FORTRESS
POWER
Secure your energy
eForce Battery-Inverter Integration Guide
APsystems
ALTENERGY POWER
Schneider
Electric
Sol-Ark
LIMITLESS POWER
ECOVAULT
victron energy
BLUE POWER
IMPORTANT NOTICE
This Quick Guide does not exempt the installer or User from reading each product manual. Failure to do so may risk damaging both Fortress Power equipment and other manufacturers and void warranty.
ABBREVIATIONS
A = Amperes
AC = Alternating Current
Ah = Amperes hour(s)
AWG = American Wire Gauge
BAT = Battery
BMS = Battery Management System
CAN = Controller Area Network
CC = Constant Current (Bulk)
CCV = Closed Circuit Voltage
°C = Degrees Celsius
CT = Current Transformer
CV = Constant Voltage (Absorption)
DC = Direct Current
ESS = Energy Storage System
EOL = End of Life
°F = Degrees Fahrenheit
HV = High Voltage
HVCO = High Voltage Cut-Off
I/O = Input or Output
ISC = Short Circuit Current
IP-Ingress Protection
in = Inches
lb. = Pounds
LED = Light Emitting Diode
LFCO = Low Voltage Cut-Off
LFP = Lithium Ferro Phosphate
LN1 = AC Line 1
LN2 = AC Line 2
LV = Low Voltage
m = Meters
mA = milliamperes
mV = millivolts
N = Neutral
NEC = National Electric Code
NEMA = The National Electrical Manufacturers Association
NFPA = National Fire Protection Association
NO = Normally Open
NC = Normally Closed
OCV = Open Loop Voltage
OSHA = Occupational Safety and Health Administration
OT = Over Temperature
OV = Over Voltage
PE = Protective Earth (Ground)
PV = Photovoltaic
R = Electrical Resistance (Ohms)
RS485 = Recommended Standard 485
SOC = State of Charge
SOC = State of Health
UT = Under Temperature
UV = Under Voltage
V = Voltage
VAC = Volts Alternating Current
VDC = Volts Direct Current
VPP = Virtual Power Plant
W = Watts (Power)
CONNECTION DIAGRAMS
CONNECTION OVERVIEW
48V Hybrid Inverter
Battery Port BAT COM PORT
RJ45 Battery to Inverter Cable
Guardian (Optional)
Terminator Coupler
RJ45 Terminator
Note: All RJ45 ports of the eWay are common
Discard the Terminating Coupler if your adding a Guardian
Built-In Connections
Required Installation
Unused Port
PARALLEL CONNECTION OVERVIEW
48V Hybrid Inverter
Battery Port BAT COM PORT
Included Unmodified Cable with RJ45 Connector
Guardian (Optional)
Rack A
Rack B
Relay Power Parallel Cable
Included Unmodified Cable with RJ45 Connector
Included Unmodified Cable with RJ45 Connector
Discard the Terminating Coupler if your adding a Guardian
RJ45 Terminator
Unused Guardian Cable
Fixed Connections
Required Installation
Unused Ports
Note: All RJ45 ports of the eWay are common
CLOSED LOOP AND PINOUT DEFINITIONS
To ensure Closed Loop communication, please follow the process below. If making a communication cable, refer to the pin out diagram for an RJ45 cable below. Type B format ethernet cable may also be used.
eForce Communication Pinout Configuration
Firmware 6016 or above
Protocol and cable
Dip Switch :1110
Using the DIP switch on the eWay Select the following protocol for Closed Loop Communication. You must do this process only the primary eWay when in parallel. The primary eWay shall be the one that connects battery to inverter communication.
ON
ENVY INVERTER-BATTERY COMMUNICATION PORT PINOUT
Lithium Profile: 18 (Fortress)
Inverter firmware shall be 1E1E or above
LCD Firmware shall be V20
PIN | COLOR (B FORMAT) | ASSIGNMENT | PIN | COLOR (B FORMAT) | ASSIGMENT |
1 | White Orange | CAN1_H | 1 | White Orange | BAT RS485 B |
2 | Orange | CAN1_L | 2 | Orange | BAT RS485 A |
3 | White Green | CAN2_G | 3 | White Green | NC |
4 | Blue | CAN2_H | 4 | Blue | BAT CAN H |
5 | White Blue | CAN2_L | 5 | White Blue | BAT CAN L |
6 | Green | RS485G1 | 6 | Green | NC |
7 | White Brown | RS485A1 | 7 | White Brown | NC |
8 | BROWN | RS485B1 | 8 | BROWN | RS485B1 |
Included Unmodified Normal Format B RJ45 Cable. Any of the included cables will work.
eForce Communication Pinout Configuration
Firmware 6016 or above
Protocol and Cable
Dip Switch:1000
Using the DIP switch on the eWay Select the following protocol for Closed Loop Communication. You must do this process only the primary eWay when in parallel. The primary eWay shall be the one that connects battery to inverter communication.
ON
SOL-ARK INVERTER-BATTERY COMMUNICATION PORT PINOUT
BMS Lithium BAT 00
PIN | COLOR (B FORMAT) | ASSIGNMENT | PIN | COLOR (B FORMAT) | ASSIGMENT |
1 | White Orange | Can1_H | 1 | White Orange | NC |
2 | Orange | Can1_L | 2 | Orange | BAT RS485 B- |
3 | White Green | Can2_G | 3 | White Green | BAT RS485 A+ |
4 | Blue | Can2_H | 4 | Blue | BAT CAN H |
5 | White Blue | Can2_L | 5 | White Blue | BAT CAN L |
6 | Green | RS485G1 | 6 | Green | GND |
7 | White Brown | RS485A1 | 7 | White Brown | BAT RS485 A+ |
8 | BROWN | RS485B1 | 8 | BROWN | BAT RS485 B- |
Modified Cable (not included). Installer may use extra cable included with the eForce or Inverter to crimp RJ45 cable to the following configuration
eForce Communication Pinout Configuration
Firmware 6016 or above
Protocol and Cable
Dip Switch :1110
Using the DIP switch on the eWay Select the following protocol for Closed Loop Communication. You must do this process only the primary eWay when in parallel. The primary eWay shall be the one that connects battery to inverter communication.
