Felicitysolar MPPT Solar Charge Controller User Guide
Make life full of hope
1. ABOUT THIS MANUAL
1.1 Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
1.3 SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect PV or battery terminals. Please refer to Installation section of this manual for the details.
- GROUNDING INSTRUCTIONS -This charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this charger.
- NEVER cause short circuited on battery output.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this charger back to local dealer or service center for maintenance.
2. INTRODUCTION
Thank you for selecting this solar charge controller. This solar charge controller is an advanced solar charger with maximum power point tracking. Applying intelligent MPPT algorithm, it allows solar charge controller to extract maximum power from solar arrays by finding the maximum power point of the array.
The MPPT battery charging process has been optimized for long battery life and improved system performance. Self-diagnostics and electronic error protections prevent damage when installation errors or system faults occur. This charger also features multifunctional LCD with communication ports for remote battery temperature and voltage measurement.
2.1 Features
- Intelligent Maximum Power Point Tracking technology increases efficiency 25%~30%
- Compatible for PV systems in 12V, 24V or 48V
- Three-stage charging optimizes battery performance (Two-stage charging in lithium battery mode)
- Maximum charging current up to 30A/45A/60A/80A/100A/120A
- Maximum efficiency up to 98%
- Automatic battery voltage detection (Lithium battery voltage needs to be set manually)
- Supports lithium battery and various lead-acid batteries, AGM and gel battery
- Integrated intelligent slot compatible with MODBUS communication
2.2 Product Overview
1. LCD display
2. Power On/Charging indicator
3. Fault and warning indicator
4. Wiring fault indicator
5. Operation button
6. PV Positive +
7. PV Negative -
8. Battery Negative -
9. Battery Positive +
10. Communication Port
3. INSTALLATION
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
- Solar charge controller x 1
- User manual x 1
3.2 Preparation
Before connecting all wirings, please take off wiring box cover by removing screws as shown below.
3.3 Mounting the Unit
Consider the following points before selecting where to install:
- This solar charge controller is designed in IP31 for indoor applications only.
- Do not mount the unit on flammable construction materials.
- Mount on a solid surface
- Install this charger at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
Install the unit to the wall by screwing two screws. Refer to right chart.
3.4 Power Connection
Wire size
The four large power terminals are sized for 14 - 2 AWG (2.5 - 35 mm 2) wire. The terminals are rated for copper and aluminum conductors. Use UL-listed Class B 300 Volt stranded wire only. Good system design generally requires large conductor wires for solar module and battery connections that limit voltage drop losses to 2% or less.
Minimum Wire Size
The table below provides the recommended minimum wire size allowed for the charger. Wire types rated for 75°C and 90°C are listed.
Typical Amperage | Wire Type | 75°C Wire | 90°C Wire |
30A | Copper | 8 AWG (10 mm²) | 8 AWG (10 mm²) |
Aluminum | 6 AWG (16 mm²) | 6 AWG (16 mm²) | |
45A | Copper | 4 AWG (25 mm²) | 6 AWG (16 mm²) |
Aluminum | 2 AWG (35 mm²) | 4 AWG (25 mm²) | |
60A | Copper | 4 AWG (25 mm²) | 6 AWG (16 mm²) |
Aluminum | 2 AWG (35 mm²) | 4 AWG (25 mm²) | |
80A | Copper | 2 AWG (35 mm²) | 4 AWG (25 mm²) |
100A | Copper | 2AWG(35 mm²) | 2AWG(35 mm²) |
120A | Copper | 2 AWG (35 mm²) | 2 AWG (35 mm²) |
Overcurrent Protection and Disconnects
CAUTION: Circuit breakers or fuses must be installed in both battery and solar circuits.
The battery circuit breaker or fuse must be rated to 125% of the maximum current or more. The recommended breaker/fuse rating for use with the charger is listed in the below table.
