Danfoss EKC 331T Capacity Controller

Model: EKC 331T

Manufacturer: Danfoss

Document Type: Manual

Introduction

Application

The controller is used for capacity regulation of compressors or condensers in small refrigerating systems. Regulation can be carried out with up to four identical capacity steps.

Advantages

Functions

Display

A signal from a pressure transmitter will always be converted and shown as a temperature value. Settings are made as for temperature values.

Function: Capacity Regulation

The cut-in capacity is controlled by signals from the connected pressure transmitter (temperature sensor) and the set reference. Outside the reference, a neutral zone is set where the capacity will neither be cut in nor out.

Outside the neutral zone (in the hatched areas named +zone and -zone), the capacity will be cut in or out if the regulation registers a change of pressure (or temperature) "away" from the neutral zone. Cut-in and cut-out will take place with the set time delays. If the pressure (or temperature) however "approaches" the neutral zone, the controller will make no changes of the cut-in capacity.

If regulation takes place outside the hatched area (named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if it were in the hatched area.

Cut-in of steps can be defined for either sequential or cyclic operation.

Diagram: Capacity Regulation Zones illustrates pressure/temperature zones relative to a reference (REF). The zones are: ++Zone (fastest response), +Zone (response), NZ (Neutral Zone), -Zone (response), --Zone (fastest response). Arrows indicate pressure/temperature changes and their effect on capacity regulation.

Operating Modes

Sequential Operation

Relays are cut in sequentially (1, 2, 3, etc.). Cut-out occurs in the opposite sequence (last cut-in relay is cut out first).

Diagram: Sequential Operation shows capacity steps (R1, R2, R3, R4) increasing over time, illustrating sequential cut-in. The corresponding cut-out phase shows the reverse sequence.

Cyclic Operation

Relays are coupled to equalize operating time. At each cut-in, the relay with the least operating time is selected. At each cut-out, the relay with the most operating time is selected.

Rx represents a random relay, and h represents the number of hours.

Diagram: Cyclic Operation shows capacity steps (R1, R2, R3, R4) with varying operating hours (h, h+, h++, h+++), illustrating how the relay with the least time is chosen for cut-in and the one with the most time for cut-out.

Compressor and Unloader Operation

For capacity regulation on two compressors with one unloader each:

C = compressor, L = Unloader.

Diagram: Compressor and Unloader Operation illustrates the relationship between compressor (Ch, Ch+) and unloader (Lh, Lh+) states over time, showing how unloaders are managed in conjunction with compressor operation.

Relay Module

The controller can function as a relay module, with relays activated by an external voltage signal connected to terminal 15-16. Hysteresis at coupling points prevents unwanted relay switching.

Survey of Functions

Normal Display

Shows the signal from the pressure transmitter/temperature sensor. If used as a relay module, 'Uin' appears.

Pressure Regulation

Function Parameter Parameter by operation via data communication
Regulation setpoint-Set point°C
Regulation is based on the set value. A change of the set value can be limited/fixed by means of settings in r02 and r03. (Push both buttons simultaneously to set the menu.)
Neutral zoner01Neutral zone
There is a neutral zone around the reference. See also page 2.
Start/stop of refrigerationr12Main switch
With this setting, refrigeration can be started and stopped. Start/stop may also be performed with an external contact function connected to the input named "DI".
Referencer13Ref. offset
The set reference may be displaced with a fixed value when a signal is received at the DI input. Regulation will then be based on the set point plus the value set here. (Cf. also Definition of DI input).
Night setbackr27NightSetback
OFF: No change of the reference. ON: (1) Offset value in "r13" forms part of the reference. The total reference can be seen when you push the lower of the two buttons.-Reference
Reference limitation
With these settings, the setpoint can only be set between the two values. (This also applies if regulation with displacements of the reference).
Max. permissible reference value.r25Max. reference
Min. permissible reference value.r26Min. reference
Correction of temperature measurementr04Adjust sensor
An offset adjustment of the registered temperature can be made. The function is used if correction for a too long sensor cable has to be made.
Unitr05(In AKM only °C and bar is used, whatever the setting)
Here you can select whether the display is to indicate SI units or US units (°C and bar or °F and psig). Setting = "C-b" will give °C and bar. Setting = "F-P" will give °F and psig. All settings made in °C or °F. Excluding o20 and o21, which are set in bar / PSIG.

