Eaton Arc-Resistant Magnum PXR Low-Voltage Switchgear

Design Guide DG019011EN

Effective April 2025

General Description

This design guide provides detailed information on Eaton Arc-Resistant Magnum PXR low-voltage switchgear, which protects operating and maintenance personnel from dangerous arcing faults by channeling arc energy out the top of the switchgear. This equipment is designed for low-voltage power distribution and control systems, specifically for switchgear applications.

Product Description

Arc-Resistant Switchgear

Arc-resistant low-voltage switchgear protects personnel by channeling arc energy safely out the top of the unit. Arcing faults, caused by human error or insulation failure, can generate extreme thermal energy and blast forces. While arc-resistant gear does not prevent these arcs, it safely redirects and contains them regardless of the origin. Magnum PXR switchgear has been tested in all three compartments for 0.5 seconds, passing IEEE® Type 2B standards at 100 kA at 508 V and 85 kA at 635 V. Both indoor rear access and indoor front access constructions are available as arc-resistant Type 2B.

Image: Eaton Arc-Resistant Magnum PXR Low-Voltage Switchgear assembly.

Accessibility Types

Eaton arc-resistant switchgear is Type 2B. Its performance is defined by accessibility type in accordance with IEEE test guide C37.20.7:

Normal Operating Conditions

Eaton arc-resistant switchgear is Type 2B. The instrument/control compartment door and breaker secondary door can be open while maintaining Type 2B protection. Arc-resistant features provide additional protection to personnel performing normal operating duties near energized equipment. Proper application requires:

Users should also refer to documents like NFPA 70E® for safety training, work practices, and methods of evaluating safe work distances from energized equipment, flash hazard potential, and proper PPE when working on or near energized equipment with doors/covers open or unsecured.

Product Offering

Arc-resistant switchgear comes standard with:

Standard Features

Image: Close-up of breaker bellows and two-point door latch mechanism.

Image: Rear dynamic flap system with ventilation openings.

Optional Features

Standards and Certifications

Ratings

Table 20.10-1. Voltage Ratings (AC)

System VoltageMaximum Voltage
208/240254
480508
600635

Table 20.10-2. Available Bus Ratings

Cross Bus AmpacityBus Bracing kA
1600100, 150
2000
3200
4000
5000100, 150
6000
8000
10,000

Overview

Eaton's Magnum PXR switchgear, backed by 70 years of development, sets industry standards for quality, reliability, maintainability, and extended operating life in low-voltage electrical distribution systems. It is designed to meet changing customer needs by providing:

Magnum PXR switchgear meets needs for general applications, service entrances, harsh environments, multiple source transfers, and special grounding systems. With a modern design, it provides:

Additional features for coordinated, safe, convenient, trouble-free, and economical control and protection of low-voltage distribution systems are also provided.

Magnum circuit breakers with PXR are designed to conform to:

Magnum PXR switchgear conforms to the following standards:

Maximum ratings for Magnum PXR switchgear are 600 Vac, 10,000 A continuous cross bus.

Seismic Qualification

Refer to eaton.com/seismic for information on seismic qualification for this and other Eaton products.

Structure Features

Image: Close-up of a Magnum PXR breaker showing through-the-door operational elements.

Bus Features

Buses and connections

Vertical and cross bus ratings in Magnum PXR switchgear are based on UL and IEEE standard temperature rise of 65 °C above a maximum ambient air temperature of 40 °C.

Image: Interior view of optional bus compartment and vertical section barriers.

Image: Insulated bus bars within the switchgear.

Wiring Features

Image: Example of control wire marking with origin/wire name/destination zone format.

Instrumentation/Metering Features

See eaton.com/meters for Metering and Power Management products.

Image: Secondary terminal compartment door with control pushbuttons, indicating lights, and switches.

Accessories and Options

Switchgear accessories

Standard accessories furnished with each Magnum PXR switchgear assembly include:

Optional Accessories

Image: Magnum PXR shutter module.

Image: Optional switchgear-mounted lifter for circuit breakers.

Image: Cable lashing device.

Image: MRR1000 remote racking device with control panel.

Enhanced Switchgear Options

Image: Grounding balls and covers for maintenance personnel protection.

Image: Remote control pendant for breaker operation.

Image: Magnum MR2 integral racking device with remote pendant.

Circuit Breakers

Eaton's Type MPS power circuit breakers are a complete, modern, and rugged line of low-voltage power circuit breakers utilizing Eaton's DE-ION® principle of arc extinction. The breaker family is distinguished by similar appearance and operation frame-to-frame. All frame sizes are either manually or electrically operated. For detailed information on Magnum PXR low-voltage power circuit breakers, refer to eaton.com/MagnumPXR.

Breaker Features

Image: Magnum PXR breaker contacts with arc chutes removed.

Stored-Energy Mechanism

A cam-type closing mechanism closes the breaker, receiving energy from a spring charged by a manual handle or a universal electric motor. Stored energy is released by manually depressing a button or electrically energizing a releasing solenoid.

Image: Front view of a Magnum PXR circuit breaker.

Arc Chute

There are three basic means of extinguishing an arc: lengthening the arc path; cooling by gas blast or contraction; and deionizing or physically removing conduction particles. The DE-ION principle is incorporated in all Magnum circuit breakers with PXR, enabling faster arc extinguishing, positive interruption, and minimum contact burning.

Breaker Operation

Levering Mechanism

The worm gear levering mechanism is self-contained on the breaker drawout element and engages slots in the breaker compartment. A standard 3/8-inch (10 mm) drive set levers the breaker between connected, test, and disconnected positions. Mechanical interlocking prevents levering unless the breaker is in the opened position.