ON
ECOVAULT INVERTER-BATTERY COMMUNICATION PORT PINOUT
BMS Communication: FOR
PIN | COLOR (B FORMAT) | ASSIGNMENT | PIN | COLOR (B FORMAT) | ASSIGMENT |
1 | White Orange | CAN1_H | 1 | White Orange | RS485 B |
2 | Orange | CAN1_L | 2 | Orange | RS485 A |
3 | White Green | CAN2_G | 3 | White Green | NC |
4 | Blue | CAN2_H | 4 | Blue | BAT CANH |
5 | White Blue | CAN2_L | 5 | White Blue | BAT CAN L |
6 | Green | RS485G1 | 6 | Green | BAT RS485 A |
7 | White Brown | RS485A1 | 7 | White Brown | BAT RS485 B |
8 | BROWN | RS485B1 | 8 | BROWN | BAT RS485 B |
Included Unmodified Normal Format B RJ45 Cable. Any of the included cables will work.
eForce Communication Pinout Configuration
Firmware 6016 or above
Protocol and Cable
Dip Switch :1100
Using the DIP switch on the eWay Select the following protocol for Closed Loop Communication. You must repeat this process for all eWay onsite.
ON
SCHNEIDER-BATTERY COMMUNICATION PORT PINOUT
Schneider 6848 XW PRO
Baud Rate 19200
PIN | COLOR (B FORMAT) | ASSIGNMENT | ||||||||||||||
1 | White Orange | CAN1_H | 1 | Do Not Connect | 3 | GND | 5 | GND ISO | 7 | RS485 A ISO | 9 | RS485 B ISO | 11 | Do Not Connect | ||
2 | Orange | CAN1_L | 2 | Do Not Connect | 4 | GND ISO | 6 | CAN L ISO | 8 | CAN H ISO | 10 | Digital input 2 (12VDC) | 12 | Do Not Connect | ||
3 | White Green | CAN2_G | ||||||||||||||
4 | Blue | CAN2_H | ||||||||||||||
5 | White Blue | CAN2_L | ||||||||||||||
6 | Green | DO | ||||||||||||||
7 | White Brown | RS485_A1 | ||||||||||||||
8 | BROWN | RS485_B1 |
Modified stripped cable
Schneider Gateway: 12 ISO1CAN L, 14 ISO1CAN H
eForce Communication Pinout Configuration
Firmware 6016 or above
Protocol and Cable
Dip Switch :1010
Using the DIP switch on the eWay Select the following protocol for Closed Loop Communication. You must do this process only the primary eWay when in parallel. The primary eWay shall be the one that connects battery to inverter communication.
ON
VICTRON-BATTERY COMMUNICATION PORT PINOUT
Victron Inverter
BMS-Can
charger
Quattro
4815000/2001
VE.Can
VE Direct 1 VE Direct 2 VE.Direct 3
WiFi Access Point
Bluetooth
Green: Active
Orange: Disabled
Connected
No connected
Disabled
Cerbo GX
VE.BUS
Press short: toggle WiFi Access Point & Bluetooth on/off
Press long: reset network settings
Micro SD
Tank
Temp
Digital inputs
Relay 1
NO COM NC
Relay 2
NO COM NC
Power In
8-70VDC
Connect Modified Cable to the Victron CERBO GX
PIN | COLOR (B FORMAT) | ASSIGNMENT | Modified Cable (not included). Installer may use extra cable included with the eForce or Inverter to crimp RJ45 cable to the following configuration | PIN | COLOR (B FORMAT) | ASSIGNMENT |
1 | White | CAN1_H | 1 | White Orange | CAN1_H | |
2 | Orange | CAN1_L | 2 | Orange | CAN1_L | |
3 | White Green | CAN2_G | 3 | White Green | CAN2_G | |
4 | Blue | CAN2_H | 4 | Blue | CAN2_H | |
5 | White Blue | CAN2_L | 5 | White Blue | CAN2_L | |
6 | Green | DO | 6 | Green | CAN2_G | |
7 | White Brown | RS485_A1 | 7 | White Brown | CAN2_H | |
8 | BROWN | RS485_B1 | 8 | BROWN | CAN2_L |
COMMISSIONING
1. Turn on the Inverter Battery Breaker on the Inverter
BRIDGED INSIDE
L1
L2
LOAD Breaker
GEN LOAD GRID
BAT + BAT+ BAT-BAT-
L1 L2 L1 L2 L1 L2
OFF
ON
Primary Battery
2. Turn ON the Disconnect on the eWay. For paralleled battery systems, only turn on the Primary Battery
OFF
ON
Primary Battery
OFF
ON
Secondary Battery
OFF
ON
Secondary Battery-n
PROGRAMMING THE INVERTER
FORTRESS POWER ENVY
Before setting the parameters, make sure the system is in Standby. Make sure to press SET for each setup. Confirm the battery is doing Closed Loop Communications with the inverter under the Battery of the Data Section.