Capacity Settings

Function Parameter Parameter by operation via data communication
Running time
To prevent frequent start/stop, values have to be set for how the relays are to cut in and out.
Min. ON time for relays.c01Min.ON time
Min. time period between cutin of same relay.c07Recycle time
Coupling (compressor and condensor)c08Step mode
Cutin and cutout can take place in three ways: 1. Sequential: First relay 1 cuts in, then relay 2, etc. Cutout takes place in the opposite sequence. ("First in, last out"). 2. Cyclic: An automatic operating time equalisation is arranged here, so that all steps will have the same operating time. (The relay with the fewest number of operating hours cuts in or out before the others) (Or put differently: "First in, last out"). 3. Compressor(s) with unloader: The cyclic operation is performed on relays 1 and 3. The unloaders are mounted on relays 2 and 4 (relays 1 and 2 belong to the first compressor, relays 3 and 4 to the other). The above mentioned "Min. On-time" and "Min. recycle time" are not used for unloaders. In connection with cutout, the two unloaders are cut out before the compressors are cut out.
Unloaders' cutin and cutout mode (Only in connection with cutin/cutout mode 3. See above). The relays for the two unloaders can be set to switch on when more capacity is required (setting = no), or they can switch off when more capacity is called for (setting = nc).c09Unloader (switch on = 0) (switch off = 1)

Detailed Function Settings

Setting for Neutral Zone Regulation

Function Parameter Parameter by operation via data communication
Regulation band under the neutral zonec10+ Zone K
Time delay between step cut-ins in the regulation band over the neutral zonec11+ Zone m
Time delay between step cut-ins in the regulation band over the "+Zone band".c12+ + Zone s
Regulation band over the neutral zonec13- Zone K
Time delay between step cut-outs in the regulation band under the neutral zonec14- Zone m
Time delay between step cut-outs in the regulation band under the "-Zone band"c15- - Zone s

Manual Control of Compressor Capacity

Function Parameter Parameter by operation via data communication
This sets the capacity that is to be cut in when switching to manual control.c31ManualCap %
Manual control of the compressor capacity is enabled here. When set to ON, the capacity that is set in "c31" is cut in.c32ManualCap

Alarm Settings

Function Parameter Parameter by operation via data communication
The controller can give alarm in different situations. When there is an alarm, all the light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay will cut in.
Upper deviationA10Max. Al. limit
Here you set when the alarm at high temperature/pressure is to enter into effect. The value is set as an absolute value. See also emergency procedure page 7.
Lower deviationA11Min. Al. limit
Here you set when the alarm at low temperature/pressure is to enter into effect. The value is set as an absolute value. See also emergency procedure page 7.
Alarm delayA03Alarm delay
If one of the two limit values is exceeded, a timer function will commence. The alarm will not become active until the set time delay has been passed. The time delay is set in minutes.
Give the top button a brief push to zeroset the alarm and to have the message shown on the display.Reset alarm
The function zerosets all alarms when set in pos. ON. With data communication, the importance of the individual alarms can be defined. Setting is carried out in the "Alarm destinations" menu.

Miscellaneous

Function Parameter Parameter by operation via data communication
External signalo10Application mode
Here you set the signal to be connected to the controller. 0: No signal/regulation stopped (display will then show OFF) 1: 4-20 mA from pressure transmitter for compressor regulation 2: 4-20 mA from pressure transmitter for condenser regulation 3: Pressure transmitter type AKS 32R for compressor regulation 4: Pressure transmitter type AKS 32R for condenser regulation 5: 0-10 V from other regulation 6: 0-5 V from other regulation 7: 5-10 V from other regulation 8: Pt1000 ohm temperature sensor for compressor regulation 9: Pt1000 ohm temperature sensor for condenser regulation 10: PTC1000 ohm temperature sensor for compressor regulation 11: PTC1000 ohm temperature sensor for condenser regulation
Number of relayso19Number of steps
Depending on the application, up to four relays may be used. This number must be set in the controller. (The relays are always used in numerical sequence).
Pressure transmitter's working range
Depending on the pressure, a pressure transmitter with a given working range is used. This working range must be set in the controller (e.g.: -1 to 12 bar). The values must be set in bar if display in °C has been selected. And in psig, if °F has been selected.
Min. valueo20Min. Trs. pres
Max. valueo21Max Trs. pres
If the two values are to be set from the AKM programme, they must be set in bar.