Protection During Levering Operation

When levering the breaker between connected, test, and disconnected positions, the operator is protected from live parts by the breaker door.

True two-step stored energy closing

Refers to the sequence required to charge and close the breaker:

  1. Breaker closing springs are charged manually or by the optional charging motor. Mechanical interlock prevents closing until springs are fully charged.
  2. With springs fully charged, the breaker can be closed by pressing the manual close pushbutton or by the optional spring release coil via a remote electrical signal.

"Stored energy" is energy held in waiting, ready to open or close the breaker within five cycles or less. The unique cam and spring design provides energy for a single close-open sequence and multiple charge-close operations (charge-close-recharge-open-close-open). Energy to open the breaker is always restored after a closing operation. Closing springs are interlocked with the breaker racking mechanism to ensure discharge before the breaker reaches the disconnect position.

Provisions for padlocking

All breakers include provision for padlocking open to prevent electrical or manual closing. This secures the breaker in connected, test, or disconnected positions by preventing levering.

Ease of inspection and maintenance

Magnum circuit breakers with PXR are designed for maximum accessibility and ease of inspection and maintenance.

Manually operated breakers

Equipped with a manual charging handle to charge closing springs. Manual closing and tripping pushbuttons operate the breaker. Remote closing and tripping can be accomplished by installing optional electric spring release and shunt trip coils. Closing springs must be charged manually before remote signals can be sent.

Electrically operated breakers

Equipped with a spring charging motor and electrically operated spring release and shunt trip coils. The manual charging handle can be used to charge springs when power is unavailable to the charging motor.

Optional Breaker Accessories

Magnum PXR Switchgear—Trip Units

Power Xpert Release trip unit

The Power Xpert Release (PXR) trip unit, with current sensors and a trip actuator, is the circuit breaker subsystem providing protection, monitoring, and metering functions. PXR analyzes signals from current sensors and voltage connections. If current level and time delay settings are exceeded, the PXR trip unit initiates a trip. Automatic overload and short-circuit tripping characteristics are determined by current rating and user-selected protection settings. Adjustments allow coordination and adaptation to any application. External control voltage is not required for current protection. All trip units have thermal memory, 50/60 Hz operation, and thermal self-protection at 90 °C.

PXR integral microprocessor-based breaker overcurrent trip systems

Provide maximum reliability with true rms sensing, excellent repeatability, and minimum maintenance. No external control source is required for protective functions.

Image: Front panels of PXR 20 and PXR 25 trip units.

Trip functions

Magnum PXR trip units provide maximum flexibility, available in LSI and LSIG configurations. Short delay or instantaneous functions can be defeated, reducing spare breaker inventories and maximizing interchangeable breaker usage.

Image: Front panel of PXR 35 top-of-the-line trip unit.

PXR 35

Top-of-the-line trip unit with higher accuracies: 0.25% metering on voltage and current, combining for 0.5% power and energy metering accuracy.

Zone selective interlocking

The PXR ZSI capability provides positive system coordination without time delays. It allows the breaker closest to the fault to trip first, keeping the rest of the distribution system online, avoiding unnecessary and costly downtime.

Arcflash Reduction Maintenance System

The Arcflash Reduction Maintenance System Maintenance Mode function of the Power Xpert Release trip units reduces arc flash incident energy during a fault condition via a parallel trip circuit that provides fast-acting response. This is separate from normal system protection settings. It operates simultaneously with normal LSIG protection, providing an added backup function. Eaton's system employs a separate, peak-sensing trip circuit that eliminates trip unit microprocessor latencies, resulting in faster clearing times than standard instantaneous tripping. This provides superior arc flash reduction compared to competitor systems that simply lower the instantaneous pickup set point or employ ZSI tripping.

There are three ways to arm the Maintenance Mode setting:

  1. Locally: Via a two-position switch on the front of the PXR 20, PXR 25, and PXR 35 trip units. The setting for reduction level is in the SYSTEM submenu.
  2. Remotely: Via a remote switch or external relay contact wired through the breaker secondary terminals. Requires a high-quality gold-plated or palladium contact.
  3. Via communication device: The trip unit display shows a confirmation screen. A Power Distribution Monitoring and Control-Enhanced or basic display-interface module can be used.

The system has five unique settings (1.5, 2.5, 4.0, 6.0, 10.0 x I) for the pickup of the reduction setting. This prevents inrush currents or load surges from triggering the Maintenance Mode function. PXR trip units can go to a lower setting of 1.5 X the frame rating I for maximum arc flash energy reduction. All three arming methods provide a local indication (blue LED ring around ON/OFF switch) to confirm the Maintenance Mode function. One of the three programmable relays in the frame module can indicate the status. This normally open relay contact allows wiring to an external stack light or annunciator for remote indication.

The Maintenance Mode function provides fast tripping even when the regular Instantaneous is set to OFF. The instantaneous LED position indicates a trip initiated by the Maintenance Mode setting. The LCD display indicates "Maintenance Mode Trip."

Diagram: Arcflash Reduction Maintenance System Time-Current Curve (Figure 20.10-1) illustrating protection curves.

Primary Protection Features

The Time-Current Curves (TCC) for the PXR 20, PXR 25, and PXR 35, when used in Magnum PXR circuit breakers, are found in document TD013172EN. All protection settings must follow the recommendations of the specifying engineer in charge of the installation.