BATTERY SET UP
Basic | Grid type 240/120V ▼ Grid Freq 60Hz▾ Set | Solar | Vbat Pchg | Ibat Pdischg |
Charge | Grid regulation UL1741/IEEE 154 Reconnect time(S) 300 | Battery SOC/SOH | Vbat_Inv BatState | CycleCnt |
HV1 V S HV2 V S HV3 V S | ||||
Discharge | LV1 V S LV2 V S LV3 V S | Grid Vchgref/Vcut | Bat capacity | |
HF1 Hz S HF2 Hz S HF3 Hz S | ||||
Advanced | UPS Vcellmax | Vcellmin | ||
LF1 Hz S LF2 Hz S LF3 Hz S | ||||
Debug | Tcellmax(°C) | Tcellmin (°C) | ||
Device info. | Battery type Lithium Set | Other BMSEvent1 | BMSEvent2 | |
Lithium brand Lithium18 Lead capacity(Ah) 400 | Echg_day Echg_all | Edischg_day Edischg_all |
SELF-CONSUMPTION MODE
Basic | Charge first(PV) Set | Basic | Operating Mode Use SOC % Use Bat V Set |
Time 1 00 00 00 00 Charge first power(kW) 12 | Charge | Bat charge current limit(A) 250 | |
Time 3 00 00 00 00 Stop charge first SOC(%) 100 | Discharge | AC charge According to SOC/Volt Set | |
Stop charge first Volt(V) 54.4 | AC charge power(kW) 6 Start AC charge SOC(%) 30 | ||
Advanced | Time 1 00 00 00 00 Start AC charge Volt (V) 48.5 | Advanced | |
Absorb voltage (V) 51.5 Float voltage (V) 51 Set | Debug | Time 2 00 00 00 00 Stop AC charge SOC(%) 51 | |
Start derate Volt(V) 48 | Device info. | Time 3 00 00 00 00 Stop AC charge Volt (V) 51 |
Basic | Operating Mode Use SOC % Use Bat V Set |
Charge | Bat charge current limit(A) 250 |
Discharge | AC charge According to SOC/Volt Set |
AC charge power(kW) 6 Start AC charge SOC(%) 30 | |
Advanced | Time 1 00 00 00 00 Start AC charge Volt (V) 51.8 |
Debug | Time 2 00 00 00 00 Stop AC charge SOC(%) 54.4 |
Time 3 00 00 00 00 Stop AC charge Volt (V) | |
Device info. |
Generator
Basic | DC Current | Gen rated power(kW) 8 Set | ||
Charge current limit(A) 100 | ||||
Charge start Volt(V) 46.5 Charge start SOC(%) 25 | ||||
Discharge | Charge end Volt(V) 51 Charge end SOC(%) Adj* | |||
Advanced | AC couple | Start Volt(V) Default Start SOC(%) Default Set | ||
Debug | End Volt(V) Default End SOC(%) Default | |||
Device info. |
Basic | Operating Mode Use SOC % Use Bat V Set | |
Charge | Discharge current limit(A) 250 Discharge start power(W) 50 | |
Discharge | On-grid Cut-off(%) 20 Off-grid Cut-off(%) 15 | |
On-grid Cut-off(V) 46 Off-grid Cut-off(V) 45 | ||
Advanced | Forced discharge Set | Discharge power(kW) 0 |
Debug | Time 1 00 00 00 00 | Stop discharge SOC(%) 0 |
Device info. | Time 2 00 00 00 00 | Stop discharge Volt(V) 0 |
Time 3 00 00 00 00 |
Basic | PV input PV1&2&3 Meter or CT CT Set | Basic | Export to Grid Max Export to Grid(kW) 0 Set |
MODBUS addr 1 Meter type 0:1 Phase Meter | Charge | Zero Export | |
Charge | Vpv start (V) 140 CT ratio 1/3000 | Parallel system | |
Discharge | Offgrid output CT direction reversed Set | Discharge | Role 1 Phase Primary Phase Default Set |
Seamless switch ✔ Charge last RSD disable | Advanced | Parallel battery | Share battery Set |
Advanced | EPS output Micro-grid | ||
AC couple without Battery | Debug | Auto Detect Phase Reset | |
Debug | Smart load Run without grid Set | Device info. | |
Device info. | PV Arc PV Arc fault clear Set |
BACK UP
Basic | PV input PV1&2&3 Meter or CT CT Set | Basic | Export to Grid Max export to Grid(kW) Adj Set | |
MODBUS addr 1 Charge | Meter type 0:1 Phase Meter | Charge | Zero Export | |
Vpv start (V) 140 CT ratio 1/3000 | Discharge | Parallel system | ||
Discharge | Offgrid output CT direction reversed Set | Discharge | Role 1 Phase Primary Phase Default Set | |
Seamless switch ✔ Charge last RSD disable | Advanced | Parallel battery | Share battery Set | |
Advanced | EPS output Micro-grid | |||
AC couple without Battery | Debug | Auto Detect Phase Reset | ||
Debug | Smart load Run without grid Set | Device info. | ||
Device info. | PV Arc PV Arc fault clear Set |
SOL-ARK
SHARE SOL-ARK MONITORING W/FORTRESS
Set up Wi-Fi with Sol-Ark Inverter using Sol-Ark's My Sol-Ark App and have your site name and Wi-Fi dongle serial number handy to register the system online with Sol-Ark. After registering, use a laptop to log into MySolArk via a web browser at http://mysolark.com
Note: For certain circumstances, temporarily use the batteries in open-loop communication mode, please follow the following link for open-loop settings:
1. To program the inverter using the Sol-Ark inverter screen, go to battery setup menu:
Solar Today= 53KWH Total=599.8 KWH
55.2V
8.03 KW 0 8
-3.2 KW 0 12
4.26 KW 0 12
00.0 KW 0 12
Basic Setup
System Alarms
Battery Setup
Li-Batt info
Grid Setup
-ID: 1807264001 SD
-COMM: 1295
-MCU: Ver0748
2. Program the 'Batt' tab first. Enter the settings as shown below and tap on 'OK' in the bottom of the menu afterwards:
Closed Loop Settings
Batt Setup | Batt | Charge | Discharge | Smart Load | Wind |
Batt Capacity | 200Ah Per eForce | Use Batt V charged |
Max A Charge | 120A Per eForce | Use Batt % Charged |
No Battery | ||
Max A Discharge | 160A Per eForce | BMS Lithium Batt 00 |
Activate Battery | ||
Tempco | 0mV/C/Cell |
Confirm closed loop communication was established by going to the Home screen and selecting Li-BATT INFO
Battery Voltage: 52.60V | 0.0 V | 0.0 A-100.0 C | 0% | 0Ah | 0.0V | 0.DA | 0x00 0x00 | ||