Recommended breaker rating:
Minimum battery circuit breaker/fuse rating | |
1.25 x 30Amps = 37.5 Amps | 1.25 x 45Amps = 56.3 Amps |
1.25 x 60Amps = 75.0 Amps | 1.25 x 80Amps = 100.0 Amps |
1.25*100Amps = 125Amps | 1.25*120Amps = 150Amps |
A disconnect is required for the battery and solar circuits to provide a means for removing power from the charger. Double pole switches or breakers are convenient for disconnecting both solar and battery conductors simultaneously.
Connect the Power Wires
WARNING: Shock Hazard
The solar modules can produce open-circuit voltages in excess of 100 Vdc when in sunlight. Verify if solar input breaker or disconnect has been opened (disconnected) before connecting system wires.
3.5 Grounding and Ground Fault Interruption
Use a copper wire to connect the grounding terminal in the wiring box to earth ground. The grounding terminal is identified by the ground symbol shown below that is stamped into the wiring box just below the terminal:
The minimum size of the copper grounding wire is 8 AWG (10 mm²).
WARNING: Risk of Fire
DO NOT bond system electrical negative to earth ground at the controller.
3.6 Remote Temperature Sensor
The included Remote Temperature Sensor (RTS) is recommended for effective temperature compensated charging. Connect the RTS to the 2-pole terminal (see figure as below). The RTS is supplied with 33 ft (10 m) of 22 AWG (0.34 mm²) cable. There is no polarity, so either wire (+ or -) can be connected to either screw terminal.
CAUTION: The controller will not activate temperature compensate charging function if the RTS is not used.
CAUTION: Equipment Damage
Never place the temperature sensor inside a battery cell. Both the RTS and the battery will be damaged.
NOTE: The RTS cable may be shortened if the full length is not needed.
3.7 Battery Voltage Sense
The voltage at the battery connection on the controller may differ slightly from the voltage directly at the battery bank terminals due to connection and cable resistance. The Battery Voltage Sense connection enables the controller to measure the battery terminal voltage precisely with small gauge wires that carry very little current, and thus have no voltage drop. Both battery voltage sense wires are connected to the 2-pole terminal inside of wiring box (see figure as below).
Be careful to connect the battery positive (+) terminal to the voltage sense positive (+) terminal and battery negative (-) terminal to the voltage sense negative terminal (-). No damage will occur if the polarity is reversed, but the controller cannot read a reversed sense voltage.
A battery voltage sense connection is not essential required to operate your controller, but it is recommended for best performance. The battery voltage sense will ensure that the voltage display in LCD is very accurate. The voltage sense wires should be cut to length as required to connect the battery to the voltage sense terminal. The wire size can range from 16 to 24 AWG (1.0 to 0.25mm²). A twisted pair cable is recommended but not required. Use UL rated 300 Volt conductors. The voltage sense wires may be pulled through conduit with the power conductors. Tighten the connector screws with 5 in-lb (0.56 Nm) torque. The maximum length allowed for each battery voltage sense wire is 98 ft (30 m).
4. OPERATION
4.1 Power-Up
WARNING: Risk of Damage
Connecting the solar module to the battery connector will permanently damage the controller.
- Confirm that the solar and battery polarities are correctly connected to the controller.
- A battery must be connected to the controller before operating it. The controller will not operate only with solar input. Solar input can trigger the controller to start up when the battery is connected without pressing the button.
- Turn on battery disconnect switch first. And press operation button for a while. Then, it will indicate a successful start-up in LCD display.
- Turn on solar disconnect switch. If the solar module is in full sunlight, the controller will begin charging.
4.2 Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the controller. It includes three indicators, one operation button and a LCD display, indicating the operating status and input/output power information.