Table 20.10-3. Primary Protection Features

ProtectionPXR 20PXR 25PXR 35
Overload protection (Long delay) (L) ANSI 51PLong delay slopeI²tI²t, I⁴t, I²tI²t, I⁴t, I²t, I¹/²t, IEEE: Moderate, extreme, very extreme, IEC: A, B, C
Long delay pickup x (I)0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 0.98, 1.00.4 to 1.0 in steps of 0.010.4 to 1.0 in steps of 0.01
Long delay time at 6 x (I)Seconds0.5, 1, 2, 4, 7, 10, 12, 15, 20, 240.5 to 24 in steps of 0.10.5 to 24 in steps of 0.1
Long delay thermal memoryEnable/disableEnable/disableEnable/disable/alarm
High load alarm 1 % x (I)OFF or 50% to < high load alarm 2 in steps of 1.0%OFF or 50% to < high load alarm 2 in steps of 1.0%OFF or 50% to < high load alarm 2 in steps of 1.0%
High load alarm 2 % x (I)OFF or > high load alarm 1 to 120% steps of 1.0%OFF or > high load alarm 1 to 120% steps of 1.0%OFF or > high load alarm 1 to 120% steps of 1.0%
High load alarm time delay1 to 60 seconds in steps of 1 second
Short circuit protection (S) ANSI 50TD ZSI ANSI 68Short delay slopeFlat, I²tFlat, I²tFlat, I²t
Short delay pickup x (I)1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 101.5 to 10 in steps of 0.11.5 to 14 in steps of 0.1
Short delay time at 8 x (I)Seconds0.1, 0.3, 0.4, 0.50.05 to 0.5 in steps of 0.010.05 to 0.5 in steps of 0.01
Short delay time flatSeconds0.05, 0.1, 0.2, 0.3, 0.4, 0.50.05 to 0.5 in steps of 0.010.05 to 0.5 in steps of 0.01
Short delay zone interlockEnable/disableEnable/disableEnable/disable
Neutral protection ANSI 50N ANSI 51N4th pole or external neutral % x (I)OFF, 60, 100OFF, 60, 100OFF, 60, 100
Pickup x (I)OFF, 2 to 15 in steps of 0.1OFF, 2 to 15 in steps of 0.1OFF, 2 to 15 in steps of 0.1
Instantaneous protection (I) ANSI 50PInstantaneous pickup x (I)OFF, 2, 4, 5, 6, 7, 8, 10, 12, 15OFF, 2 to 15 in steps of 0.1OFF, 2 to 15 in steps of 0.1
Making current release level determined by frame AYYY
Ground (earth) fault protection (G) ANSI 51G ZSI ANSI 68Ground fault sensingResidual, source ground or zero sequenceResidual, source ground or zero sequenceResidual, source ground or zero sequence
Ground fault pickup—trip (I) x (I)0.2, 0.4, 0.6, 0.8, 1.00.2 to 1.0 in steps of 0.010.2 to 1.0 in steps of 0.01
Ground fault pickup—alarm x (I)OFF, 0.2, 0.4, 0.6, 1.0OFF, 0.2 to 1.0 in steps of 0.01OFF, 0.2 to 1.0 in steps of 0.01
Ground fault delay I²t at 0.625 x (I) Seconds0.1, 0.2, 0.3, 0.5, 1.00.1 to 1 in steps of 0.010.1 to 1 in steps of 0.01
Ground fault delay flat Seconds0.05, 0.2, 0.3, 0.5, 1.00.05 to 1 in steps of 0.010.05 to 1 in steps of 0.01
Ground fault zone interlockEnable/disable with ground fault pickupEnable/disable with ground fault pickupEnable/disable with ground fault pickup
Ground fault thermal memoryEnable/disableEnable/disableEnable/disable
Ground fault pre-alarm %50 to 100 of I in steps of 1.050 to 100 of I in steps of 1.050 to 100 of I in steps of 1.0
Maintenance Mode protection (Arcflash Reduction Maintenance System) (A) ANSI 50Switch positionsON or remote LED lights when enabledON or remote LED lights when enabledON or remote LED lights when enabled
Maintenance mode pickup x (I)1.5, 2.5, 4.0, 6.0, 8.0, 10.01.5, 2.5, 4.0, 6.0, 8.0, 10.01.5, 2.5, 4.0, 6.0, 8.0, 10.0
Relay contact for remote indication of modeYYY

Note: If I²t slope is selected, not all times are available; consult time-current curves. Ground fault pickup is limited to a maximum of 1200 A for ANSI/UL/CSA versions to comply NEC® standards. Maintenance mode pickup maximum setting may be limited based on rating I.

