Danfoss EKC 331T Capacity Controller
Model: EKC 331T
Manufacturer: Danfoss
Document Type: Manual
Introduction
Application
The controller is used for capacity regulation of compressors or condensers in small refrigerating systems. Regulation can be carried out with up to four identical capacity steps.
Advantages
- Patented neutral zone regulation
- Sequential or cyclic operation
Functions
- Regulation: Regulation with up to four relay outputs can be carried out. Regulation takes place with a set reference which is compared to a signal from a pressure transmitter or a temperature sensor.
- Relay module: It is possible to use the controller as a relay module, so that the relays are cut in or out by means of an external voltage signal.
- Alarm function: A relay becomes activated when the set alarm limits are exceeded.
- Digital input: The digital input can be used for:
- Night operation where the suction pressure is raised
- Heat recovery where the condensing pressure is raised
- External start/stop of the regulation.
- Monitoring of safety circuit
- Reverse function: The regulation can be reversed so that the relays are activated in case of falling temperature, rather than by the rising temperature.
- Possibility of data communication
Display
A signal from a pressure transmitter will always be converted and shown as a temperature value. Settings are made as for temperature values.
Function: Capacity Regulation
The cut-in capacity is controlled by signals from the connected pressure transmitter (temperature sensor) and the set reference. Outside the reference, a neutral zone is set where the capacity will neither be cut in nor out.
Outside the neutral zone (in the hatched areas named +zone and -zone), the capacity will be cut in or out if the regulation registers a change of pressure (or temperature) "away" from the neutral zone. Cut-in and cut-out will take place with the set time delays. If the pressure (or temperature) however "approaches" the neutral zone, the controller will make no changes of the cut-in capacity.
If regulation takes place outside the hatched area (named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if it were in the hatched area.
Cut-in of steps can be defined for either sequential or cyclic operation.
Diagram: Capacity Regulation Zones illustrates pressure/temperature zones relative to a reference (REF). The zones are: ++Zone (fastest response), +Zone (response), NZ (Neutral Zone), -Zone (response), --Zone (fastest response). Arrows indicate pressure/temperature changes and their effect on capacity regulation.
Operating Modes
Sequential Operation
Relays are cut in sequentially (1, 2, 3, etc.). Cut-out occurs in the opposite sequence (last cut-in relay is cut out first).
Diagram: Sequential Operation shows capacity steps (R1, R2, R3, R4) increasing over time, illustrating sequential cut-in. The corresponding cut-out phase shows the reverse sequence.
Cyclic Operation
Relays are coupled to equalize operating time. At each cut-in, the relay with the least operating time is selected. At each cut-out, the relay with the most operating time is selected.
Rx
represents a random relay, and h
represents the number of hours.
Diagram: Cyclic Operation shows capacity steps (R1, R2, R3, R4) with varying operating hours (h, h+, h++, h+++), illustrating how the relay with the least time is chosen for cut-in and the one with the most time for cut-out.
Compressor and Unloader Operation
For capacity regulation on two compressors with one unloader each:
- Relays 1 and 3 are connected to the compressor motors.
- Relays 2 and 4 are connected to the unloaders.
- Relays 1 and 3 operate to equalize operating time between the two compressors.
C
= compressor, L
= Unloader.
Diagram: Compressor and Unloader Operation illustrates the relationship between compressor (Ch, Ch+) and unloader (Lh, Lh+) states over time, showing how unloaders are managed in conjunction with compressor operation.
Relay Module
The controller can function as a relay module, with relays activated by an external voltage signal connected to terminal 15-16. Hysteresis at coupling points prevents unwanted relay switching.
Survey of Functions
Normal Display
Shows the signal from the pressure transmitter/temperature sensor. If used as a relay module, 'Uin' appears.
