Fisher Type EZR Pilot-Operated Regulator

Instruction Manual D103681X012 | January 2020

Summary

This document provides a comprehensive overview of the Fisher Type EZR Pilot-Operated Regulator, detailing its specifications, operation, installation, and maintenance procedures.

Introduction

The Type EZR is a pilot-operated regulator designed for use in transmission and distribution networks, as well as industrial and commercial pipeline applications. It can be equipped with an optional Type OS2 slam shut for rapid gas flow cutoff in cases of under or over outlet pressure.

Description

Main Valve

The Type EZR consists of:

The Type EZR conforms to the PED 2014/68/EU and is classified in Category IV.

Pilot Options

Regulator Options

Characteristics

Table 1. General Characteristics for Type EZR Regulator

Characteristic PS TS SLAM SHUT Accuracy Set point range Accuracy
Operating pressure 72.4 bar(1) -17/66°C(1) - - -
Outlet pressure - - 0.35 to 69 bar 2.5-5 2.5-5
Minimum differential PN 20: 2 to 3 bar - - - -
Maximum operating differential PN 50: 18.6 bar - - - -
Max emergency differential PN 100: 50.0 bar - - - -
Accuracy 72.4 bar - - - 5 (Piston) up to 100 bar

(1) Values correspond to the characteristics of the regulator diaphragm.

Table 2. Pressure and Temperature Characteristics

Body Pmax (bar) Tmin (°C) Tmax (°C)
A216WCB 96.7 -20 71
A352LCC 100 -30 71

The regulator body and the slam shut have been designed to support different pressure and temperature levels.

Flow Coefficients and Valve Plug Travel

Table 3. Flow Coefficients and Valve Plug Travel Information

Coefficients Capacity DN 25 DN 50 DN 80 DN 100 DN 150
Cg 100% 480 1800 3400 5550 11200
60% 290 1020 1970 3300 7150
30% 140 560 970 1690 3570
C1 100% 33 36 37 38 36
60% 29 28 29 27 30
30% 30 29 26 26 26
Valve plug travel (mm) 35 35 50 50 50

Pilot Pressure Ranges

Table 4. Pilot Pressure Ranges

Type Outlet Pressure Range, bar Spring Color Part Number
PRX/120
PRX/125
1.0 to 1.8 Yellow M0255240X12
1.8 to 3.0 Green M0255230X12
3.0 to 5.5 Blue M0255180X12
5.5 to 8.5 Black M0255220X12
8.5 to 14.5 Silver M0255210X12
14.5 to 23.0 Gold M0255200X12
23.0 to 30.0 Aluminium M0255860X12
30.0 to 40.0 Red M0255190X12
PRX/120-AP
PRX/125-AP
30.0 to 80.0 Clear M0273790X12
161EB
161EBM
0.35 to 1.0 White 17B1260X012
0.69 to 2.8 Yellow 17B1262X012
2.1 to 5.2 Black 17B1259X012
4.8 to 9.7 Green 17B1261X012
9.0 to 13.8 Blue 17B1263X012
13.8 to 24.1 Red 17B1264X012
161EBΗ
161EBΗΜ
17.2 to 31.0 Blue 17B1263X012
27.6 to 48.2 Red 17B1264X012

Materials

Regulator:

Pilot:

Connections

Inlet / Outlet:

Labelling

The regulator label provides essential information including model, size (DN), pressure ratings (PN), certifications, serial number, and manufacturing date. Figure 2 shows a typical regulator label, and Figure 3 shows a label for a regulator with an OS2 Slam Shut.

Key information on the label includes:

Operation

Regulator

The Type EZR is a pilot-driven, diaphragm/plug regulator. Tight shutoff is achieved through the combined force of the diaphragm/plug against the slotted cage, the closing spring, and inlet pressure.

Slam Shut

The safety manometric box (BMS) senses the pressure in the protected zone. If this pressure exceeds the set tripping pressure, the release relay opens the valve plug, causing it to close on the orifice due to spring force and fluid pressure. Flow is obstructed until the fault is corrected and the mechanism box is manually reset. Reopening requires equal pressure balance on inlet and outlet sides.

Dimensions and Weights

Detailed dimensions and weights for various configurations of the Type EZR and EZR-OS2 regulators, including different pilot types and flange ratings, are provided in the following tables and figures.