Enhanced Protection Features

Table 20.10-4. Enhanced Protection Features

ANSI StandardEnhanced ProtectionUnitsSettings
PXR 25Three modes of operation are selectable for these protection functions: OFF, Alarm or Trip.
ANSI 59Voltage protectionOvervoltage pickupVolts180 to 720 in steps of 1
Overvoltage delaySeconds1 to 300 in steps of 1
ANSI 27Voltage protectionUndervoltage pickupVolts60 to 670 in steps of 1
Undervoltage delaySeconds1 to 300 in steps of 1
ANSI 47Voltage protectionVoltage unbalance pickup% Volts5 to 25 in steps of 1
Voltage unbalance delaySeconds1 to 300 in steps of 1
ANSI 46Current protectionCurrent unbalance pickup% Amps5 to 25 in steps of 1
Current unbalance timeSeconds1 to 300 in steps of 1
ANSI 78VCurrent protectionPhase loss pickup% Amps75
Phase loss delaySeconds1 to 240 in steps of 1
ANSI 32RPower protectionReverse power pickupkW1 to 65,500 in steps of 1
Reverse power delaySeconds1 to 300 in steps of 1
PXR 35
ANSI 59Motor protectionOver voltage pickup% Volts102 to 150 in steps of 0.1
Over voltage delaySeconds0.05 to 300 in steps of 0.05
ANSI 27Motor protectionUnder voltage pickup% Volts50 to 98 in steps of 0.1
Under voltage delaySeconds0.05 to 300 in steps of 0.05
ANSI 47Motor protectionVoltage unbalance pickup% Volts2 to 90 in steps of 1
Voltage unbalance delaySeconds1 to 300 in steps of 0.05
ANSI 46Motor protectionPhase rotation (sequence) pickupABC or CBA
Current unbalance pickup% Amps2 to 90 in steps of 1
Current unbalance delaySeconds1 to 300 in steps of 0.05
ANSI 78VMotor protectionPhase loss pickup% Amps75
Phase loss delaySeconds1 to 240 in steps of 1
ANSI 32RMotor protectionReverse power pickupkW1 to 65,500 in steps of 1
Reverse power delaySeconds0.05 to 300 in steps of 0.05
Reverse reactive power pickupkvar1 to 65,500 in steps of 1
Reverse reactive power delaySeconds1 to 300 in steps of 1
ANSI 32PPower protectionReal power pickupkW1 to 65,500 in steps of 1
Real power delaySeconds1 to 300 in steps of 1
Apparent power pickupkVA1 to 65,500 in steps of 1
Apparent power delaySeconds1 to 300 in steps of 1
Reactive power pickupkvar1 to 65,500 in steps of 1
Reactive power delaySeconds1 to 300 in steps of 1
Real power demand pickupkW1 to 65,500 in steps of 1
Apparent power demand pickupkVA1 to 65,500 in steps of 1
Reactive power demand pickupkvar1 to 65,500 in steps of 1
ANSI 55Power protectionPower factor pickup0.2 to 0.95 in steps of 0.05
Power factor delaySeconds1 to 60 in steps of 1
ANSI 81OFrequency protectionOver frequency pickup% Hz100.1 to 110 in steps of 0.1
Over frequency delaySeconds0.05 to 60 in steps of 0.05
ANSI 81UFrequency protectionUnder frequency pickup% Hz90 to 99.9 in steps of 0.1
Under frequency delaySeconds0.05 to 60 in steps of 0.05
Total harmonic distortion alarmCurrent pickup10 to 30 in steps of 1
Current delaySeconds1 to 60 in steps of 1
Voltage pickup10 to 30 in steps of 1
Voltage delaySeconds1 to 60 in steps of 1
ANSI 25Synchronism checkMin live line volt%Vnom10 to 130 in steps of 1
Max dead line volt%Vnom10 to 100 in steps of 1
Min live load volt%Vnom10 to 130 in steps of 1
Max dead load volt%Vnom1 to 100 in steps of 1
Max volt difference%Vnom1 to 5 in steps of 1
Max slip frequencyHz0.01 to 2 in steps of 0.01
Max angle differenceDegrees1 to 60 in steps of 1
Volt dead timeSeconds0 to 300 in steps of 1

Note: Three modes of operation are selectable for these protection functions: OFF, Alarm or Trip. Two modes of operation are selectable for these protection functions: OFF or Alarm. Can be mapped to a programmable relay and used in conjunction with the spring release.

Current, Voltage, Frequency, Power and Energy Data

The PXR 20, PXR 25, and PXR 35 provide real-time metering information regarding protected loads. PXR 25 and PXR 35 include monitoring of voltage and phase angle to support power and energy data. All accuracy requires control power (AUX) to the trip unit and is specified for a three-phase balanced load.

Table 20.10-5. Metering Data

DescriptionUnitsAccuracy
Current Metering
IA, IB, IC, IN, IGAmperesPXR 20 and PXR 25: ±0.5% of reading over the range of 10% to 120% x I at 25 °C (77 °F)
Minimum IA, IB, IC, IN, IGAmperesPXR 35: ±0.25% of reading over the range of 10% to 120% x I at 25 °C (77 °F)
Maximum IA, IB, IC, IN, IGAmperes
THD for IA, IB, IC, IN%
Demand IA, IB, IC, IN, IGAmperes
Demand maximum IA, IB, IC, IN, IGAmperes
Voltage Metering
VAB, VBC, VCA (line-to-line)VoltsPXR 25: ±0.5% of reading over the range of 102 to 690 Vac line-to-line at 25 °C (77 °F)
Minimum VAB, VBC, VCAVoltsPXR 35: ±0.25% of reading over the range of 102 to 690 Vac line-to-line at 25 °C (77 °F)
Maximum VAB, VBC, VCAVolts
THD for VAB, VBC, VCA%
VAN, VBN, VCN (line-to-neutral)Volts
Minimum VAN, VBN, VCNVolts
Maximum VAN, VBN, VCNVolts
Power Metering
RealkWPXR 25: ±1.0% of reading over the range of 20% to 120% x I, 102 to 690 Vac line-to-line, and PF of 0.8 leading to 0.5 lagging at 25 °C (77 °F)
ApparentkVAPXR 35: ±0.50% of reading over the range of 10% to 120% x I, 102 to 690 Vac line-to-line, and PF of 0.8 leading to 0.5 lagging at 25 °C (77 °F)
Reactivekvar
Real demandkW
Apparent demandkVA
Reactive demandkvar
Real demand (peak)kW
Apparent demand (peak)kVA
Reactive demand (peak)kvar
Energy Metering
Real total (forward + reverse)kWhPXR 25: ±1.0% of reading over the range of 20% to 120% x I, 102 to 690 Vac line-to-line, and PF of 0.8 leading to 0.5 lagging at 25 °C (77 °F)
Real net (forward - reverse)kWhPXR 35: ±0.50% of reading over the range of 10% to 120% x I, 102 to 690 Vac line-to-line, and PF of 0.8 leading to 0.5 lagging at 25 °C (77 °F)
Real forward (delivered by source to load)kWh
Real reverse (delivered by load to source)kWh
Apparent energykVAh
Reactive received (in quadrant 3 and 4)kvarh
Reactive delivered (in quadrant 1 and 2)kvarh
Reactive total (delivered + received)kvarh
Reactive net (delivered - received)kvarh
Frequency Metering
HzPXR 20 and PXR 25: Not available
PXR 35: ±0.1 Hz
Power Factor Metering
N/APXR 35: Available
PXR 20 and PXR 25: Not available