Pressure Regulation
Function | Parameter | Parameter by operation via data communication |
---|---|---|
Regulation setpoint | - | Set point°C |
Regulation is based on the set value. A change of the set value can be limited/fixed by means of settings in r02 and r03. (Push both buttons simultaneously to set the menu.) | ||
Neutral zone | r01 | Neutral zone |
There is a neutral zone around the reference. See also page 2. | ||
Start/stop of refrigeration | r12 | Main switch |
With this setting, refrigeration can be started and stopped. Start/stop may also be performed with an external contact function connected to the input named "DI". | ||
Reference | r13 | Ref. offset |
The set reference may be displaced with a fixed value when a signal is received at the DI input. Regulation will then be based on the set point plus the value set here. (Cf. also Definition of DI input). | ||
Night setback | r27 | NightSetback |
OFF: No change of the reference. ON: (1) Offset value in "r13" forms part of the reference. The total reference can be seen when you push the lower of the two buttons. | - | Reference |
Reference limitation | ||
With these settings, the setpoint can only be set between the two values. (This also applies if regulation with displacements of the reference). | ||
Max. permissible reference value. | r25 | Max. reference |
Min. permissible reference value. | r26 | Min. reference |
Correction of temperature measurement | r04 | Adjust sensor |
An offset adjustment of the registered temperature can be made. The function is used if correction for a too long sensor cable has to be made. | ||
Unit | r05 | (In AKM only °C and bar is used, whatever the setting) |
Here you can select whether the display is to indicate SI units or US units (°C and bar or °F and psig). Setting = "C-b" will give °C and bar. Setting = "F-P" will give °F and psig. All settings made in °C or °F. Excluding o20 and o21, which are set in bar / PSIG. |
Capacity Settings
Function | Parameter | Parameter by operation via data communication |
---|---|---|
Running time | ||
To prevent frequent start/stop, values have to be set for how the relays are to cut in and out. | ||
Min. ON time for relays. | c01 | Min.ON time |
Min. time period between cutin of same relay. | c07 | Recycle time |
Coupling (compressor and condensor) | c08 | Step mode |
Cutin and cutout can take place in three ways: 1. Sequential: First relay 1 cuts in, then relay 2, etc. Cutout takes place in the opposite sequence. ("First in, last out"). 2. Cyclic: An automatic operating time equalisation is arranged here, so that all steps will have the same operating time. (The relay with the fewest number of operating hours cuts in or out before the others) (Or put differently: "First in, last out"). 3. Compressor(s) with unloader: The cyclic operation is performed on relays 1 and 3. The unloaders are mounted on relays 2 and 4 (relays 1 and 2 belong to the first compressor, relays 3 and 4 to the other). The above mentioned "Min. On-time" and "Min. recycle time" are not used for unloaders. In connection with cutout, the two unloaders are cut out before the compressors are cut out. | ||
Unloaders' cutin and cutout mode (Only in connection with cutin/cutout mode 3. See above). The relays for the two unloaders can be set to switch on when more capacity is required (setting = no), or they can switch off when more capacity is called for (setting = nc). | c09 | Unloader (switch on = 0) (switch off = 1) |
Detailed Function Settings
Setting for Neutral Zone Regulation
Function | Parameter | Parameter by operation via data communication |
---|---|---|
Regulation band under the neutral zone | c10 | + Zone K |
Time delay between step cut-ins in the regulation band over the neutral zone | c11 | + Zone m |
Time delay between step cut-ins in the regulation band over the "+Zone band". | c12 | + + Zone s |
Regulation band over the neutral zone | c13 | - Zone K |
Time delay between step cut-outs in the regulation band under the neutral zone | c14 | - Zone m |
Time delay between step cut-outs in the regulation band under the "-Zone band" | c15 | - - Zone s |
Manual Control of Compressor Capacity
Function | Parameter | Parameter by operation via data communication |
---|---|---|
This sets the capacity that is to be cut in when switching to manual control. | c31 | ManualCap % |
Manual control of the compressor capacity is enabled here. When set to ON, the capacity that is set in "c31" is cut in. | c32 | ManualCap |
Alarm Settings
Function | Parameter | Parameter by operation via data communication |
---|---|---|
The controller can give alarm in different situations. When there is an alarm, all the light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay will cut in. | ||
Upper deviation | A10 | Max. Al. limit |