Table 5. Dimensions (mm) - Type EZR-OS2 (part 1)

Body DNBCEHType 161EB PilotType PRX Pilot
25233315348252250-
50243330357261265-
80361366410314301-
100393410454358345-
150423396468372332-

Table 6. Weights (kg) - Type EZR-OS2

Body DNCL150 RFCL300 RFCL600 RF
25202122
50394143
80636971
100104113123
150192211244

Table 7. Dimensions (mm) - Type EZR (part 1)

Body DNBCEType 161EB PilotType PRX Pilot
2522062335239-
5022683340245-
80343105392297-
100372137433336-
150420178465368-

Table 8. Weights (kg) - Type EZR

Body DNCL150 RFCL300 RFCL600 RF
25121416
50262731
80505157
100677388
15097108161

Table 9. Dimensions (mm) - Types EZR and EZR-OS2 (part 2)

Body DNPNCLASSADJM
2516 25 40150 300 600-193.5193.5193.51841972106854
50-2542672672542672861656854
805.03173172983173371819554
100-3503683683523683941879554
150-4514734734514735082499554

Table 10. Dimensions (mm) - BMS (Safety Manometric Box)

TypeFG
Diaphragm162181
Piston71204
Bellows74223

Installation

All interventions on the equipment should only be performed by qualified and trained personnel.

WARNING

Personal injury or equipment damage, due to bursting of pressure-containing parts may result if this regulator is over-pressured or is installed where service conditions could exceed the limits given in the Specification section and on the appropriate nameplate, or where conditions exceed any rating of the adjacent piping or piping connections. To avoid such injury or damage, provide pressure-relieving or pressure-limiting devices to prevent service conditions from exceeding those limits. Also, be sure the installation is in compliance with all applicable codes and regulations.

Additionally, physical damage to the regulator could break the pilot off the main valve, causing personal injury and property damage due to bursting of pressure-containing parts. To avoid such injury and damage, install the regulator in a safe location.

WARNING

Only personnel qualified through training and experience should install, operate and maintain a regulator. Before installation, make sure that there is no damage to, or debris in, the regulator. Also make sure that all tubing and piping are clean and unobstructed.

  • The regulator is installed on horizontal pipeline. Version with slam shut, the release relay is situated towards the bottom (see schematic).
  • Installation according to EN12186 recommended.
  • Install according to direction of fluid flow (arrow).
  • When assembling with adjacent elements care must be taken not to create pressure force on the body and the assembling elements (bolts, O-rings, flanges) should be compatible with the geometry and working conditions of the equipment.

Figure 7 illustrates Type EZR Installation Configurations for Regulator, Monitor, and Working Monitor setups.

Operation Schematic

Figure 8 provides a schematic of the Type EZR-OS2 Regulator, illustrating the flow paths for inlet pressure (Pu), modulated pressure (Pm), outlet pressure (Pd), and atmospheric pressure (Pb).

WARNING

If the case arises a support must be used to avoid pressure force on the body (a support can be installed under the flanges). Version with integral slam shut, connect the safety manometric box (IS) to the impulse at 4D on a straight run of the outlet pipe. It is recommended to separate the slam shut impulse line (IS) from that of the pilot (IP). Do not connect the impulses on the lower generator line. It is recommended to install an isolation valve and an atmospheric valve, which can be useful for slam shut tripping and verifications. No modification should be made to the structure of the equipment (drilling, grinding, soldering...). It is recommended to install a servicing valve on the outlet pipeline to facilitate adjustments and bleeding off to the atmosphere. Verify that the inlet side is protected by an appropriate device(s) to avoid exceeding the limits of utilization (PS, TS).

WARNING

Verify that the limits of utilization correspond to the appropriate operating conditions. Version with integral slam shut, verify that the safety manometric box (BMS) and spring correspond to the appropriate operating conditions on the outlet side of the regulator. The equipment should not receive any type of shock, especially the release relay. The user should verify or carry out a protection adapted to the environment. Fire, seismic and lightening are not taken into consideration in standard regulators. If required, a special product selection and/or specific calculations may be supplied according to specific requirements. Version without integral slam shut, verify that a pressure limiting device on the outlet side of the regulator guarantees a pressure limit inferior or equal to the pilot PS.

Commissioning

Operations concerning the integral slam shut version are in italic. All interventions on equipment should only be performed by qualified personnel.

Preliminary Verifications

Positions before commissioning

The equipment is ready for commissioning.