Note: Neutral current accuracy for internal sensor (four-pole) breakers. From 50 A to 125 A, current accuracy is ±0.50% of reading and power and energy metering is ±1% of reading; below 50 A, accuracy is ±1% of reading and power and energy metering is ±2% of reading. The PXR 35 includes voltage metering for line and load. By default, the line side is VDB1 (upper terminals) and has 0.25% accuracy. Accuracy for VDB2 (lower terminals) is 1%. Maximum and minimum values are held until reset using PXPM or the display. Demand values are on a configurable fixed or sliding window of 5 to 60 minutes. Power and energy metering and protection functions are calculated with the convention that power flow is from line to load through the circuit breaker. This assumes the top side conductor to be the line side. If the distribution system is configured such that the bottom side is the line side, the power values will indicate reverse power. This can be changed by using the display and navigation button. Navigate to the Edit Settings menu and under Power Feed, select Forward or Reverse.

Magnum PXR Switchgear Class UL 1066 Low-Voltage Power Circuit Breakers

Table 20.10-6. Magnum PXR Switchgear Class UL 1066 Low-Voltage Power Circuit Breakers

Frame AmperesBreaker TypeFrame Typerms Symmetrical Current Ratings kA 50/60 HzShort-Time Withstand Rating at 254/508 VacAvailable Programmed Nominal (I) Rating for PXR Trip Units
Interrupting at 254 VacInterrupting at 508 VacInterrupting at 635 Vac
800MPN-408Narrow42424242100, 200, 250, 300, 400, 600, 800
MPN-608Narrow65656565
MPN-C08Narrow1001006565
MPS-408Standard42424242
MPS-608Standard65656565
MPS-808Standard85858585
MPS-C08Standard10010010085
1200MPN-412Narrow42424242100, 200, 250, 300, 400, 600, 800, 1000, 1200
MPN-612Narrow65656565
MPN-C12Narrow10010065100
MPS-612Standard65656565
MPS-812Standard85858585
MPS-C12Standard10010010085
1600MPN-416Narrow42424242100, 200, 250, 300, 400, 600, 800, 1000, 1200, 1600
MPN-616Narrow65656565
MPN-C16Narrow1001006565
MPS-616Standard65656565
MPS-816Standard85858585
MPS-C16Standard10010010085
2000MPN-620Narrow65656565200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000
MPN-C20Narrow1001006565
MPS-620Standard65656565
MPS-820Standard85858585
MPS-C20Standard10010010085
2500MPS-625Standard65656565200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, 2500
MPS-825Standard85858585
MPS-C25Standard10010010085
3200MPS-632Standard65656565200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3000, 3200
MPS-832Standard85858585
MPS-C32Standard10010010085
4000MPN-640Double Narrow656565652000, 2500, 3200, 4000
MPN-840Double Narrow85856585
MPN-C40Double Narrow10010065100
MPS-840Double85858585
MPS-C40Double100100100100
5000MPS-850Double858585852500, 3200, 4000, 5000
MPS-C50Double100100100100
6000MPS-C60Double1001001001003200, 4000, 5000, 6000

Note: Interrupting ratings shown are based on breaker equipped with integral PXR trip unit. Interruption ratings for non-automatic breakers are equal to the published short-time withstand rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short-time ratings consists of maintaining the rated current for two periods of 0.5 second each, with a 15-second interval of zero current between the two periods. 100 A nominal is only available in narrow frame options. Breaker applied in a tested fan cooled enclosure.

Metering Devices

Power Xpert Energy Meter (PXE)

The PXE offers enhanced accessibility to critical information for managing electrical distribution systems. It supports sag/swell waveform capture and provides real-time circuit information in numeric and graphical formats to monitor circuit parameters (current loading, voltage, power levels, harmonics). Information can be viewed using the optional web-enabled communication module. Optional WiFi offers enhanced connectivity and web browser access.

Image: Power Xpert Energy Meter (PXE) display.

Meter features include:

PXQ

PXQ utilizes aggregated power quality metrics to contextualize disturbance events with adaptable views and personalization. It includes onboard web pages for enhanced root-cause analysis of power quality events.

Image: PXQ power quality meter.

The PXQ series includes:

PXQ Expansion Modules

PXQ provides options for additional capabilities and customization.

Enhanced Capture Module (PXQ-ENH)

Improves PXQ's diagnostic capabilities by detecting and recording high-speed voltage transients (as short as 100 ns with up to 10 kV magnitude). Forensic waveform data is available (1 cycle (17 ms) COMTRADE at 167,000 samples per cycle). When combined with the PXQ-ST2-1A1, it replaces the PXM8000.

Expanded Input Module (PXQ-SER)

Each PXQ can have up to two input expansion modules, each with 16 additional digital inputs, totaling up to 40 inputs (8 + 16 + 16). Digital inputs can be configured for:

Image: PXQ system with Enhanced Capture Module (PXQ-ENH) and two Expanded Input Modules (PXQ-SER).