Here you set when the alarm at high temperature/pressure is to enter into effect. The value is set as an absolute value. See also emergency procedure page 7. | ||
Lower deviation | A11 | Min. Al. limit |
Here you set when the alarm at low temperature/pressure is to enter into effect. The value is set as an absolute value. See also emergency procedure page 7. | ||
Alarm delay | A03 | Alarm delay |
If one of the two limit values is exceeded, a timer function will commence. The alarm will not become active until the set time delay has been passed. The time delay is set in minutes. | ||
Give the top button a brief push to zeroset the alarm and to have the message shown on the display. | Reset alarm | |
The function zerosets all alarms when set in pos. ON. With data communication, the importance of the individual alarms can be defined. Setting is carried out in the "Alarm destinations" menu. |
Miscellaneous
Function | Parameter | Parameter by operation via data communication |
---|---|---|
External signal | o10 | Application mode |
Here you set the signal to be connected to the controller. 0: No signal/regulation stopped (display will then show OFF) 1: 4-20 mA from pressure transmitter for compressor regulation 2: 4-20 mA from pressure transmitter for condenser regulation 3: Pressure transmitter type AKS 32R for compressor regulation 4: Pressure transmitter type AKS 32R for condenser regulation 5: 0-10 V from other regulation 6: 0-5 V from other regulation 7: 5-10 V from other regulation 8: Pt1000 ohm temperature sensor for compressor regulation 9: Pt1000 ohm temperature sensor for condenser regulation 10: PTC1000 ohm temperature sensor for compressor regulation 11: PTC1000 ohm temperature sensor for condenser regulation | ||
Number of relays | o19 | Number of steps |
Depending on the application, up to four relays may be used. This number must be set in the controller. (The relays are always used in numerical sequence). | ||
Pressure transmitter's working range | ||
Depending on the pressure, a pressure transmitter with a given working range is used. This working range must be set in the controller (e.g.: -1 to 12 bar). The values must be set in bar if display in °C has been selected. And in psig, if °F has been selected. | ||
Min. value | o20 | Min. Trs. pres |
Max. value | o21 | Max Trs. pres |
If the two values are to be set from the AKM programme, they must be set in bar. |
Controller Settings and Operation
DI Input Usage
The digital input can be connected to a contact function, and the contact can now be used for one of the following functions:
- 0: DI input not used
- 1: Regulation reference displaced when contact is cut in
- 2: Regulation is started and stopped when the contact is cut in and out, respectively.
- 3: Monitoring of the compressor's safety circuit. When the contact on the DI input cuts out, all relay outputs will immediately be cut out. At the same time, the alarm will sound.
Parameter: o22, Function: Di control
Operating Hours
The operating hours for the four relays can be read in the following menus. The read value is multiplied by 1000 to obtain the number of hours. On reaching 999 hours, the display stops and must be reset to 0. There will be no alarm or error message for counter overflow.
(In the AKM display, the hour number has not been multiplied)
- Value for relay number 1: Parameter: o23, Function: DO 1 run hour
- Value for relay number 2: Parameter: o24, Function: DO 2 run hour
- Value for relay number 3: Parameter: o25, Function: DO 3 run hour
- Value for relay number 4: Parameter: o26, Function: DO 4 run hour
Refrigerant Setting
Before refrigeration is started, the refrigerant must be defined. You may choose between the following refrigerants:
Parameter: o30, Function: Refrigerant
List of refrigerants (e.g., 1=R12, 2=R22, ..., 37=R407F). Warning: Wrong selection of refrigerant may cause damage to the compressor.
Manual Control
From this menu, relays can be cut in and out manually. OFF gives no override, but a number between 1 and 4 will cut in a corresponding relay. The other relays will be off.
Parameter: o18
Frequency
Set the net frequency.
Parameter: o12, Function: 50/60 Hz (50=0, 60=1)
Address
If the controller is built into a network with data communication, it must have an address, and the master gateway must know this address. These settings can only be made when a data communication module has been mounted and the cable installation is completed (see document "RC.8A.C"). The address is set between 1 and 60. The address is sent to the gateway when the menu is set to ON.
Parameter: o03
Access Code
To protect settings with a numerical code, set a value between 0 and 100. To cancel, set to OFF.
Parameter: o05
Cooling or Heating
Cooling: Relays are cut in when the temperature is above the reference. Heating: Relays are cut in when the temperature is below the reference.