Controller Settings and Operation

DI Input Usage

The digital input can be connected to a contact function, and the contact can now be used for one of the following functions:

Parameter: o22, Function: Di control

Operating Hours

The operating hours for the four relays can be read in the following menus. The read value is multiplied by 1000 to obtain the number of hours. On reaching 999 hours, the display stops and must be reset to 0. There will be no alarm or error message for counter overflow.

(In the AKM display, the hour number has not been multiplied)

Refrigerant Setting

Before refrigeration is started, the refrigerant must be defined. You may choose between the following refrigerants:

Parameter: o30, Function: Refrigerant

List of refrigerants (e.g., 1=R12, 2=R22, ..., 37=R407F). Warning: Wrong selection of refrigerant may cause damage to the compressor.

Manual Control

From this menu, relays can be cut in and out manually. OFF gives no override, but a number between 1 and 4 will cut in a corresponding relay. The other relays will be off.

Parameter: o18

Frequency

Set the net frequency.

Parameter: o12, Function: 50/60 Hz (50=0, 60=1)

Address

If the controller is built into a network with data communication, it must have an address, and the master gateway must know this address. These settings can only be made when a data communication module has been mounted and the cable installation is completed (see document "RC.8A.C"). The address is set between 1 and 60. The address is sent to the gateway when the menu is set to ON.

Parameter: o03

Access Code

To protect settings with a numerical code, set a value between 0 and 100. To cancel, set to OFF.

Parameter: o05

Cooling or Heating

Cooling: Relays are cut in when the temperature is above the reference. Heating: Relays are cut in when the temperature is below the reference.

Parameter: o07, Function: Refg./Heat

Operating Status and Alarms

Operating Status

The controller displays status codes when waiting for the next regulation point. Push the upper button briefly (1s) to view status codes. The individual status codes have the following meanings:

Status Code Meaning EKC state (0 = regulation)
S2When the relay is operated, it must be activated for min. x minutes (cf. C01)2
S5Renewed cut-in of the same relay must not take place more often than every x minutes (cf. C07)5
S8The next relay must not cut in until x minutes have elapsed (cf. C11-C12)8
S9The next relay must not cut out until x minutes have elapsed (cf. C14-C15)9
S10Regulation stopped with the internal or external start/stop10
S20Emergency control20
S25Manual regulation of outputs25
PSPassword required. Set passwordPS

Alarm Messages

Alarm Code Message Alarms
A1High temperature alarm (cf. A10)High temp. alarm
A2Low temperature alarm (cf. A11)Low temp. alarm
A11No refrigerant has been selected (cf. o30)RFG not selected
A12Regulation stopped due to interrupted signal on the DI inputDI Alarm
A45Regulation stopped with setting or with external switchA45 Stand by
E1Error in the controllerController fault
E2Control signal outside the range (short-circuited/interrupted)Out of range

Service

Warning! Direct start of compressors

To prevent compressor breakdown, parameter c01 and c07 should be set according to supplier requirements or in general:

*) Direct activating of solenoid valves does not require settings different from factory (0).

Emergency Procedure

If the controller registers irregularities in the registered signals, it will start an emergency procedure:

For compressor regulation:

For condenser regulation:

Operation and Menu Survey

Display

Values are shown with three digits. The setting determines whether temperature is shown in °C or °F.

Display: A three-digit numerical display.

Light-emitting diodes (LED) on front panel

Four LEDs indicate when relays are operated. All LEDs flash if there is an error. Error codes can be uploaded to the display and alarms cancelled by pushing the top button briefly.

Controller Messages

Code Message
E1Errors in the controller
E2Regulation out of range or control signal is defect.
A1High pressure alarm
A2Low pressure alarm
A11No refrigerant selected
A12Regulation stopped due to interrupted signal on the DI input
A45Regulation is stopped
PSPassword is required

The Buttons

To change a setting, use the two buttons to increase or decrease the value. Access the menu by pushing the upper button for a couple of seconds. Find the parameter code and push both buttons simultaneously to change the value. Save the new value by pushing both buttons simultaneously again.

Examples of Operations

Set the regulation's set point

  1. Push the two buttons simultaneously.
  2. Push one of the buttons and select the new value.
  3. Push both buttons again to conclude the setting.