Communications

Power Xpert Gateway 1000

Ethernet communications are available via Power Xpert Gateway PXG1000 with one of three configurations in low-voltage switchgear:

Basic (Gateway)

Enhanced (Dashboard)

Enhanced plus Remote Racking

Includes all options listed above with the addition to control any integral remote racking (MR2) devices installed in the circuit breakers.

Image: Power Xpert Gateway PXG1000 communication module.

Image: Enhanced Graphics Option display showing system overview.

Automatic Transfer

Automatic transfer and intelligent control packages are as follows:

Image: ATC-900 automatic transfer controller.

Image: Programmable Logic Controller (PLC) module.

For information on automatic transfer and intelligent control solutions, see the LVA Automatic and Intelligent Solutions brochure.

High-Resistance Grounding

General Description

High-resistance grounding adds safety to a grounded system while minimizing service interruptions due to grounds, where continuity of service is a high priority. It provides a path for ground current via a resistance that limits current magnitude, and monitors to determine abnormal conditions. This ensures maximum continuity of service as no tripping occurs for the resistance-limited ground fault. The ground current path is provided at the service beginning by placing resistance in the connection from system neutral to ground. Control equipment continuously measures ground current; a relay detects when current exceeds a predetermined level, alerting personnel. The system has built-in fault tracing. An integral transformer provides control power from the primary source.

Image: Integrated High-Resistance Grounding (HRG) compartment within switchgear.

Standard Features (Basic Version)

Digital HRG Compartment Features

Standardized digital HRG compartment condenses HRG functionality into a 1/4-high arrangement.

Surge Protection Devices

Integrated SPDs

Eaton integrates industry-leading SPD Series surge protective devices into panelboard and switchboard assemblies. Lead length is minimized to maximize SPD performance. Integrated SPD units are UL listed and labeled to UL 1449 5th Edition.

Image: Eaton SPD-400480Y4C Surge Protective Device.

Key features include:

The breadth of SPD Series' features, options, and configurations ensures the correct unit is available for all electrical applications, including service entrances, distribution switchboards, panelboards, and point-of-use applications. For complete SPD product description, application, and ratings, visit eaton.com/spd.

Power Xpert SPD

The Power Xpert SPD is an advanced monitoring display to track and record surge events and remaining protection status on each phase. Surge events are categorized as low, medium, and high according to IEEE Standard C62.41, logged with time and date stamps. The RJ45 Ethernet port provides communication between the surge device and the LAN connection, Modbus TCP/IP, or BACnet/IP protocols. Ability to access the remote webpage through Power Xpert Gateway 1000. Email alarm notifications are available when configured through Power Xpert Gateway 1000.

Table 20.10-7. Feature Package Comparison

FeatureBasicStandardStandard with Surge CounterPower Xpert SPD
Surge protection using thermally protected MOV technology
Dual-colored protection status indicators for each phase and the neutral-ground protection mode
Audible alarm with silence button
Form C relay contact
EMI/RFI filtering, providing up to 50 dB of noise attenuation from 10 kHz to 100 MHz
Surge counter with reset
Tri-colored protection status indicators for each phase and the neutral-ground protection mode
Percentage protection remaining status
RJ45 Ethernet port for LAN connection, Modbus TCP/IP or BACnet/IP
Ul webpage and programmable settings
Time-and-date stamped surge log and surge categorization

Note: Neutral-ground protection mode available in applicable voltage configurations only.

Layouts and Dimensions

Breaker Layouts

Magnum PXR Rear-Accessible Switchgear

Diagrams illustrating various breaker layouts and structure dimensions for Magnum PXR Rear-Accessible Switchgear.

Main-Tie-Main Example Layouts

Diagrams illustrating various Main-Tie-Main example layouts and dimensions.

Structure Dimensions

Conduit Area Location

Diagrams illustrating structure dimensions and conduit area locations.

Table 20.10-8. Arc-Resistant Structure Dimensions in Inches (mm)

WDACCRecommended Number of Conduits for Top Entry (4.00 Inch / 101.6 mm)
22.00 (558.8)72.00 (1828.8)36.00 (914.4)14.80 (375.9)6
78.00 (1981.2)42.00 (1066.8)20.80 (528.3)9
84.00 (2133.6)48.00 (1219.2)26.80 (680.7)13
90.00 (2286.0)54.00 (1371.6)34.80 (883.9)15
30.00 (762.0)72.00 (1828.8)36.00 (914.4)14.80 (375.9)8
78.00 (1981.2)42.00 (1066.8)20.80 (528.3)12
84.00 (2133.6)48.00 (1219.2)26.80 (680.7)20
90.00 (2286.0)54.00 (1371.6)34.80 (883.9)24
44.00 (1117.6)72.00 (1828.8)36.00 (914.4)14.80 (375.9)12
78.00 (1981.2)42.00 (1066.8)20.80 (528.3)18
84.00 (2133.6)48.00 (1219.2)26.80 (680.7)26
90.00 (2286.0)54.00 (1371.6)34.80 (883.9)30

Note: Arc-resistant switchgear's conduit space for bottom entry is the same as regular rear-accessible gear.

Diagrams illustrating structure dimensions, conduit areas, and exhaust configurations.

Heat Loss

Table 20.10-11. Heat Loss Data — Estimated Heat Loss Per Breaker (Watts)

Breaker FrameDrawout Mounting Only
800150
1600329
2000374
3200719
4000749
50001000
60001440

Estimated Heat Loss Per Structure (Watts)

Loss is based on fully loaded vertical and cross bus rating in a structure as given below.