Parameter: o07, Function: Refg./Heat
Operating Status and Alarms
Operating Status
The controller displays status codes when waiting for the next regulation point. Push the upper button briefly (1s) to view status codes. The individual status codes have the following meanings:
Status Code | Meaning | EKC state (0 = regulation) |
---|---|---|
S2 | When the relay is operated, it must be activated for min. x minutes (cf. C01) | 2 |
S5 | Renewed cut-in of the same relay must not take place more often than every x minutes (cf. C07) | 5 |
S8 | The next relay must not cut in until x minutes have elapsed (cf. C11-C12) | 8 |
S9 | The next relay must not cut out until x minutes have elapsed (cf. C14-C15) | 9 |
S10 | Regulation stopped with the internal or external start/stop | 10 |
S20 | Emergency control | 20 |
S25 | Manual regulation of outputs | 25 |
PS | Password required. Set password | PS |
Alarm Messages
Alarm Code | Message | Alarms |
---|---|---|
A1 | High temperature alarm (cf. A10) | High temp. alarm |
A2 | Low temperature alarm (cf. A11) | Low temp. alarm |
A11 | No refrigerant has been selected (cf. o30) | RFG not selected |
A12 | Regulation stopped due to interrupted signal on the DI input | DI Alarm |
A45 | Regulation stopped with setting or with external switch | A45 Stand by |
E1 | Error in the controller | Controller fault |
E2 | Control signal outside the range (short-circuited/interrupted) | Out of range |
Service
- u07: Voltage signal on the analogue input
- u10: Status on DI- input
- u15: Status on relay output DO1
- u25: Signal on pressure transmitter input (bar / PSIG)
- u58: Status on relay output DO2
- u59: Status on relay output DO3
- u60: Status on relay output DO4
- u62: Status on relay output "alarm"
Warning! Direct start of compressors
To prevent compressor breakdown, parameter c01 and c07 should be set according to supplier requirements or in general:
- Hermetic Compressors: c07 min. 5 minutes
- Semihermetic Compressors: c07 min. 8 minutes and c01 min. 2 to 5 minutes (Motor from 5 to 15 KW)
*) Direct activating of solenoid valves does not require settings different from factory (0).
Emergency Procedure
If the controller registers irregularities in the registered signals, it will start an emergency procedure:
For compressor regulation:
- If the signal from the temperature sensor/pressure transmitter becomes smaller than expected, the controller will continue operating with the average capacity that has been cut in during the past 60 minutes. This cut-in capacity will gradually decline as time passes.
- If the signal becomes smaller than the set value of A11, the capacity will instantly be cut out.
For condenser regulation:
- If the signal from the temperature sensor/pressure transmitter becomes smaller than expected, or if the condensing pressure becomes bigger than the set value of A10, the entire capacity will instantly be cut in.
Operation and Menu Survey
Display
Values are shown with three digits. The setting determines whether temperature is shown in °C or °F.
Display: A three-digit numerical display.
Light-emitting diodes (LED) on front panel
Four LEDs indicate when relays are operated. All LEDs flash if there is an error. Error codes can be uploaded to the display and alarms cancelled by pushing the top button briefly.
Controller Messages
Code | Message |
---|---|
E1 | Errors in the controller |
E2 | Regulation out of range or control signal is defect. |
A1 | High pressure alarm |
A2 | Low pressure alarm |
A11 | No refrigerant selected |
A12 | Regulation stopped due to interrupted signal on the DI input |
A45 | Regulation is stopped |
PS | Password is required |
The Buttons
To change a setting, use the two buttons to increase or decrease the value. Access the menu by pushing the upper button for a couple of seconds. Find the parameter code and push both buttons simultaneously to change the value. Save the new value by pushing both buttons simultaneously again.
- [Menu/Alarm Reset]: Gives access to the menu (or cuts out an alarm).
- [Change]: Gives access to changes.
- [Save]: Saves a change.
Examples of Operations
Set the regulation's set point
- Push the two buttons simultaneously.
- Push one of the buttons and select the new value.
- Push both buttons again to conclude the setting.
Set one of the other menus
- Push the upper button until a parameter is shown.