Battery Current: -1A | Battery charge Voltage: 56.0V | 1 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 |
Battery Temp.: 20.5C | Charge current limit: 324A | 2 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 |
SOC = 58% SOH = 100% Discharge current limit: 360A | 3 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 0.00 | |
Nominal_Cap: 0 Ah | 4 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 0.00 | |
Alarms: 0x00 0x00 | 5 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 | |
6 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 | ||
7 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 | ||
8 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 | ||
9 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 | ||
10 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 | ||
11 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 | ||
12 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 | ||
13 0.0 V | 0.0 A | 0.0 C | 0.0% | 0.0Ah | 0.0V | 0.0A | 000 |
Open Loop Settings
Batt Setup | Batt | Charge | Discharge | Smart Load | Wind |
Batt Capacity | 200Ah Per eForce | Use Batt V charged |
Max A Charge | 120A Per eForce | Use Batt % Charged |
No Battery | ||
Max A Discharge | 160A Per eForce | BMS Lithium Batt |
Activate Battery | ||
Tempco | 0mV/C/Cell |
Note:
a) If closed loop communication is set up correctly, enabling 'BMS Lithium Batt 00' will adjust some values automatically. In this tab, those would be 'Batt Capacity' and 'Tempco'.
b) If the total charge/discharge current capacity of the batteries exceeds the inverter's capabilities, use the maximum current settings of the inverter.
For example, if you have four eForce batteries and one Sol-Ark 12K inverter, based on the size of the battery bank, 'Max A Charge' and 'Max A discharge' should be 240A each. But Sol-Ark 12K can only carry 185A DC going to or coming from the battery. So, in this case, both 'Max A Charge' and 'Max A Discharge' would be set to 185A.
c) If recovering a deeply discharged battery, adjust the above charge amps to 10A.
3. Next, program the 'Charge' tab in the 'Battery Setup' menu:
Batt Setup | Batt | Charge | Discharge | Smart Load | Wind |
Start V 45V 45.8V | Float V 52V | 51V Open Loop | |
Absorption V 52V | 51.5V Open Loop | ||
Start % 10% 15% | Equalization V 52V | 51.5V Open Loop | |
120A Per eForce | 120A Per eForce | ||
0 Days | 0 Hours | ||
☑ Gen Charge ☑ Grid Charge |
Note:
a) The settings shown in the latter screenshot are the most conventional ones, hence, adjustments may be required (please see the table below).
The approach described in the note "2b" applies while programing this tab as well. Additionally, current set point (A) must not exceed the generators' capability.
Grid-tied | Portable Generator | Stationary Generator | Gen Charge | Grid Charge | Time of Use |
Y | N | N | uncheck | 15% | 20% |
Y | N | Y | 10% | 15% | 20% |
N | Y | N | 20% | uncheck | n/a |
N | N | Y | uncheck | 20% | n/a |
N | Y | Y | 10% | 20% | n/a |
b) Larger generators are commonly tied into the grid side of the inverter rather than the dedicated generator input. Make check-marks and current adjustments accordingly. This fact was kept in mind while creating the last two rows of the table above.
c) Fortress batteries may be discharged to its full rated capacity without voiding the warranty, but for best overall experience and battery life, limit the discharge to 80% except for very rare occasions. Here is a list of our suggested triggers:
d) It is acceptable to raise the grid or generator start triggers to increase the reserve capacity of the system.
4. Program the Discharge tab:
Batt Setup | Batt | Charge | Discharge | Smart Load | Wind |
Shutdown 45V | 10% | Batt Resistance 5 mOhms | |
Low Batt 46V | 20% | Batt Charge Efficiency 98% | |
Restart 46.2V | 25% | BMS_Err_Stop | |
Batt Empty V 44.8V |
Note:
a) At 'Shutdown' state of charge (battery bank charge percentage), inverter prevents battery from powering the loads. The battery(s) will renew/continue providing power to the loads when the battery bank is recharged to 'Restart' state of charge. 'Shutdown' and 'Restart' state of charge set-points can be increased to increase the "reserve capacity" of the system, but that will cause less battery charge usage. The correct shutdown level is specific to the project site.
b) Low battery is an alarm also specific to the project site, integrated with the Sol-Ark monitoring app. We suggest a 20% state of charge as a low battery alarm level. But it is a good idea to increase it if the 'Shutdown' and 'Restart' set-points are increased.
c) The battery empty voltage should not be lower than 44.8V. The last statement from the previous note applies to the 'Batt Empty V'. Usually this set-point does not exceed 45.5V.
Grid Setup / Time-of-Use
Time-of-use settings are specific to each end user but also important to having system behavior meeting customer expectations. system to behave as the end user wants it to behave. There are a few important things to know when programming Sol-Ark's time-of-use settings:
1) Checking the "charge" column boxes will force a grid charge to that battery.