RatingVertical BusCross Bus
2000410288
320016231163
400010971169
500014101217
600020301265
80002240
10,0003500

Note: For lower than maximum load currents, watt loss may be estimated by reducing the full load loss by the following: WL=(IL/IFL)²WFL, where WL=Load Watts, WFL=Full Load Watts, IL=Actual Load Current, IFL=Full Load Current. Vertical section bus is sized per main cross bus maximum rating or by IEEE C37.20.1 to a maximum of 5000 A. (4000 A in 18.00-inch [457.2 mm] structure.) In addition to the available bus bracings shown in Table 20.10-2, the bus has been tested for short-circuit values of 85 kA for a full 60 cycles.

Closing Times of Magnum PXR Breakers

Opening Times—Dependent on Function Used

Center of Gravity

For seismic calculations, the following dimensions should be used to locate the center of gravity for indoor Magnum PXR switchgear.

Table 20.10-12. Center of Gravity Location

Dimensions in Inches (mm)
VerticalLeft-to-RightFrom the Front
60.00 (1524.0)Center of lineup26.00 (660.4)

Weights

Table 20.10-13. Magnum PXR Indoor Rear Switchgear Structure Approximate Weights (Standard Construction Less Breakers)

Width in Inches (mm)Depth in Inches (mm)Approximate Weight in Lb (kg)
Breaker Structure
18.00 and 22.00 (457.2 and 558.8)60.00 (1542.0)1250 (568)
66.00 (1676.4)1300 (591)
72.00 (1828.8)1350 (614)
78.00 (1981.2)1400 (639)
84.00 (2133.6)1450 (659)
90.00 (2286.0)1500 (682)
30.00 (762.0)60.00 (1542.0)1900 (864)
66.00 (1676.4)2000 (909)
72.00 (1828.8)2100 (955)
78.00 (1981.2)2200 (1000)
84.00 (2133.6)2300 (1045)
90.00 (2286.0)2400 (1091)
44.00 (1117.6)60.00 (1542.0)2500 (1136)
66.00 (1676.4)2600 (1182)
72.00 (1828.8)2700 (1227)
78.00 (1981.2)2800 (1273)
84.00 (2133.6)2900 (1318)
90.00 (2286.0)3000 (1364)
Auxiliary/Transition Structures
18.00 and 22.00 (457.2 and 558.8)60.00 (1542.0)950 (432)
66.00 (1676.4)1000 (455)
72.00 (1828.8)1050 (477)
78.00 (1981.2)1100 (500)
84.00 (2133.6)1150 (523)
90.00 (2286.0)1200 (545)
30.00 (762.0)60.00 (1542.0)1700 (773)
66.00 (1676.4)1750 (795)
72.00 (1828.8)1800 (818)
78.00 (1981.2)1850 (840)
84.00 (2133.6)1900 (864)
90.00 (2286.0)1950 (886)

Note: See Table 20.10-14 for breaker weights.

Table 20.10-14. Magnum PXR Front-Access Construction Switchgear Structure Approximate Weights (Less Breakers)

Width in Inches (mm)Depth in Inches (mm)Approximate Weight in lb (kg)
Breaker Structure
18.00, 22.00 and 24.00 (457.2, 558.8 and 609.6)40.00 (1016.0)1100 (500)
30.00 (762.0)40.00 (1016.0)1750 (795)
44.00 (1117.6)40.00 (1016.0)2200 (1000)
Cable Compartment
18.00, 22.00 and 24.00 (457.2, 558.8 and 609.6)40.00 (1016.0)800 (363)
30.00 (762.0)40.00 (1016.0)1550 (705)
44.00 (1117.6)40.00 (1016.0)1600 (727)

Note: See Table 20.10-13 for breaker weights.

Table 20.10-15. Magnum PXR Arc-Resistant Switchgear Additional Approximate Weights

Arc-Resistant ComponentApproximate Weight kg/Foot (m)
Plenum34 (50.60)
Exhaust duct38 (56.55)

Service Conditions

All low-voltage air power circuit breakers are tested per IEEE Standard C37.1 for a system X/R ratio of 6.6 maximum. It is common within low-voltage systems to experience power factor and X/R values outside the range of standard values, requiring evaluation against published product ratings.

For applications of power breakers within distribution systems having calculated X/R ratios higher than 6.6, derating of the air power breakers kAIC rating is required. Per IEEE methodology, the calculated short circuit current at the point of interest is increased by the Table 20.10-17 multiplying factors (MF) to yield an "apparent value of short circuit current," which is then compared to published breaker ratings. Only breakers with published ratings higher than the "apparent fault current" can be safely applied.

For example, if unfused air power breakers rated 65 kAIC were considered within a 480/277 Vac distribution system where the X/R at the point of breaker application is 14.25 and the calculated fault current was determined to be 60 kA, the determination of the suitability of these breakers yields:

Apparent Fault Current = 60 kA x MF = 60 kA x 1.112 = 66.72 kA

Therefore, because 66.72 kA exceeds the 65 kAIC rating, higher rated kAIC breakers would need to be applied.

Table 20.10-17. Air Power Breaker Derating

System X/R RatioSystem % PFDerating and Multiplying Factors for Air Power Breakers
FusedUnfused
DeratingMFDeratingMF
1.7350.01.0001.0001.0001.000
3.1830.01.0001.0001.0001.000
3.8725.01.0001.0001.0001.000
4.9020.01.0001.0001.0001.000
6.5915.00.9391.0651.0001.000
8.2712.00.8981.1140.9621.000
9.9510.00.8701.1490.9371.067
11.728.50.8491.1780.9181.089
14.257.00.8271.2090.8991.112
19.975.00.7971.2550.8741.144

Standards

Magnum PXR circuit breakers meet or exceed all applicable requirements of IEEE Standards C37.13 and C37.17, ANSI C37.50 and CSA.