- Push one of the buttons and find the parameter you want to change.
- Push both buttons simultaneously until the parameter value is shown.
- Push one of the buttons and select the new value.
- Push both buttons again to conclude the setting.
Menu Survey
Function | Parameter | Min. | Max. | SW: 2.0x Factory setting |
---|---|---|---|---|
Normal display | °C | |||
Shows the signal from the temperature sensor / pressure transmitter | ||||
Reference | ||||
Set the regulation's set point | - | -60 °C | 170 °C | 3 |
Neutral zone | r01 | 0.1 K | 20 K | 4.0 |
Correction of signal from the sensor | r04 | -20 K | 20 K | 0.0 |
Select SI or US display: 0=SI (bar/°C). 1=US (Psig/°F) | r05 | c-b | F-P | c-b |
Start/stop of regulation (0=off) | r12 | 0 | 1 | 0 |
Reference displacement by signal at DI input | r13 | -50 K | 50 K | 0 |
Reference limitation. Max. value | r25 | -50°C | 170°C | 50°C |
Reference limitation. Min. value | r26 | -60°C | 50°C | -60°C |
Displacement of reference (On=activ "r13") | r27 | Off | On | Off |
Capacity | ||||
Min. ON time for relays | c01 | 0 min. | 30 min | 2 |
Min. time period between cutins of same relay | c07 | 0 min. | 60 min. | 4 |
Definition of regulation mode 1: Sequential (step mode / FILO) 2: Cyclic (step mode / FIFO) 3: Compressor with unloader If the regulation mode 3 has been selected, the relays for the unloaders can be defined to: no: Cut in when more capacity is required nc: Cut out when more capacity is required | c08 | 1 | 3 | 1 |
Regulation parameter for + Zone | c10 | 0.1 K | 20 K | 3 |
Regulation parameter for + Zone min. | c11 | 0.1 min. | 60 min. | 2 |
Regulation parameter for ++ Zone seconds | c12 | 1 s | 180 s | 30 |
Regulation parameter for - Zone | c13 | 0.1 K | 20 K | 3 |
Regulation parameter for - Zone min. | c14 | 0.1 min. | 60 min. | 1 |
Regulation parameter for - - Zone seconds | c15 | 1 s | 180 s | 30 |
Cutin capacity at manual control. See also "c32" | c31 | 0% | 100% | 0% |
Manual control of capacity (when On the value in "c31" will be used*) | c32 | Off | On | Off |
Alarm | ||||
Alarm time delay | A03 | 1 min. | 90 min. | 30 |
Upper alarm limit (absolute value) | A10 | -60 °C | 170 °C | 50 |
Lower alarm limit (absolute value) | A11 | -60 °C | 120 °C | -60 |
Miscellaneous | ||||
Controllers address | o03* | 1 | 240 | 0 |
On/off switch (service-pin message) | o04* | - | - | - |
Access code | o05 | off(-1) | 100 | - |
Inverse function (HE: heating at relays = on) | o07 | rE | HE | rE |
Define input signal and application: 0: no signal / regulation stopped 1: 4-20 mA pressure transmitter - compressor reg. 2: 4-20 mA pressure transmitter - condenser reg. 3: AKS 32R pressure transmitter - compressor reg. 4: AKS 32R pressure transmitter - condenser reg. 5: 0-10 V relay module 6: 0-5 V relay module 7: 5-10 V relay module 8: Pt 1000 ohm sensor - compressor reg. 9: Pt 1000 ohm sensor - condenser reg. 10: PTC 1000 ohm sensor - compressor reg. 11: PTC 1000 ohm sensor - condenser reg. | o10 | 0 | 11 | 0 |
Set supply voltage frequency | o12 | 50 Hz | 60 Hz | 50 |
Manual operation with "x" relays | o18 | 0 | 4 | 0 |
Data
Function | Parameter | Min. | Max. | SW: 2.0x Factory setting |
---|---|---|---|---|
Define number of relay outputs | o19 | 1 | 4 | 4 |
Pressure transmitter's working range - min. value | o20 | -1 bar | 5 bar | -1 |
Pressure transmitter's working range - max. value | o21 | 6 bar | 199 bar | 12 |
Define DI input: 0: not used 1: Contact displaces reference 2: Contact starts and stops regulation 3: Interrupted contact will cut out the capacity, and alarm will be given. | o22 | 0 | 3 | 0 |