2) Leaving the "charge" column boxes unchecked will act as a low battery cut-off.
3) Enabling "grid-sell" will allow the battery to sell back to the grid when it is otherwise 100% full.
4) Solar will charge the battery to 100% if there is enough sunlight available and all the loads are otherwise met.
5) Additional settings worth exploring in the Grid Setup Menu are the frequency ranges and grid profile settings useful for generator compatibility.
Back-up Only Customers:
Batteries work better and last longer if they are used, rather than staying 100% full. Our recommendation is to allow the battery to drop to 70% during the early morning hours and then have it go to 100% during the day. You do not need to enable a grid-charge for this functionality. You may want to increase the grid start % or voltage in the battery setup menu.
Time-of-use Customers:
1) To maintain solar tax credit compliance, you will want to prioritize battery charging in the hours before the time-of-use period so that the battery is 100% going into the time frame.
2) You may also want to enable a grid charge the hour before the time-of-use period to ensure the battery reaches 100%
3) You may not want to discharge the battery too aggressively. Sticking to no more than 9kW per eVault or 3.3kW per eFlex Max is optimal for maximizing battery life under time-of-use grid sell-back. Likewise, selling back at less than the full rated value of the inverter is healthy for inverter life. So for example, if you can identify that the battery and inverter will be fully utilized over the time of use rate period by discharging at 5kW rate instead of the full rated capacity of the inverter, it will extend battery life.
4) That said, the mantra is "use it or lose it" - it is more economically advantageous for the end user to use the battery when it is financially advantageous to do so, rather than to keep the battery at 100% always.
Bad Utility Buyback Rates aka "no net-metering" aka "bad net-metering":
Allow the battery to discharge to a 20% state-of-charge over night, so that it can absorb as much solar power as possible during the day rather than having that energy sold back to the grid. Staggering the step down percentages throughout the night so that the battery so that the battery hits 20% right in the early morning will mitigate the risk of power outage between sun up and sun down. Maintain the final 20% time-of-use step with a grid charge to make sure the battery does not go below 20% (which would trigger a full grid recharge at 15% per prior steps). During the day, it does not matter if you prioritize the grid or the battery first when recharging with solar power.
Grid Param
Suggested Grid-Tie Parameters
Limiter | Sell Control | Grid Input | FreqVolt | PowFac | Relay |
Grid Sell 9000 | Time 3:00AM | Power(W) 3kW | Batt 30% | Charge | Sell |
Limited Power to Home | 5:00AM | 3kW | 20% | ||
Limited Power to Load | 9:00AM | 9kW | 100% | ||
Time of Use Setup | 3:00PM | 3kW | 100% | ||
7:00PM | 6kW | 60% | |||
9:00PM | 3kW | 45% | |||
CANCEL | OK |
Note: Change the programming from Percentage to Voltage in the Battery setup menu. (Use Batt % Charge / Use Batt V charge)
Here are more aggressive settings for minimizing sell-back to the grid (but allowing grid-sellback when the batteries are full).
Grid Param
For minimizing grid sell-back, no TOU
Limiter | Sell Control | Grid Input | FreqVolt | PowFac | Relay |
Grid Sell 9000 | 3:00AM | 9kW | 20% | ||
Limited Power to Home | 5:00AM | 9kW | 20% | ||
Limited Power to Load | 9:00AM | 9kW | 20% | ||
Time of Use Setup | 3:00PM | 9kW | 20% | ||
7:00PM | 9kW | 20% | |||
9:00PM | 9kW | 20% | ✓ | ||
CANCEL | OK |
ECOVAULT
OPERATION AND DISPLAY PANEL
The operation and display panel of the inverter includes one LCD screen, three indicators, and four physical buttons.
Inverter
Display
Physical button | Physical button Description | LED Indicator | Description |
SET | Enter/Exit the setup menu | AC/INV | Normally ON: Grid Green bypass output Flash: inverter output |
UP | Go to the next option | CHARGE Yellow | Normally ON: charging Flash: charging |
DOWN | Go to the previous option | FAULT Red | Normally ON: level-1 fault Flash: level-2 fault OFF: level-3 or level-4 fault |
ENTER | Confirm/Enter the option in setup menu |
ICON | DESCRIPTION | ICON | DESCRIPTION |
PV panel | Grid | ||
Battery | Generator | ||
The inverter is working | Load | ||
The inverter is communicating with the data collector | The buzzer is in mute mode | ||
The inverter is in standby mode | Power flow direction | ||
There is a fault | The inverter is working normally | ||
Load power: 80%-100% | Settings | ||
Load power: 60%-79% | SOC: 80%-100% | ||
Load power: 40%-59% | SOC: 60%-79% | ||
Load power: 20%-39% | SOC: 40%-59% | ||
Load power: 5%-19% | SOC: 20%-39% | ||
Battery under voltage | SOC: 5%-19% | ||
Overload | Battery over-discharge | ||
System communication error | BMS fault | ||