System Voltage and Frequency

Magnum PXR breakers are designed for operation on AC systems only, 60 Hz or 50 Hz, 635 V maximum.

Continuous Current Ratings

Unlike transformers, generators, and motors, circuit breakers are maximum-rated devices with no built-in temporary overload current ratings. Each application must consider maximum anticipated current demand, initial and future, including temporary overloads. The continuous rating of any Magnum circuit breaker with PXR is limited to the frame size current rating. All current ratings are based on a maximum ambient air temperature of 40 °C (104 °F).

Ambient Temperature

The temperature of the air surrounding the enclosure should be within the limits of: -30 °C (-22 °F) to +40 °C (+104 °F).

Altitude

Breakers are applicable at their full voltage and current ratings up to a maximum altitude of 6600 ft (2012 m) above sea level. When installed at higher altitudes, ratings are subject to correction factors in accordance with IEEE C37.20.1.

Table 20.10-16. Altitude Derating Factors

Altitude FeetMetersVoltage CorrectionCurrent Correction
660020121.0001.000
700021340.9890.998
750022860.9760.995
800024380.9630.993
850025910.9500.990
900027430.9330.987
950028960.9170.983
10,00030480.9000.980
10,50032000.8830.977
11,00033530.8670.973
11,50035050.8500.970
12,00036580.8330.967
12,50038100.8170.963
13,00039620.8000.960

Unusual Environmental and Operating Conditions

Special attention should be given to applications subject to the following conditions:

  1. Damaging or hazardous fumes, vapors, etc.: Generally recommended to install switchgear in a clean, dry room with filtered and/or pressurized clean air to avoid derating effects of non-ventilated enclosures.
  2. Excessive or abrasive dust.
  3. Salt spray, excessive moisture, dripping, etc.: Drip shields in equipment rooms and space heaters in indoor weatherproof enclosures may be indicated depending on severity.
  4. Excessively high or low ambient temperatures: For ambient temperatures exceeding 40 °C, continuous current ratings of breaker frame sizes, buses, and current transformers are subject to a derating factor calculated from the formula: (105° Total - Special Ambient, °C) / (105° Total - 40 °C Standard Ambient). Circuit breakers are not adversely affected by very low outdoor ambient temperatures, particularly when energized and carrying load currents. Standard space heaters in weatherproof switchgear raise temperature slightly and prevent condensation. Electrical components like relays and instruments must be applied within manufacturer's specified limits.
  5. Exposure to seismic shock: Magnum PXR assemblies and breakers are certified for applications through International Building Code 2021 (IBC) and California Building Code 2019 (CBC). Assembly modifications may be required.
  6. Abnormally high frequency of operation: May indicate a lesser number of operations between servicing and more frequent replacement of parts.

PDF preview unavailable. Download the PDF instead.

eaton-rear-access-arc-resistant-magnum-pxr-low-voltage-switchgear-design-guide-dg019011-en-us Adobe PDF Library 17.0

Related Documents

Preview Eaton Magnum DS Front Access Arc-Resistant Low-Voltage Switchgear Design Guide
Explore the Eaton Magnum DS Front Access Arc-Resistant Low-Voltage Switchgear Design Guide, detailing advanced power distribution and control systems. Learn about arc-resistant features for enhanced personnel safety, robust construction, flexible configurations, and comprehensive protection capabilities for industrial and commercial applications.
Preview Eaton Arc Quenching Magnum PXR Low-Voltage Switchgear Design Guide
Explore the Eaton Arc Quenching Magnum PXR low-voltage switchgear, a comprehensive solution for enhanced safety and power distribution. This guide details arc quenching technology, substation integration, layout options, and technical specifications for improved incident energy reduction.
Preview Eaton xEnergy Elite: Low Voltage Motor Control and Power Distribution Solutions
Discover the Eaton xEnergy Elite, a high-performance IEC motor control center and low voltage power distribution solution. Learn about its advanced safety features, business continuity advantages, durable and scalable design, and comprehensive component offerings for industrial applications.
Preview Eaton Power Distribution Systems Design Guide: Principles, Analysis, and Application
This Eaton Design Guide provides comprehensive information on the principles, analysis, and implementation of robust power distribution systems, covering system design, components, protection, and various system types for electrical engineers.
Preview Eaton Bussmann Series Expulsion Fuse Links for Medium Voltage Distribution Transformers
This document provides detailed information on Eaton's Bussmann Series expulsion fuse links, designed for protecting medium voltage distribution transformers. It covers product options, technical specifications, application notes, and cross-reference information for various models including Type T, K, and XA.
Preview Eaton Molded Case Circuit Breakers: Power Defense, Series G, and Series C
Explore Eaton's comprehensive range of Molded Case Circuit Breakers, including the Power Defense, Series G, and Series C lines. This catalog details product specifications, applications, and ordering information for advanced electrical protection solutions.
Preview Eaton Wiring Manual 2011: Electrical Systems, Automation, and Power Management
Comprehensive 2011 Wiring Manual from Eaton, detailing the Moeller series for electrical systems, automation, motor control, and power management. Includes technical guides, product information, and safety standards.
Preview Eaton Medium-Voltage Switchgear Product Catalog: Xiria and Power Xpert UX
Explore Eaton's Xiria family (Xiria, Xiria E, Xiria NGX) and Power Xpert UX medium-voltage switchgear. Discover SF6-free, reliable, and compact solutions for industrial, commercial, and utility power distribution.