Set one of the other menus

  1. Push the upper button until a parameter is shown.
  2. Push one of the buttons and find the parameter you want to change.
  3. Push both buttons simultaneously until the parameter value is shown.
  4. Push one of the buttons and select the new value.
  5. Push both buttons again to conclude the setting.

Menu Survey

Function Parameter Min. Max. SW: 2.0x Factory setting
Normal display°C
Shows the signal from the temperature sensor / pressure transmitter
Reference
Set the regulation's set point--60 °C170 °C3
Neutral zoner010.1 K20 K4.0
Correction of signal from the sensorr04-20 K20 K0.0
Select SI or US display: 0=SI (bar/°C). 1=US (Psig/°F)r05c-bF-Pc-b
Start/stop of regulation (0=off)r12010
Reference displacement by signal at DI inputr13-50 K50 K0
Reference limitation. Max. valuer25-50°C170°C50°C
Reference limitation. Min. valuer26-60°C50°C-60°C
Displacement of reference (On=activ "r13")r27OffOnOff
Capacity
Min. ON time for relaysc010 min.30 min2
Min. time period between cutins of same relayc070 min.60 min.4
Definition of regulation mode 1: Sequential (step mode / FILO) 2: Cyclic (step mode / FIFO) 3: Compressor with unloader If the regulation mode 3 has been selected, the relays for the unloaders can be defined to: no: Cut in when more capacity is required nc: Cut out when more capacity is requiredc08131
Regulation parameter for + Zonec100.1 K20 K3
Regulation parameter for + Zone min.c110.1 min.60 min.2
Regulation parameter for ++ Zone secondsc121 s180 s30
Regulation parameter for - Zonec130.1 K20 K3
Regulation parameter for - Zone min.c140.1 min.60 min.1
Regulation parameter for - - Zone secondsc151 s180 s30
Cutin capacity at manual control. See also "c32"c310%100%0%
Manual control of capacity (when On the value in "c31" will be used*)c32OffOnOff
Alarm
Alarm time delayA031 min.90 min.30
Upper alarm limit (absolute value)A10-60 °C170 °C50
Lower alarm limit (absolute value)A11-60 °C120 °C-60
Miscellaneous
Controllers addresso03*12400
On/off switch (service-pin message)o04*---
Access codeo05off(-1)100-
Inverse function (HE: heating at relays = on)o07rEHErE
Define input signal and application: 0: no signal / regulation stopped 1: 4-20 mA pressure transmitter - compressor reg. 2: 4-20 mA pressure transmitter - condenser reg. 3: AKS 32R pressure transmitter - compressor reg. 4: AKS 32R pressure transmitter - condenser reg. 5: 0-10 V relay module 6: 0-5 V relay module 7: 5-10 V relay module 8: Pt 1000 ohm sensor - compressor reg. 9: Pt 1000 ohm sensor - condenser reg. 10: PTC 1000 ohm sensor - compressor reg. 11: PTC 1000 ohm sensor - condenser reg.o100110
Set supply voltage frequencyo1250 Hz60 Hz50
Manual operation with "x" relayso18040

Data

Function Parameter Min. Max. SW: 2.0x Factory setting
Define number of relay outputso19144
Pressure transmitter's working range - min. valueo20-1 bar5 bar-1
Pressure transmitter's working range - max. valueo216 bar199 bar12
Define DI input: 0: not used 1: Contact displaces reference 2: Contact starts and stops regulation 3: Interrupted contact will cut out the capacity, and alarm will be given.o22030
Operating hours of relay 1 (value times 1000)o230 h99.9 h0
Operating hours of relay 2 (value times 1000)o240 h99.9 h0
Operating hours of relay 3 (value times 1000)o250 h99.9 h0
Operating hours of relay 4 (value times 1000)o260 h99.9 h0
Setting of refrigerant 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User defined. 14=R32. 15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=XP10. 37=R407F. *) This setting will only be possible if a data communication moduel has been installed in the controller.o300370

Service

Function Parameter
Voltage on the analogue inputu07
Status on DI- inputu10
Status on relay output DO1u15
Signal on pressure transmitter input (bar / PSIG)u25
Status on relay output DO2u58
Status on relay output DO3u59
Status on relay output DO4u60
Status on relay output "alarm"u62

Factory setting

To return to factory-set values:

