc
¹ Wire ferrules recommended. Wire ferrule determines stripping length.
² Current inputs (CTs) must have spade or ring terminal connections.
Supported System Types
Power System Configuration | Number of Wires | CTs Qty. | Meter Terminal | Voltage Connections Qty. | Meter Terminal | See Figure |
---|---|---|---|---|---|---|
1PH2W LN | 2 | 1 | I1 | 2 | V1, Vn | 5 |
1PH2W LL | 2 | 1 | I1 | 2 | V1, V2 | 6 |
1PH3W LL with N | 3 | 2 | I1, I2 | 3 | V1, V2, Vn | 7 |
¹ For 1 and 2 CT systems, configure the meter for the phases where the CT is installed. Refer to the PM5350 User Guide for details.
Power System Configuration | Number of Wires | CTs Qty. | Meter Terminal | Voltage Connections Qty. | Meter Terminal | See Figure |
---|---|---|---|---|---|---|
3PH3W Dlt Crnr Gnd | 3 | 2 | I1, I3 | 3 | V1, V2, V3 | 8 |
3PH3WDlt Ungnd | 3 | 3 | I1, I2, I3 | 3 | V1, V2, V3 | 9 |
3PH3W Wye Ungnd | 3 | 3 | I1, I2, I3 | 3 | V1, V2, V3 | 18 |
3PH3W Wye Res Gnd | 3 | 3 | I1, I2, I3 | 3 | V1, V2, V3 | 10 |
3PH4W Opn Dlt Ctr Tp | 4 | 3 | I1, I2, I3 | 4 | V1, V2, V3, Vn | 10 |
3PH4W Dlt Ctr Tp | 4 | 3 | I1, I2, I3 | 4 | V1, V2, V3, Vn | 10 |
3PH4W Wye Gnd | 4 | 3 | I1, I2, I3 | 4 | V1, V2, V3, Vn | 19 |
3PH4W Wye Res Gnd | 4 | 3 | I1, I2, I3 | 4 | V1, V2, V3, Vn | 19 |
Power System Configuration | Number of Wires | CTs Qty. | Meter Terminal | Voltage Connections Qty. | Meter Terminal | See Figure |
---|---|---|---|---|---|---|
3PH3W Dlt Crnr Gnd | 3 | 2 | I1, I3 | 2 | V1, V3 (V2 to Ground) | 11 |
3PH3WDlt Ungnd | 3 | 3 | I1, I2, I3 | 2 | V1, V3 (V2 to Ground) | 12 |
3PH3W Wye Ungnd | 3 | 3 | I1, I2, I3 | 3 | V1, V2, V3 (Vn to Ground) | 13 |
3PH3W Wye Res Gnd | 3 | 3 | I1, I2, I3 | 3 | V1, V2, V3 (Vn to Ground) | 14 |
3PH4W Opn Dlt Ctr Tp | 4 | 3 | I1, I2, I3 | 2 | V1, V3 (Vn to Ground) | 15 |
3PH4W Dlt Ctr Tp | 4 | 3 | I1, I2, I3 | 3 | V1, V2, V3 (Vn to Ground) | 16 |
3PH4W Wye Gnd | 4 | 3 | I1, I2, I3 | 3 | V1, V2, V3 (Vn to Ground) | 17 |
3PH4W Wye Res Gnd | 4 | 3 | I1, I2, I3 | 3 | V1, V2, V3 (Vn to Ground) | 17 |
¹ For 1 and 2 CT systems, configure the meter for the phases where the CT is installed. Refer to the PM5350 User Guide for details.
Overcurrent Protection
Clearly label the device's disconnect circuit mechanism and install it within easy reach of the operator. The disconnect circuit breaker or fusing must be rated for the available short circuit current at the connection points.
Control Power Source | Source Voltage (Vs) | Fuse | Fuse Amperage |
---|---|---|---|
CPT | Vs ≤ 125 Vac | FNM or MDL | 250 mA |
CPT | 125 < Vs ≤ 240 Vac | FNQ or FNQ-R | 250 mA |
CPT | 240 < Vs ≤ 265 Vac | FNQ or FNQ-R | 250 mA |
Line Voltage | Vs ≤ 240 Vac | FNQ-R | 250 mA |
Line Voltage | Vs > 240 Vac | FNQ-R | 250 mA |
DC | Vs ≤ 300 Vdc | LP-CC | 500 mA |
Fuse Selection Criteria:
- Select overcurrent protection rated as listed above.