Button Operation | Function | Action Description |
Power on | Press the button until LCD backlight is on. | |
Backlight on | Press shortly | |
Enter LCD setting mode | Press the button for 3 seconds. | |
Select LCD setting programs or modify parameter | Press shortly. | |
Confirm selection in setting programs or return back to previous menu | Press the button for 1.5 seconds. |
4.3 LCD Display Icons
Icon | Function description |
Input Source Information | |
8.8.8 | Indicates the PV input voltage. |
Configuration Program and Fault Information | |
E9 | Indicates battery equalization is activated. |
88 | Indicates fault codes. |
88 | Indicates warning codes. |
Output Information | |
8.8.8 Volt | Indicate battery voltage. |
8.8.8 KW | Indicate charging power. |
88.8 Amp | Indicate charging current. |
BATT.CAPACITY | Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode. |
LED Indicator
LED Indicator | Messages | LED Indicator | Messages |
POWER ON/CHARGING | Solid On: The controller is on. Flashing: The controller is charging. Bulk charge stage: flashing every 0.5 second Absorption stage: flashing every second Equalize stage: flashing every 3 seconds Float stage: flashing every 5 seconds |
FAULT/WARNING | Solid On: Fault occurs. Flashing: Warning situation occurs. |
WIRING FAULT | Solid On: Battery polarities are not connected correctly. |
4.4 LCD setting
After pressing button for 3 seconds, the unit will enter setting mode. Shortly press button to select setting programs. And then, pressing button for at least 1.5 seconds to confirm the selected program. After that, shortly press button to modify the parameter of the program. If pressing button for at least 1.5 seconds, you will return to previous menu. After waiting for 10 seconds without any action, it will automatically exit setting mode.
Setting Programs: | Program | Description | Options |
00 | Exit setting mode | Escape | |
01 | Maximum charging current | 30A(Default) 01 30A 45A(Default) 01 45A 60A(Default) 01 60A 80A(Default) 01 80A 100A(Default) 01 100A 120A(Default) 01 120A |
Setting range is from 30A, 45A,60A, 80A, 100A or 120A. Increment of each short press is 1A. The value will be back to 10A once the value is a 30A, 45A,60A, 80A, 100A or 120A.
Use-Defined(Default) 02 USE |
AGM 02 AGn |
Flooded 02 FLd |
LIB 02 L16 |
|||
02 | Battery type | If "Use-Defined" is selected, battery charge voltage can be set up in program 3 and 4. If "Llb" is selected, battery charge voltage can be set up in program 3. Note: "Lib" mode can only be displayed after parameter 05 is set as one of 12V 24V/48V.If you want to set "Lib", first set the 05 battery rated voltage (MPPT 45A(12/24V) can't set the Absorption voltage to 48v, Llb mode can't set the AUO), then set 02 to "Llb" |
||||
03 | Absorption voltage | 14.4V (Default) 03 14.4 If "Use-Defined" is selected in program 02, this program can be set up. The setting range is from12.0V to 15.0V. If "Llb" is selected in program 02, the setting range is from 12.0V to 15.0V/24.0V to 30.0V/48.0V to 60.0V If this program is selected to modify, the changeable figure will be shown as below. 03 14.4 |
||||
04 | Float voltage | 13.6V (Default) 04 13.6 If this program is selected to modify, the changeable figure will be shown as below. 04 13.6 Increment of each short press is 0.1. Once the value is achieved 15.0V, the value will jump back to 12.0V. |
Increment of each short press is 0.1V. The value will jump back to 12.0V after 15.0V is achieved. If "Use-Defined" is selected in program 02, this program can be set up. The setting range is from 12.0V to 15.0V. If "Llb" is selected in program 02,this parameter is consistent with Absorption voltage |
4.4 LCD setting (Continued)
Battery Charging Status. | Battery voltage | LCD Display |
Status | ||
Constant Current mode / Constant Voltage mode | < 2V/cell | 4 bars will flash in turns. |
2~2.083V/cell | The right bar will be on and the other three bars will flash in turns. | |
2.083~2.167V/cell | The two right bars will be on and the other two bars will flash in turns. | |
> 2.167 V/cell | The three right bars will be on and the left bar will flash. | |
Floating mode | Batteries are fully charged. | 4 bars will be on. |
Parameter | Unit | Battery type | Absorp. Stage Volt | Float Stage Volt | Equalize Stage Volt | En/Disable | Absorp. Time Minutes | Equalize Time Minutes | Equalize Interval Days |
Option | AGM | 14.4 | 13.6 | 14.6 | Disable | 150 | 60 | 120 | 30 |