Commissioning (Act slowly)

The equipment is commissioned. It is recommended to seal the release relay.

Maintenance

Servicing Check

Recommended frequency: Twice yearly minimum.

Verification: Set point verification, regulator valve plug tightness, tripping and set point value, slam shut valve tightness.

Departure positions

Inlet and outlet sides of regulator under pressure.

Tightshut verification (and tripping verification for integral slam shut versions)

Table 11. Troubleshooting for Types EZR and EZR-OS2 Regulators

SymptomCauseAction
If the outlet pressure increasesInternal leakControl the regulator valve plug, Control the regulator orifice, Control the pilot, or contact after-sales
If the outlet pressure decreasesExternal leakLocate and seal the leak, or contact after-sales
If the outlet pressure is constantThe regulator is tightshutIncrease the set point until tripping occurs (without exceeding the outlet limits)
If the slam shut valve plug will not closeOperation faultyControl the release relay, Control the slam shut valve plug, or contact after-sales
If the slam shut valve plug closesOperation correctObserve the evolution of the outlet pressure (control tightness)
If the outlet pressure is constantInternal leakPurge the outlet side of the regulator, Control the slam shut valve plug, Control the slam shut orifice, Control the bypass, or contact after-sales
If the outlet pressure increasesInternal leakControl the slam shut valve plug
If the outlet pressure is constantSlam shut valve plug is tightshutControl the bypass

Filter verification

Troubleshooting

Table 13. Troubleshooting for Type EZR Regulator

SYMPTOMSCAUSEACTIONS
If outlet pressure increasesInternal leakControl the regulator valve plug, Control the regulator seat, Control the pilot, or contact after-sales
If inlet pressure decreasesExternal leakLocate and repair leak, or contact after-sales
If inlet pressure is stableThe regulator is tightshutIncrease the set point until tripping occurs (without exceeding the outlet limits)
If the slam shut valve plug will not closeOperation faultyControl the release relay, Control the slam shut valve plug, or contact after-sales
If the slam shut valve plug closesOperation correctObserve the evolution of the outlet pressure (control tightness)
If the outlet pressure is stableInternal leakPurge the outlet side of the regulator
If the outlet pressure increasesInternal leakControl the slam shut valve plug, Control the slam shut seat, Control the bypass, or contact after-sales
If the outlet pressure is stableValve plug is tightshutControl the bypass

Disassembly

Recommended frequency: Every 2 to 6 years (or less depending on operating conditions).

Verification: Condition of O-rings, diaphragms, lubrication.

Replacement: O-rings, diaphragm.

Tools: Dimensions according to tables below.

Preliminary Operations

Pilot

Slam Shut (Version with slam shut)

Reassembly

Slam Shut Reassembly (Version with slam shut)

Spare Parts

Figures 10, 11, and 12 show various pilot types, filters, and restrictors. Table 14 lists the spare parts for the 161EB Series Pilot, Type 112 Restrictor, and Type 252 Filter.

Table 14. 161EB Series Pilot, Type 112 Restrictor and Type 252 Filter Spare Parts List

DescriptionKeyReferencePilot Type
Pilot kit 0.34 to 13.8 bar15R161X000012161EB
Pilot kit 13.8 to 24.1 bar15R161X000022161EB
Pilot kit EBH(M)16R161HX00012161EBH
O-ring171C8538X0052-
Filter cartridge1817B6813X012-
O-ring191F269206992-
SAV kit 0.34 to 13.8 bar(1)197435161EB
SAV kit 13.8 to 24.1 bar(1)197436161EBM
SAV kit 24.1 to 48.3 bar(1)197437161EBΗΜ
Pilot kit 0.34 to 13.8 bar15R161MX00012161EBM
Pilot kit 13.8 to 24.1 bar15R161MX00022161EBM
Pilot kit EBH(M)16R161HMX0012161EBΗΜ
SAV kit 0.34 to 13.8 bar(1)197438161EBM
SAV kit 13.8 to 24.1 bar(1)197439161EBΗΜ
SAV kit 24.1 to 48.3 bar(1)197440-
(1) The SAV kits include item numbers 15 or 16, 17, 18 and 19.