Operating hours of relay 1 (value times 1000) | o23 | 0 h | 99.9 h | 0 |
Operating hours of relay 2 (value times 1000) | o24 | 0 h | 99.9 h | 0 |
Operating hours of relay 3 (value times 1000) | o25 | 0 h | 99.9 h | 0 |
Operating hours of relay 4 (value times 1000) | o26 | 0 h | 99.9 h | 0 |
Setting of refrigerant 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User defined. 14=R32. 15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=XP10. 37=R407F. *) This setting will only be possible if a data communication moduel has been installed in the controller. | o30 | 0 | 37 | 0 |
Service
Function | Parameter |
---|---|
Voltage on the analogue input | u07 |
Status on DI- input | u10 |
Status on relay output DO1 | u15 |
Signal on pressure transmitter input (bar / PSIG) | u25 |
Status on relay output DO2 | u58 |
Status on relay output DO3 | u59 |
Status on relay output DO4 | u60 |
Status on relay output "alarm" | u62 |
Factory setting
To return to factory-set values:
- Cut out the supply voltage to the controller.
- Keep both buttons depressed simultaneously while reconnecting the supply voltage.
Data
Specification | Value | |
---|---|---|
Supply voltage | 230 V a.c. +/-15% 50/60 Hz, 5 VA | |
Input signal | Pressure transmitter*) with 4-20 mA or temperature sensor Pt 1000 ohm or temperature sensor PTC 1000 ohm or voltage signal (0 - 5 V, 0-10V or 5-10V) | |
Digital input to external contact function | ||
Relay output | 4 pcs. SPST | AC-1: 4 A (ohmic) AC-15: 3 A (inductive) |
Alarmrelay | 1 pcs. SPST | AC-1: 4 A (ohmic) AC-15: 1 A (inductive) |
Data communication | Possible to connect a data communication module | |
Environments | -10 - 55°C, during operation -40 - 70°C, during transport | |
20-80% Rh, not condensed | ||
No shock influence / vibrations | ||
Enclosure | IP 20 | |
Weight | 300 g | |
Mounting | DIN rail | |
Display | LED, 3 digits | |
Terminals | max. 2.5 mm² multicore | |
Approvals | EU Low voltage Directive and EMC demands re CE-marking complied with. LVD-tested acc. to EN 60730-1 and EN 60730-2-9 EMC-tested acc. to EN 61000-6-3 and EN 61000-4-(2-6,8,11) |
*) Pressure transmitter: As pressure transmitter can be used AKS 3000 or AKS 33 (AKS 33 has a higher accuracy than AKS 3000). It is also possible to use an AKS 32R. Please refer to catalogue RKOYG...
Ordering
Type | Function | Code No. |
---|---|---|
EKC 331T | Capacity controller | 084B7105 |
EKA 175 | Data communication module (accessories), (RS 485 module) | 084B8579 |
Connections
Necessary connections
Terminals:
- 25-26: Supply voltage 230 V a.c.
- 3-10: Relay connections no. 1, 2, 3 and 4
- 12-13: Alarm relay. There is connection between 12 and 13 in alarm situations and when the controller is dead.
Control signal (see also o10)
Either terminals:
- 14-16: Voltage signal from AKS 32R
- 17-18: Current signal from AKS 3000 or AKS 33
- 15-16: Sensor signal from AKS 21, AKS 12 or EKS 111
- 15-16: Voltage signal from an other regulation.
External contact function, if applicable
19-20: Contact function for displacement of reference or start/stop of the regulation or for monitoring of safety circuit.
Data communication, if applicable
21-22: Mount only, if a data communication module has been mounted. It is important that the installation of the data communication cable be done correctly. Cf. separate literature No. RC8AC...
Diagram: Controller Connections shows terminal blocks and connections for supply voltage, relays, alarm, control signals (AKS 32R, AKS 33, AKS 21, 0-10V), DI input, and data communication.
General Information
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
ADAP-KOOL® is a registered trademark.