Option | Flooded | 14.6 | 13.8 | 14.6 | Disable | 150 | 60 | 120 | 30 |
Default Customized | Disable | 150 | 60 | 120 | 30 | ||||
Option | Llb | Disable |
05 | Battery rated voltage | Auto (Default) 05 AVO |
If "AUO" is selected, connected battery voltage system will be automatically detected. Note:Llb mode can't set the AUO |
12V 05 124 |
If "12V" is selected, the unit is considered as 12V battery system. | 24V 05 244 |
If "24V" is selected, the unit is considered as 24V battery system. | 48V 05 484 |
If "48V" is selected, the unit is considered as 48V battery system. Note: MPPT 30A,45A(12/24V) can't set the Absorption voltage to 48v. |
06 | Battery C.V. charging duration | 150 minutes (Default) 06 150 |
The setting range is from 5 minutes to 900 minutes. Increment of each short press is 5 minutes. It will jump back to 5minutes after 900 is achieved. | ||||||
07 | BTS temperature compensation ratio | 0mV (Default) 07 0.0 |
The setting range is from 0mV to 60.0mV. Increment of each short press is 0.1 mV. The value will jump back to 0mV after 60.0mV is achieved. For each 12V battery, the derated battery charging voltage is followed the below formula: (Battery temperature - 25 o C) * BTS ratio. | ||||||
08 | Battery equalization enable/disable | Disable (Default) 08 E9d |
In the lithium battery mode, it is disabled by default and cannot be set. | Enable 08 ЕЧЕ |
|||||
09 | Battery equalization voltage | 14.6V (Default) 09 14.6 |
The setting range is from 12.0V to 15.5V. Increment of each short press is 0.1V. The value will jump back to 12.0V after 15.5V is achieved. |
||||||
10 | The maximum current of battery equalization | 15A (Default) 10 158 |
The setting range is from 30A,45A, 60A,80A, 100A or 120A.Increment of each short press is 1A. The value will jump back to 30A,45A, 60A, 80A, 100A or 120A is achieved. |
11 | Battery equalized time | 60 minutes (Default) 11 60 |
The setting range is from 5 minutes to 900 minutes. Increment of each short press is 5 minutes. It will jump back to 5 minutes after 900 is achieved. | ||||||
12 | Battery equalized timeout | 120 minutes (Default) 12 120 |
The setting range is from 5 minutes to 900 minutes. Increment of each short press is 5 minutes. The value will jump back to 5 minutes after 900 minutes are achieved. | ||||||
13 | Equalization interval | 30 days (Default) 13 30d |
The setting range is from 0 day to 90 days. | ||||||
14 | Equalization activated immediately | Disable (Default) 14 A85 |
If equalization function is enabled in program 08, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will shows" E ". If "Disable” is selected, it will cancel equalization function until next activated equalization time arrives based on program 13 setting. At this time, "E9" will not be shown in LCD main page. | Disable (Default) 14 AEN |
4.5 Reference Code
Type | Code | Event | Type | Code | Event | ||
Fault | 01 | Over charge current | Warning | 20 | PV is low loss | ||
02 | Over temperature | 21 | Output derating caused from high PV voltage | ||||
03 | Battery voltage is too low | 22 | Output derating caused from high temperature | ||||
04 | Battery voltage is high | 23 | Low alarm for battery temperature | ||||
05 | PV high loss | ||||||
06 | Battery temperature is too low | ||||||
07 | Battery temperature is too high | ||||||
No display in LCD screen. | 1. Restart the charger. 2. If the problem remains, please contact your installer. |
1. Keep the charger in the cool environment. 2. If the problem remains, please contact your installer. |
1. Check the battery wire connection. 2. If the wire connection is ok, please contact your installer. |
1. Reconnect the battery to the charger. 2. If the problem remains, please contact your installer. |
1. Please check the voltage of the solar panel, it should be less than 140V or 190V. 2. If the voltage is ok, please contact your installer. |
1. Check your remote temperature sensor and your battery ambient temperature. 2. If the problem remains, please contact your installer. |
1. Check your remote temperature sensor and your battery ambient temperature. 2. If the problem remains, please contact your installer. |
1. Check battery wire connection. 2. Push the button, if the problem remains, please contact your installer. |
5. CHARGING LOGIC
5.1 3-stage Charging
In general, this solar charge controller is designed with 3-stage battery charging algorithm for fast, efficient, and safe battery charging. The following picture shows the sequence of charging stages.