- Select current interrupt capacity based on installation category and fault current capability.
- Select overcurrent protection with a time delay.
- Voltage rating should be based on the input voltage applied.
- If a 250 mA fuse is not available with the required fault current capability, use a fuse rated at a maximum of 500 mA.
- Fuse protection can be substituted with a molded-case circuit breaker 0.5 A/4P.
Technical Specifications
AC Control Power | Operating Range | 85 to 265 Vac |
Burden | 4.1 VA/1.5 W typical, 6.7 VA/2.7 W maximum at 120 Vac; 6.3 VA/2.0 W typical, 8.6 VA/2.9 W maximum at 230 Vac; 11.9 VA/3.5 W maximum at 265 Vac | |
Frequency | 45 to 65 Hz | |
Ride-Through Time | 100 mS typical at 120 Vac and maximum burden; 400 mS typical at 230 Vac and maximum burden | |
DC Control Power | Operating Range | 100 to 300 Vdc |
Burden | 1.4 W typical, 2.6 W maximum at 125 Vdc; 1.8 W typical, 2.7 W maximum at 250 Vdc; 3.8 W maximum at 300 Vdc | |
Ride-Through Time | 50 mS typical at 125 Vdc and maximum burden | |
Unom | Measured Voltage with overrange and Crest Factor | 277 V L-N |
Input-Voltage | UL: 20 to 300 Vac L-L, CAT III; IEC: 20 to 480 Vac L-L; 20 to 277 Vac L-N, CAT III; 20 to 690 Vac L-L; 20 to 400 Vac L-N, CAT II | |
Withstand | 700 Vac L-L; 404 Vac L-N | |
Input-Current | Permanent Overload | Continuous 20 A; 10 sec/hr 50 A; 1 sec/hr 500 A |
Impedance | 10 MΩ | |
Frequency Range | 45 to 70 Hz | |
CT Ratings Secondary | 1 A, 5 A Nominal | |
Measured Current with overrange and Crest Factor | 5 mA to 9 A | |
Withstand Impedance | < 0.3 MΩ | |
Frequency Range | 45 to 70 Hz | |
Burden | < 0.024 VA at 9 A | |
Rated Impulse Voltage | 2.5 KV |
Operating Temperature | Meter | -25 to +70 °C (-13 to +158 °F) |
Display | -20 to +70 °C (-4 to +158 °F) (Display functions to -25 °C (-13 °F) with reduced performance) | |
Storage Temperature | Meter + Display | -40 to +85 °C (-40 to +185 °F) |
Humidity Rating | 5 to 95% RH at 50 °C (122 °F) (non-condensing) | |
Pollution Degree | 2 | |
Altitude | ≤ 3000 m | |
Indoor use only | ||
Compliance | Protective Class | Class II (Double insulation at user-accessible area) |
Safety Instructions
Read these instructions carefully and familiarize yourself with the device before installation, operation, service, or maintenance. Pay attention to safety messages indicated by symbols.
⚠️ The addition of the safety alert symbol to a "Danger" or "Warning" label indicates an electrical hazard that will result in personal injury if instructions are not followed.
⚠️ This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
? DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. Schneider Electric assumes no responsibility for consequences arising from the use of this material. A qualified person has skills and knowledge related to electrical equipment construction, installation, and operation, and has received safety training to recognize and avoid hazards.
Wiring Diagrams
Input/Output
⚠️ WARNING: UNINTENDED EQUIPMENT OPERATION
- Do not use this device for critical control or protection applications where human or equipment safety relies on the control operation.
- Do not rely solely on device data to determine if your power system is functioning correctly or meeting all applicable standards and compliances.
- Do not use device control for time-critical functions due to potential delays between initiation and application of control action.