System overvoltage | System undervoltage | ||
System overtemperature | System under temperature | ||
Battery full power | System overcurrent | ||
Sealed lead-acid battery | User defined battery | ||
Flooded lead-acid battery | Ternary Li-ion battery | ||
Gel lead-acid battery | Energy-saving mode | ||
LFP Li-ion battery | PV power is charging the battery | ||
PV power is loading |
AC input power is charging the battery
The output mode of the inverter is Grid first
The output mode of the inverter is Grid bypass
The output mode of the inverter is PV first
The output mode of the inverter is battery first
REAL-TIME PARAMETERS VIEW
On the screen, press the UP/DOWN button to view real-time data of the inverter in operation
NOTICE
Main Screen
View Real-Time Data
Real-Time Data
SETUP FAULT SETUP DATE START BMS P MAINS CHARGE VOLT RECOVER PARAM ID CODE VALUE TIME END VER BAT LOAD DISCHG CURR GENERAT
PAGE PV
BATTERY
AC INPUT
LOAD
GENERAL
1 | PV input voltage | Battery voltage | Grid input voltage | Single-phase voltage | Current time |
2 | PV input current | Battery current | Grid input current | Single-phase current | Current date |
3 | PV input power | Battery voltage | Grid total input power | Single-phase active power | PV gross generation |
4 | PV generation for the day | Battery current | Grid charging capacity for the day | Single-phase apparent power | Total load consumption |
5 | PV heat sink temperature | Heat sink temperature | Grid frequency | Inverter output frequency | RS485 address |
6 | Rated open circuit voltage | Rated battery voltage | Bus voltage | Rated output frequency | Software version |
7 | Maximum PV charge current | Maximum battery charges current | Maximum Grid charge current | Total output active power | / |
8 | Total output apparent frequency | / |
SETTINGS
NOTICE
If you use lithium battery which has communication with Inverter, please skip all Battery Voltage setting (04~07)
INVERTER MODE OF OPERATION DESCRIPTION
00 | Exit | ESC | Exit the setup menu |
01 | ESS Operation Mode | UTI (default) Backup Mode | Backup Mode (Load Source Priority: PV → Grid → Battery) |
If PV power is insufficient, the system uses both PV and grid power to support the load. | |||
When PV power exceeds the demand, the excess energy charges the battery. | |||
Grid power is only used for charging when the battery is over discharged (if setting 06 is PV-only charging, the grid will not charge the battery). | |||
The battery discharges only in off-grid mode | |||
Self-Consumption Mode | SBU | Self-Consumption Mode (Load Source Priority: PV → Battery → Grid) | |
(Recommend) | PV Power Priority - The system first uses solar (PV) power to supply the load. | ||
Battery Backup - If PV power is insufficient, the system draws power from the battery to support the load. |
SOL
Grid as Last Resort – The system switches to grid power only when the battery voltage drops below the set threshold (Parameter 4).
Return to PV/Battery - Once the battery voltage recovers above the set threshold (Parameter ⑤), the system switches back to PV or battery power for load supply.
Self-Consumption Mode (Load Source Priority: PV → Battery → Grid)
The PV mode is to be applied first and when the PV power is unavailable or the battery voltage is lower than the set value in the item 4, it will switch to the Grid mode
SUB
PV and Grid prioritize Charging the Battery
Battery Charging Priority Mode
PV Priority for Charging - The system prioritizes PV power to charge the battery.
Grid-Assisted Charging - If PV power is insufficient, the system uses both PV and grid power for charging (except when Parameter 06 is set to PV- only charging, in which case the grid will not charge the battery).
Grid Powers the Load - While the battery is charging, the grid supplies power to the load when PV alone is not sufficient.
Hybrid Load Supply - If PV power is enough for charging but insufficient for the load, the system will use both PV and grid power to support the load.
Battery Discharges Only in Off-Grid Mode - The battery does not discharge when the system is connected to the grid; it is reserved for off-grid operation only.
FN | PARAMETER | EFORCE | EFLEX MAX/EFLEX | EVAULT MAX |
04 | Battery Low Cut of Voltage | 48V | 51.2V | 51.2V |
WHEN PARAMETER ITEM 01 IS SET TO SBU (SOLAR-BATTERY UTILITY) OR SOL (SOLAR ONLY) MODE, THE SYSTEM PRIORITIZES PV AND BATTERY POWER. HOWEVER, IF THE BATTERY VOLTAGE DROPS BELOW THE SET CUT-OFF POINT, THE POWER SOURCE AUTOMATICALLY SWITCHES FROM THE INVERTER TO THE GRID TO PREVENT BATTERY OVER-DISCHARGE | ||||
06 | Grid Charge Setting | SNU (RECOMMENDED) | SNU (RECOMMENDED) | SNU(RECOMMENDED) |
SNU (DEFAULT): BOTH PV AND GRID CAN CHARGE THE BATTERY, WITH PV AS THE PRIORITY CHARGING SOURCE OSO: GRID POWER WILL NOT CHARGE BATTERY | ||||
07 | Battery Charge Current | 120Adc per eForce | 60Adc per eFlex MAX/eFlex | 140Adc per eVault MAX |