1) Bulk charge stage
In bulk charge stage, charge current begins to flow, typically at the maximum rate of the charge source. The controller will supply solar power to charge battery as much as possible.
2) Absorption stage
When battery charging voltage is reached to Absorption voltage point, the charging stage changes from bulk charge to Absorption. Constant-voltage regulation is used to maintain battery voltage at the Absorption stage. If the charging current drops to one-tenth of the maximum charging current setting point, the charging status will change to Float stage.
If the elapsed time of absorption stage is over setting value for C-V charging time, it will also transfer to Float stage.
• Float timeout
If the battery voltage remains lower than the Float voltage for 30 minutes, the controller will return to Bulk charging stage.
3) Float Stage
After the battery is fully charged in the Absorption stage, the controller will reduces the battery voltage to the setting point of Float voltage. Once in Float stage, constant-voltage regulation is used to maintain battery voltage at setting point of float voltage.
In lithium battery mode: the charging logic has no floating charge stage
• Float cancel voltage
Once the battery voltage drops to setting point of Float cancel voltage, the controller also returns to Bulk charging stage. Float cancel voltage = Floating charging voltage - (1V x battery numbers in series)
5.2 Equalize Stage
Equalization function is added into solar charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.
• When to Equalize
In Absorption stage, if the charging current drops lower than the maximum charging current of battery equalization, the controller will start to enter Equalize stage.
If solar charge controller is working in float stage, but at this time, the setting equalization interval (battery equalization cycle) is arrived, it will transfer to equalize stage.
• Equalize charging time and timeout
In Equalize stage, based on maximum charging current of battery equalization, the controller will supply solar power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the solar charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the solar charge control will stop equalization and transfer to float stage.
5.3 Setting Parameter and Default Value
Recommended and default parameter settings are listed below.
6. TROUBLE SHOOTING
Fault Code | Fault Event | Situation | Fault Code | Fault Event | Situation |
01 | Over charge current | 1. Restart the charger. 2. If the problem remains, please contact your installer. |
20 | PV is low loss | 1. Please check the voltage of the solar panel, it should be less than 140V or 190V. 2. If the voltage is ok, please contact your installer. |
02 | Over temperature | 1. Keep the charger in the cool environment. 2. If the problem remains, please contact your installer. |
21 | Output derating caused from high PV voltage | 1. Check your remote temperature sensor and your battery ambient temperature. 2. If the problem remains, please contact your installer. |
03 | Battery voltage low | 1. Check the battery wire connection. 2. If the wire connection is ok, please contact your installer. |
22 | Output derating caused from high temperature | 1. Check your remote temperature sensor and your battery ambient temperature. 2. If the problem remains, please contact your installer. |
04 | Battery voltage high | 1. Reconnect the battery to the charger. 2. If the problem remains, please contact your installer. |
23 | Low alarm for battery temperature | |
05 | PV high loss | No display in LCD screen. | 1. Check battery wire connection. 2. Push the button, if the problem remains, please contact your installer. |
||
06 | Battery temperature too low | ||||
07 | Battery temperature too high |
7. SPECIFICATIONS
Table 1 Electrical Specifications
MODEL | SCCM3024 | SCCM4524 | SCCM4548 | SCCM6048 | SCCM8048 | SCCM10048 | SCCM12048 |
Maximum Battery Current | 30Amps | 45Amps | 45Amps | 60 Amps | 80 Amps | 100Amps | 120 Amps |