- Do not use digital inputs for voltage sensing applications over 36 Vdc.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The PM5350 features four (4) digital inputs and two (2) digital mechanical relay outputs. Digital inputs support Normal and Demand sync modes. Digital outputs support External Control (default), Demand sync, and Alarm modes. When configured for Alarm mode, the digital output can be controlled by the meter in response to an alarm condition.
Communications Capabilities
? DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Do not attempt to service the power meter. CT and PT or VT inputs may contain hazardous currents and voltages.
- Only authorized service personnel from the manufacturer should service the power meter.
- Shield conductors may be energized if not properly connected.
- Shield wire should be installed per the device's installation instructions and grounded at one end only.
Failure to follow these instructions will result in death or serious injury.
Baud Rate | Maximum Communication Distances (1 to 32 Devices) | |
---|---|---|
Feet | Meters | |
9600 | 8,000 | 2,438 |
19200 | 6,000 | 1,829 |
38400 | 2,500 | 762 |
Note: Distances listed are guides and may vary for non-PowerLogic™ devices. Refer to master device documentation for limitations.
Daisy-chaining Devices to the Power Meter
The RS-485 slave port allows the power meter to be connected in a daisy chain with up to 31, 2-wire devices. A communications link refers to a chain of devices connected by a communications cable.
If the power meter is the last device on the daisy chain, terminate it with the provided terminator. Refer to Table 8 for maximum daisy-chain communications distances for 2-wire devices. The terminal's voltage and current ratings comply with EIA RS-485 standards.
Operating the Display
The power meter features a large, back-lit LCD display that shows up to six lines of information plus a seventh row for menu options.
How the Buttons Work
Button Symbol | Navigation | Edit | Select | OK | Yes | No | Ack | Reset |
---|---|---|---|---|---|---|---|---|
> | Return to previous screen. For setup screens: If changes are made, a confirmation screen is displayed. If editing a value, exits edit mode and restores the previous value. | |||||||
> | Move cursor down. | |||||||
> | Move cursor up. | |||||||
> | Move the cursor one character to the left. | |||||||
> | Move cursor one character to the right. | |||||||
+ | Increment active character; toggle list selection On. | |||||||
- | Decrement active character; toggle list selection Off. | |||||||
Edit | Select parameter or item to edit. | |||||||
Select | Select/deselect item for association. | |||||||
OK | Enter change to a parameter. | |||||||
Yes | Accept. | |||||||
No | Reject. | |||||||
Ack | Acknowledge alarms. | |||||||
Reset | Reset selected item. |
China ROHS Certificate
The "Administrative Measures for the Restriction of Hazardous Substances in Electric Appliance and Electronic Products" requires this document to be shipped with all PM5350 products to the People's Republic of China. Purchasers in other countries may disregard.
Product: PowerLogic™ PM5350 (METSEPM5350)
Part Name | Hazardous Substances | |||||
---|---|---|---|---|---|---|
Lead (Pb) | Mercury (Hg) | Cadmium (Cd) | Hexavalent Chromium (Cr(VI)) | Polybrominated Biphenyls (PBB) | Polybrominated Diphenyl Ethers (PBDE) | |
Metal parts | O | O | O | O | O | O |
Plastic parts | O | O | O | O | O | O |
PCBA | O | O | O | O | O | O |
This table is made according to SJ/T 11364. O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572. X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572.
Company Information
Schneider Electric Limited
Stafford Park 5
Telford TF3 3BL
United Kingdom
Schneider Electric
35 rue Joseph Monier
92500 Rueil-Malmaison, France
+33 (0) 1 41 29 70 00
www.se.com
PowerLogic and Schneider Electric are trademarks or registered trademarks of Schneider Electric in France, the USA and other countries. Other trademarks are the property of their respective owners.
- This product must be installed, connected, and used in compliance with prevailing standards and/or installation regulations.
- If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired.
- The safety of any system incorporating this product is the responsibility of the assembler/installer of the system.
- As standards, specifications, and designs change from time to time, always ask for confirmation of the information given in this publication.
Document Number: 63230-401-202 A11
Revision: 05/2022
© 2022 Schneider Electric. All Rights Reserved.