Table 15. Types EZR and EZR-OS2 Spare Parts List

Regulator, Type EZRDescriptionKeyDN / In.Reference
O-ring140000925/140002450/240009180/3400045100/4400262150/6
O-ring219B2838X01218B2124X01218B8514X01218B2140X01219B0359X012
Guide3401950401951401952401953401954
O-ring4400527400263400258400260400261
Bypass5180977180977180977180977180977
SAV kit PN 201 to 14197421197422197424197425197427
SAV kit PN 50/1001 to 14197421197423197424197426197427
SAV kit PN 206 to 14197428197429197431197432197434
SAV kit PN 50/1006 to 14197428197430197431197433197434
O-ring618B3438X01218B3438X01210A8931X01210A8931X01210A3800X012
O-ring71H2926X00321H2926X00321D1917069921D1917069921D191706992
O-ring813A1584X05213A1584X05210A3803X06210A3803X062T12050X0012
O-ring919B2838X01218B2124X01218B8514X01218B2140X01219B0359X012
PN 20 diaphragm1039B2397X01229B2715X02239B2726X01238B5965X01249B0357X012
PN 50/100 diaphragm1039B2397X01228B2123X05239B2726X01239B3996X01249B0357X012
O-ring1113A1584X05213A1584X05210A3803X06210A3803X062T12050X0012
O-ring121E2163069921E2163069921J4888X00521J4888X005211A8741X052
O-ring1314A5713X01210B4428X01210B4366X01210B4373X0121H862306992
O-ring14----1D269206992
Safety manometric box-See D103683X012_OS2_IM manual----

PDF preview unavailable. Download the PDF instead.

manuals-ezr-pressure-reducing-regulator-instruction-manual-europe-middle-east-africa-fisher-en-en-5906372 MCM Plus Adobe PDF Library 15.0; modified using iTextSharp™ 5.5.10 ©2000-2016 iText Group NV (AGPL-version)

Related Documents

Preview Fisher 299H Series Pressure Reducing Regulators Instruction Manual
Comprehensive instruction manual for Fisher 299H Series pressure reducing regulators, covering installation, adjustment, maintenance, and parts ordering. Designed for broad capacity in distribution, industrial, and commercial applications, these regulators feature integral pilots and handle inlet pressures up to 175 psi.
Preview Fisher Type 114PL High-Pressure Reducing and Low-Flow System: Instruction Manual
Instruction manual for the Fisher Type 114PL High-Pressure Reducing and Low-Flow System. Covers installation, startup, adjustment, maintenance, specifications, operational schematics, safety warnings, and parts ordering. Includes model numbers D104438X012, BSL85, and RPE.
Preview Fisher 299H Series Pressure Reducing Regulators Instruction Manual
Comprehensive instruction manual for Fisher 299H Series pressure reducing regulators, covering installation, adjustment, maintenance, specifications, and parts ordering. Includes details on 299H, 299HR, 299HV, and 299HVR models, their operation, and safety warnings for industrial and commercial applications.
Preview Fisher Type Y693 Gas Blanketing Regulator Instruction Manual
Instruction manual for the Fisher Type Y693 Gas Blanketing Regulator, covering installation, startup, maintenance, and parts information. Includes specifications, operating principles, and safety warnings.
Preview Fisher 1261-R and 1261-E Self-Operated Control Valves Instruction Manual
This instruction manual provides comprehensive guidance for the Fisher 1261-R and 1261-E self-operated control valves. It details product descriptions, specifications, installation procedures, maintenance guidelines (including packing and trim), parts ordering, and dimensional data. The manual is essential for proper installation, operation, and maintenance to ensure safety and optimal performance.
Preview Fisher Actuator Sizing Guide for Sliding-Stem Valves
This guide provides comprehensive information on sizing Fisher actuators for sliding-stem valves using both the AP Method and the Force Method. It includes detailed tables and procedures to help engineers and technicians select the appropriate actuator for various control valve applications.
Preview Fisher FIELDVUE DVC6200 Digital Valve Controllers - Product Information
Information on the Fisher FIELDVUE DVC6200 Digital Valve Controllers, including safety precautions, installation, operation, and maintenance guidelines. The document is available in multiple languages.
Preview Fisher FIELDVUE DVC6200p Digital Valve Controller - Safety and Operation Guide
This document provides essential safety information and operational guidelines for the Fisher FIELDVUE DVC6200p Digital Valve Controller. It emphasizes the need for trained personnel and careful adherence to documentation to prevent injury or damage. The guide is available in multiple languages.