Nominal System Voltage | 12VDC/24VDC | 12,24VDC(Auto detection) | 12V, 24V, 48V DC (Auto detection) | ||||
Maximum Solar Input Voltage | 95V | 145V | 195V | ||||
PV Start-up Voltage | 15V | 15V | |||||
PV Array MPPT Voltage Range | 15-80VDC/30-80VDC | 15-130VDC/30-130VDC | 15-170VDC/30-170VDC | ||||
Maximum Input Power | 12V-420W 24V-830W |
12V-625W 24V-1250W |
12V-625W 24V-1250W |
12V-825W 24V-1650W |
12V-1100W 24V-2200W |
||
PV Array voltage & Battery current | ![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
Heatsink temperature & Battery current | ![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
Transient Surge Protection | Solar high voltage disconnect Solar high voltage reconnect Battery high voltage disconnect Battery high voltage reconnect High temperature disconnect High temperature reconnect |
||||||
Protections | Solar high voltage disconnect Solar high voltage reconnect Battery high voltage disconnect Battery high voltage reconnect High temperature disconnect High temperature reconnect |
Table 2 Battery Charging
MODEL | SCCM3024 | SCCM4524 | SCCM4548 | SCCM6048 | SCCM8048 | SCCM10048 | SCCM12048 |
Charging Algorithm | 3-Step | ||||||
Charging stages | Bulk, Absorption, Float | ||||||
Temperature compensation coefficient | -5 mV/°C/cell (25 °C ref.) | ||||||
Temperature compensation range | 0 °C to +50 °C | ||||||
Charging Curve | ![]() |
Table 3 Mechanical and Environment
Model | SCCM3024 | SCCM4524 | SCCM4548 | SCCM6048 | SCCM8048 | SCCM10048 | SCCM12048 |
Product Size (W x H x D,mm) | 283x160x105 | 283x180x105 | 333x215x120 | 190x151x74 | 205x160x78 | ||
Product Weight (Kg) | 1.2 Kg | 1.8 Kg | 4.0 Kg | 5.1 Kg | 6.4 Kg | 7.0 Kg | |
Ambient Temperature Range | 0°C to +55°C | ||||||
Storage Temperature | - 40°C to 75°C | ||||||
Humidity | 0%-90%RH(No condensing) | ||||||
Enclosure | IP31 (indoor&vented) |
8. MPPT charger controller match to the Inverter
In actual application system, MPPT controller and inverter will charge the battery at the same time, the charging current will excessive to occur unsafe situation, so we add the function of matching the inverter to limit the charging current of the battery. However, since it needs to be matched with MPPT of different manufacturers, but the MPPT charging current cannot be limited. The current solution is to limit the charging current of the inverter.
The inverter match to the MPPT controller is mainly including two function:
- Enabling or disable inverter to match the MPPT function. (Special attention: when upgrading the firmware of the inverter, it needs to disable the function matching MPPT first);
- Limited the charging current of the inverter. The methods are as follows:
a) When the MPPT charging current ≥ inverter setting charging current, the maximum allowable charging current of the inverter equal to 0;
b) When the MPPT charging current < inverter setting charging current, the maximum allowable charging current of the inverter equal to inverter setting charging current subtract MPPT charging current;
8.1 Match the inveter to the MPPT controller:
- To enable the inverter to match the MPPT controller, the inverter and MPPT controller should be switched on first, and the communication lines between them have been connected;
- Then press the "Down"button of the inverter for more than 2.5 seconds, until the MPPT charger icon flashes. At this time, you can release the button. The icon flashing indicates that the inverter is trying to communicate with the MPPT. The inverter is releasing. After pressing the button for 10 seconds, the icon stops flashing. When the communication is successful, it means that the function is successfully enabled.
- After successfully enabling, the matching MPPT function flag will be saved in the EEPROM. Restarting the inverter does not need to be manually enabled again.
- After successfully enabling, turning the page on the LCD screen will display MPPT PV voltage, power and other information.