08 | Battery Type | L14/15/16 | L14/15/16 | L14/15/16 |
09 | Battery boost charge voltage (Bulk & Absorption) | 51.4V | 55.2V | 55.2V |
10 | Boost Charge duration | 60min | 60min | 60min |
11 | Battery floating charge voltage | 51V | 54V | 54V |
12 | Battery over- discharge Protection voltage (delayed shutdown) | 44.8V | 48V | 48V |
13 | Battery over- discharge delay time | 50s | 50s | 50s |
WHEN THE BATTERY VOLTAGE DROPS BELOW THE THRESHOLD SET IN PARAMETER ITEM 12, THE INVERTER WILL WAIT FOR THE DELAY TIME SET IN THIS PARAMETER BEFORE SHUTTING OFF THE OUTPUT. SETTING RANGE: 5S - 50S ADJUSTMENT STEP: 5S PURPOSE: THIS DELAY PREVENTS UNNECESSARY SHUTDOWNS DUE TO TEMPORARY VOLTAGE DIPS, ENSURING STABLE SYSTEM OPERATION WHILE STILL PROTECTING THE BATTERY FROM OVER-DISCHARGE | ||||
14 | Battery under- voltage alarm threshold | 46 | 51.2 | 51.2 |
WHEN THE BATTERY VOLTAGE IS LOWER THAN THE THRESHOLD, IT WILL GIVE AN UNDER-VOLTAGE ALARM AND THE OUTPUT WILL NOT SHUT DOWN. SETTING RANGE: 40 V-52 V, WITH A STEP OF 0.4 V | ||||
15 | Battery over discharge protection voltage | 44.8 | 48 | 48 |
16 | Battery equalization charge | DIS (Default) | DIS (Default) | DIS (Default) |
DIS: DISABLE EQUALIZATION CHARGE ENA: ENABLE EQUALIZATION CHARGE, ONLY AVAILABLE FOR FLOODED LEAD-ACID BATTERIES, SEALED LEAD-ACID BATTERIES, AND USER-DEFINED ONES |
32 | RS485 Communication Function | CAN | CAN | CAN |
33 | BMS communication | FOR | FOR | FOR |
35 | Battery under- voltage recovery threshold | 46 | 51.2 | 51.2 |
37 | Battery Recharge Voltage | 48 | 51.2 | 51.2 |
39 | Charge current limit (Communicate with BMS ) | LCBMS (default) | LCBMS (default) | LCBMS (default) |
LCSET: THE MAXIMUM BATTERY CHARGE CURRENT IS NOT GREATER THAN THE SET VALUE OF "07" LCBMS (DEFAULT): THE MAXIMUM BATTERY CHARGE CURRENT IS NOT GREATER THAN THE MAXIMUM BMS ALLOWED CURRENT LCINV: THE MAXIMUM BATTERY CHARGE CURRENT IS NOT GREATER THAN INVERTER ALLOWED CURRENT | ||||
40-45 | Start and End Charge time 1,2,3, | 00:00:00 | 00:00:00 | 00:00:00 |
46 | Timed battery charge function | DIS | DIS | DIS |
DIS (DEFAULT): DISABLE THE FUNCTION ENA: WHEN THE TIMED GRID CHARGING/LOAD SUPPLY FUNCTION IS ENABLED, THE POWER SUPPLY MODE WILL OPERATE BASED ON THE CONFIGURED TIME PARAMETERS AND BATTERY STATE (RANGE 0:00:00-23:59:00) | ||||
1. OPERATING MODES SBU MODE ACTIVATION: THE SYSTEM WILL OPERATE IN SBU MODE WHEN TIMED GRID CHARGING IS ENABLED. THE INVERTER WILL PRIORITIZE SOLAR (S) AND BATTERY (B) POWER, SUPPLYING LOADS FROM THESE SOURCES. WHEN THE SYSTEM REACHES THE CONFIGURED CHARGING PERIOD OR THE BATTERY ENTERS AN OVER-DISCHARGE STATE, IT WILL SWITCH TO GRID (U) POWER FOR BATTERY CHARGING. UTI MODE ACTIVATION (WITH TIMED DISCHARGE ENABLED): IF THE TIMED DISCHARGE FUNCTION IS ALSO ENABLED, THE SYSTEM WILL SWITCH TO UTI MODE. IN THIS MODE, THE INVERTER: USES GRID POWER FOR BATTERY CHARGING ONLY DURING THE SET CHARGING PERIOD. SWITCHES TO BATTERY INVERTER OPERATION DURING THE CONFIGURED DISCHARGE PERIOD OR IF THE GRID POWER IS LOST. | ||||
47-52 | Start and End discharge time 1,2,3 | 00:00:00 | 00:00:00 | 00:00:00 |
53 | Timed battery discharge function | DIS | DIS | DIS |
DIS (DEFAULT): DISABLE THE FUNCTION |
ENA: AFTER THE TIMED BATTERY DISCHARGE FUNCTION IS ENABLED, THE POWER SUPPLY MODE WILL BE CHANGED INTO UTI, WHERE THE SYSTEM ONLY SWITCHES TO THE POWER SUPPLY OF BATTERY INVERTER DURING THE SET DISCHARGE PERIOD OR GRID FAILURE
58 | SOC setting for discharge alarming | 25% | 25% | 25% |
WHEN THE CAPACITY IS LESS THAN THE SET VALUE, THE SOC ALARMS (UNIT: %, ONLY AVAILABLE DURING NORMAL BMS COMMUNICATION) | ||||
59 | SOC setting for discharge cutoff | 20% | 20% | 20% |
WHEN THE CAPACITY IS LESS THAN THE SET VALUE, THE DISCHARGE STOPS (UNIT: %, ONLY AVAILABLE DURING NORMAL BMS COMMUNICATION) | ||||
60 | SOC setting for charge cutoff | 100% | 100% | 100% |
WHEN THE CAPACITY IS GREATER THAN THE SET VALUE, THE CHARGE STOPS (UNIT: %, ONLY VALID DURING NORMAL BMS COMMUNICATION) | ||||
61 | SOC setting for switching to grid | 25% | 25% | 25% |
WHEN THE CAPACITY IS LESS THAN THE SET VALUE, IT SWITCHES TO GRID (UNIT: %, ONLY AVAILABLE DURING NORMAL BMS COMMUNICATION) | ||||
62 | SOC setting for Switching to inverter Output | 100 | 100 | 100 |
WHEN THE CAPACITY IS GREATER THAN THE SET VALUE, IT SWITCHES TO THE INVERTER OUTPUT MODE (UNIT: %, ONLY AVAILABLE DURING NORMAL BMS COMMUNICATION) | ||||
73 | Max charging current by generator | 80Adc | 80Adc | 80Adc |
SCHNEIDER
1. Connect to Schneider's Insight Local
2. Go to SETUP>CONFIGURATION>MODBUS SETTINGS and select 19200 Baud Rate. Click Apply
Dashboard | Devices | Events | Setup | About |
Configuration | Site Settings | Network | Time setup | Manage Passwords |
Device Detection | Smart Energy Manager | BMS Setup | Import & export settings | Units |
Modbus settings | Serial Port A Baud rate 19200 Parity none Stop bits 1 Error Limit 3 Timeout (ms) 1000 Apply Cancel |