Data

Specification Value
Supply voltage230 V a.c. +/-15% 50/60 Hz, 5 VA
Input signalPressure transmitter*) with 4-20 mA or temperature sensor Pt 1000 ohm or temperature sensor PTC 1000 ohm or voltage signal (0 - 5 V, 0-10V or 5-10V)
Digital input to external contact function
Relay output4 pcs. SPSTAC-1: 4 A (ohmic)
AC-15: 3 A (inductive)
Alarmrelay1 pcs. SPSTAC-1: 4 A (ohmic)
AC-15: 1 A (inductive)
Data communicationPossible to connect a data communication module
Environments-10 - 55°C, during operation
-40 - 70°C, during transport
20-80% Rh, not condensed
No shock influence / vibrations
EnclosureIP 20
Weight300 g
MountingDIN rail
DisplayLED, 3 digits
Terminalsmax. 2.5 mm² multicore
ApprovalsEU Low voltage Directive and EMC demands re CE-marking complied with.
LVD-tested acc. to EN 60730-1 and EN 60730-2-9
EMC-tested acc. to EN 61000-6-3 and EN 61000-4-(2-6,8,11)

*) Pressure transmitter: As pressure transmitter can be used AKS 3000 or AKS 33 (AKS 33 has a higher accuracy than AKS 3000). It is also possible to use an AKS 32R. Please refer to catalogue RKOYG...

Ordering

Type Function Code No.
EKC 331TCapacity controller084B7105
EKA 175Data communication module (accessories), (RS 485 module)084B8579

Connections

Necessary connections

Terminals:

Control signal (see also o10)

Either terminals:

External contact function, if applicable

19-20: Contact function for displacement of reference or start/stop of the regulation or for monitoring of safety circuit.

Data communication, if applicable

21-22: Mount only, if a data communication module has been mounted. It is important that the installation of the data communication cable be done correctly. Cf. separate literature No. RC8AC...

Diagram: Controller Connections shows terminal blocks and connections for supply voltage, relays, alarm, control signals (AKS 32R, AKS 33, AKS 21, 0-10V), DI input, and data communication.

General Information

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

ADAP-KOOL® is a registered trademark.

PDF preview unavailable. Download the PDF instead.

DOC055586425221 IR Adobe PDF Library 9.9; modified using iTextSharp™ 5.5.10 ©2000-2016 iText Group NV ( ; licensed version)

Related Documents

Preview Danfoss EKC 202 Series User Guide: Temperature Control for Refrigeration
This user guide details the Danfoss EKC 202 series controllers, designed for precise temperature management in refrigeration appliances and cold rooms. It covers features like defrost control, fan operation, alarms, and connectivity within ADAP-KOOL® systems.
Preview Danfoss EKC 367: Instructions and Operation Guide
Comprehensive instructions and operational guide for the Danfoss EKC 367 electronic refrigeration controller, covering installation, connections, parameters, and troubleshooting.
Preview Danfoss EKC 201C Controller for Temperature Control - Manual
Technical manual detailing the features, operation, and specifications of the Danfoss EKC 201C temperature controller, designed for refrigeration appliances and supermarkets. Covers installation, functions, parameters, and troubleshooting.
Preview Danfoss EKC 315A Controller: Instructions and Operation Manual
Comprehensive instructions and operational guide for the Danfoss EKC 315A refrigeration and air conditioning controller, covering connections, menu navigation, parameter settings, and troubleshooting.
Preview Danfoss ICAD 600/900 Actuator: Installation, Operation, and Technical Data
Comprehensive guide to the Danfoss ICAD 600 and ICAD 900 actuators, covering installation, electrical data, general operation, parameter settings, alarms, and technical specifications. Includes wiring diagrams and compatibility information.
Preview Danfoss EKC 202D and EKC 302D Temperature Controllers: Manual and Specifications
A comprehensive guide to the Danfoss EKC 202D and EKC 302D temperature controllers, detailing their applications in refrigeration, operational principles, functions, digital inputs, defrost methods, alarm settings, technical specifications, and ordering information.
Preview Danfoss AK-PC 530 Capacity Controller User Guide
Comprehensive user guide for the Danfoss AK-PC 530 capacity controller, detailing its application in refrigeration systems, regulation methods, functions, operation, and technical specifications.
Preview Danfoss EKC 102C1 Temperature Controller: Official Instructions and Guide
Explore the official instructions for the Danfoss EKC 102C1 temperature controller. This guide covers setup, parameter configuration, operation, and troubleshooting for refrigeration and air conditioning systems.