Action | LCD display | Action | LCD display |
Matching MPPT function is prohibited | ![]() |
8.2 Matching MPPT function is prohibited:
- To prevent the inverter from matching the MPPT function, the MPPT should be turned off or the communication connection between the two should be disconnected.
- Then long press the "Down"button of the inverter for more than 2.5 second, until the MPPT charger icon flashes. At this point, the button can be released. The flashing icon indicates that the inverter is trying to communicate with MPPT. The flashing icon will stop 10 seconds after the button is released. When communication fails, it means it is forbidden successfully.
Action | Instruction | LCD display |
Match MPPT function | Long press"Down"button until the icon in the red box in the right picture flashes, indicating that the inverter is trying to communicate with MPPT. The icon disappears after the inverter loosens the button for 10 seconds. | ![]() |
8.3 Matching MPPT function successfully enabled:
Action | Instruction | LCD display |
Match MPPT function to enable successfully | If MPPT is in charging state: When the MPPT function is successfully enabled, the icon in the red box in the right picture will appear | ![]() |
Match MPPT function to enable successfully | If MPPT is not in the charging state, but PV voltage is greater than 30V and is in the startup state: When the MPPT function is successfully enabled, the icon in the red box in the right picture will appear | ![]() |
8.4 Matching MPPT function is prohibited successfully:
Action | Instruction | LCD display |
Match MPPT function | When the matching MPPT function is prohibited successfully, MPPT icon information will no longer be displayed | ![]() |
Whether matching MPPT function enables judgment | 1. If the MPPT function is enabled, the LCD interface page turning will display PV voltage, power and other information; 2. If the matching MPPT function is enables judgment prohibited, the LCD interface page turning will not display PV voltage, power and other information; |
![]() |
File Info : application/pdf, 12 Pages, 1.25MB
DocumentDocumentReferences
Related Documents
![]() |
Felicitysolar IVEM Series Hybrid Solar Inverter (IVEM5048) - 5000W Explore the Felicitysolar IVEM Series Hybrid Solar Inverter, model IVEM5048. This 5000W inverter features pure sine wave output, MPPT solar charge controller, high PV voltage support (500V), and parallel operation capabilities for efficient home and commercial solar energy systems. |
![]() |
Solar Inverter IVEM3024/5048: Features and Specifications Detailed information on the Felicitysolar IVEM3024/5048 solar inverter, including features like configurable input voltage, battery charging, AC/Solar priority, and technical specifications for both models. |
![]() |
Felicitysolar LiFePO4 Battery System User Manual for Households User manual for the Felicitysolar LiFePO4 Battery System (Model FLA48200) for households, covering installation, operation, specifications, and emergency procedures. |
![]() |
Felicitysolar IVEM Series Solar Inverter User Guide This user guide provides comprehensive instructions for the Felicitysolar IVEM Series solar inverters, covering models from 8KVA to 12KVA. It details installation, operation, safety precautions, specifications, and troubleshooting for these advanced solar inverters. |
![]() |
Felicitysolar FLA48100-EU User Manual: Installation and Operation Guide Comprehensive user manual for the Felicitysolar FLA48100-EU LiFePO4 battery system. Covers safety, transportation, installation, operation, maintenance, and troubleshooting for reliable household energy storage. |
![]() |
Felicitysolar FLA12200 LiFePO4 Battery System User Manual Comprehensive user manual for the Felicitysolar FLA12200 LiFePO4 Battery System, covering installation, operation, safety instructions, specifications, and troubleshooting for household use. |
![]() |
Felicitysolar LiFePO4 Battery System for Households User Guide Comprehensive user guide for the Felicitysolar LiFePO4 Battery System for Households (Model LPBF24100-M), covering installation, operation, safety instructions, specifications, fault codes, and emergency procedures. |
![]() |
Felicitysolar LPBF48200-A User Manual: LiFePO4 Battery System for Households Comprehensive user manual for the Felicitysolar LPBF48200-A LiFePO4 Battery System. Covers installation, operation, maintenance, safety, and troubleshooting for household energy storage. |