3. Go to SETUP>Device Detection> input range 1-10. Click Detect.
Dashboard | Devices | Configuration | Detect devices | Network | Manage Passwords |
Port Range | RS-485-1 1 to 10 | Events | Setup | About |
4. Make sure that Insight Home is reading the battery internal parameters
InsightLocal Version: v1.17 | Build number: 79 |
Dashboard | Devices | Events | Setup | About |
Device Overview | Status | Events | Configuration | |
Inverter/Chargers | Charge Controllers | Other Devices | BMS | BMS 0 Online |
Modbus Address 230 | Device Association House Battery Bank 1 | Device Name BMS | Device Number 0 | BMS 0 |
Voltage 53.26 V | Current 0 A | Maximum Discharge Current 168 A | Device Association | |
Temperature 25.00 °C | Maximum Charge Current 126 A | Device Name | ||
SOC 98% | Maximum Charge Voltage 56 V | Device Number | ||
State of Charge 98% | Minimum Discharge Voltage 46.5 V | Serial number | ||
State of Health 100% | Force Charge Low SOC 0 | Unique Identifier | ||
Discharge Over Current Fault 0 | Force Charge Request Calibration 0 | Bus ID | ||
Charge Over Current Fault 0 | Charge Permitted 1 | Bus Address | ||
Under Temperature Fault 0 | Discharge Permitted 1 | Build Number | ||
Over Temperature Fault 0 | ||||
Under Voltage Fault 0 | ||||
Over Voltage Fault 0 | ||||
Cell Voltage Difference Too High Fault 0 | ||||
Communication Error Fault 0 | ||||
System Error Fault 0 | ||||
Discharge Current High Warning 0 | ||||
Charge Current High Warning 0 | ||||
High Temp Warning 0 | ||||
Low Temp Warning 0 | ||||
Voltage High Warning 0 | ||||
Voltage Low Warning 0 | ||||
Cell Voltage Difference Too High Warning 0 | ||||
Communication Error Warning 0 |
5. Associate Battery as House Battery Bank 1
InsightLocal Version: v1.17 | Build number: 79 |
Dashboard | Devices | Events | Setup | About |
Other: BMS 0 Change Selection | Status | Events | Configuration | |
Device Overview | ||||
Inverter/Chargers | Charge Controllers | Other Devices | BMS DEV | BMS 0 Online |
Parameter Settings
Charger Settings
Recharge Voltage ? 46 V | Charge Block Start ? 12 00 AM | |
Recharge SOC? 20 % | Recharge SOC Delay ? 60 S | Charge Block Stop? 12 00 AM |
PARAMETER | VALUE |
CHARGER SETTINGS | |
RECHARGE VOLTAGE | 46V |
RECHARGE SOC | 20% |
RECHARGE DELAY | 60s |
BATTERY SETTINGS | |
BATTERY TYPE | LI-ION |
CHARGE CYCLE | EXTERNAL BMS |
SOC CONTROL ENABLE | Enabled |
BATTERY BANK CAPACITY | 200aH per eForce |
MAXIMUM CHARGE RATE | 100% |
MAXIMUM BULK CHARGE CURRENT | 120A per eForce |
MAXIMUM ABSORPTION CHARGE CURRENT | 120A per eForce |
MAXIMUM FLOAR CHARGE | 120A per eForce |
DEFAULT BATTERY TEMPERATURE | WARM |
ABSORPTION TIME | 3600 |
BULK/BOOST VOLTAGE | 51.5 |
ABSORPTION VOLTAGE SET POINT | 51.5 |
MAXIMUM DISCHARGE CURRENT | 160A per eForce |
MAXIMUM DISCHARGE TIME INTERVAL | 8 |
LOW BATTERY CUT OUT | 44.8V |
LOW BATTERY CUT OUT DELAY | 10s |
LOW BATTERY CUT OUT HYSTERESIS | 2 |
LOW BATTERY CUTOUT WARNING OFFSET | 2 |
HIGH BATTERY CUT OUT | 58V |
CHARGE CYCLE TIMEOUT | 1440s |
HIGH SOC CUT OUT | 99% |
HIGH SOC CUT OUT DELAY | 2s |
LOW SOC CUT OUT | 15% |
LOW SOC CUT OUT DELAY | 60s |
VICTRON
Setup Steps
1 | Device List Quattro 48/3000/35-2x50 120V Notifications Settings Pages | 2 | Settings GPS Generator start/stop Tank pump Relay Services 1/0 Pages | 3 | Services Modbus TCP MQTT on LAN (SSL) VE.Can port BMS-Can port Pages | 4 | VE.Can port CAN-bus profile VE.Can & Lynx lon BMS (250 kbit/s) Devices NMEA2000-out Unique identity number selector 1 Above selector sets which block of unique identity numbers to use for the NAME Unique Identity Numbers in the PGN 60928 NAME field. Change only when using Pages |
5 | CAN-bus profile Disabled VE.Can & Lynx lon BMS (250 kbit/s) VE.Can & CAN-bus BMS (250 kbit/s) CAN-bus BMS (500 kbit/s) Oceanvolt (250 kbit/s) | 6 | Device List CAN-bus BMS battery 84% 52.40V -3.5A Quattro 48/3000/35-2x50 120V Notifications Settings |