Siemens Dual Function AFCI/GFCI Circuit Breaker Installation Instructions

Important Safety Information

⚠️ DANGER: Hazardous voltage. Will cause death or serious injury.

Turn off and lock out power supplying equipment before installing AFCI/GFCI.

⚠️ CAUTION: Hazard of Equipment Damage. Will cause damage to the AFCI/GFCI module.

Do not reverse-feed or back-wire. Do not subject to megger, high voltage, or hi-pot test. Remove the breaker before high-potting occurs on the system or on the circuit.

Safety Instructions

Figure 1: Circuit Breaker Components

The diagram shows a dual function AFCI/GFCI circuit breaker with the following labeled components:

Installation Instructions

  1. Turn "OFF" and lock out the power to the equipment in which the AFCI/GFCI is to be installed.
  2. Move the handle of the breaker (A) to the "OFF" position.
  3. Engage the back of the AFCI/GFCI with the mounting tabs in the panelboard. For the plug-in type, push down firmly on the front end to engage the line terminal stab. For the bolt-in type, securely fasten the line terminal to the panelboard load bus.
  4. Connect the panelboard neutral (pig-tail) (B) wire to a load center or panel neutral bar (C) as shown in Figure 1. Torque per specifications on wiring diagram or equipment label.
  5. Strip insulation off load wires to a length of 3/8 in.
  6. Connect load neutral wire (D) into terminal (H) and load power wire (E) to terminal (I) as shown in Figure 1. Ensure that wire connectors are properly torqued to 25 lb-in.

Testing Instructions

  1. Turn on power to load center or panelboard.
  2. Turn "ON" the AFCI/GFCI handle.
  3. Press blue test button (F) as shown in Figure 1.

The AFCI/GFCI breaker is functioning properly when:

LEDs (J, M) are used to indicate the last known trip condition. Test every month.

Troubleshooting

Problem: AFCI/GFCI does not trip after pressing the test button.

Possible Cause Solution
Panelboard is not energized Check to ensure that the panelboard is energized.
The circuit breaker handle is in the "OFF" position The circuit breaker handle must be in the "ON" position.
The circuit breaker is in the tripped position Reset the circuit breaker by switching the handle to the "OFF" position and then to the "ON" position.
Panel neutral (pigtail) is not connected to the neutral bus bar Check that the load power wire, panel neutral (pig-tail) wire, and load neutral wire are properly connected.

Problem: AFCI/GFCI trips immediately after the AFCI/GFCI or a connected device has been turned on.

Possible Cause Solution
The arc-fault circuit interrupter is not wired properly. Check that the load power wire, panel neutral (pig-tail) wire, and load neutral wire are properly connected. A qualified electrician should make the repairs.
Short-circuit If the AFCI/GFCI trips when a device is turned on, remove the device from the circuit and turn the AFCI/GFCI on. If the AFCI/GFCI does not trip, this would indicate a short in the device. A qualified electrician should make the repairs.
AFCI/GFCI does not have a dedicated neutral Check wiring to ensure that there are no shared neutral connections.
AFCI/GFCI does not have the correct neutral Check wiring to ensure the load power wire and load neutral wire are from the same branch circuit.
A ground-fault condition exists A quick way to check for ground-fault conditions is to substitute a GFCI circuit breaker in place of the AFCI/GFCI. If the GFCI trips, then you have a ground-fault condition. A common ground fault is a grounded neutral, which may only cause a trip under load. This occurs when the neutral conductor contacts a grounded conductor, so check your junction box and fixture connections.
An arc-fault condition exists Reset the circuit breaker by switching the handle to the "OFF" position and then to the "ON" position. If the AFCI/GFCI trips again, call a qualified electrician to make the repairs.

Problem: AFCI/GFCI trips after it has been turned on, but not immediately

Possible Cause Solution
The arc-fault circuit interrupter is not wired properly. Check that the load power wire, panel neutral (pig-tail) wire, and load neutral wire are properly connected. A qualified electrician should make the repairs.
Overloaded circuit There are probably too many devices plugged into the circuits and overloading the AFCI/GFCI.
An arc-fault condition exists Reset the circuit breaker by switching the handle to the "OFF" position and then to the "ON" position. If the AFCI/GFCI trips again, call a qualified electrician to make the repairs.

If solutions do not work, the AFCI/GFCI circuit breaker must be replaced.

LED Indication Guide (after recent trip has occurred)

Turn AFCI/GFCI to "ON" position. Observe LED indications and compare to chart at right. LED indications will appear for 5 seconds each time the AFCI/GFCI is turned "ON". LED display will appear each time the AFCI/GFCI is reset up to 30 days after last trip.

LED (J) LED (M) Last Known Trip Condition
OFF OFF OVERCURRENT
ON OFF ARC FAULT or PTT Passed
ON ON ARC FAULT TO GROUND
ON ON GROUND FAULT

Clearing the last known trip condition:

  1. Turn the AFCI/GFCI to the "OFF" position.
  2. Press and hold the PTT button.
  3. Turn the AFCI/GFCI to the "ON" position.
  4. Release the PTT button after 3 seconds.
Models: Q115DFP, Dual Function Afci-Gfci Circuit Breaker, Afci-Gfci Circuit Breaker, Dual Function Circuit Breaker, Circuit Breaker, Breaker

File Info : application/pdf, 4 Pages, 240.96KB

48026750 Microsoft Word for Microsoft 365

Related Documents

Preview Siemens Load Centers & Circuit Breakers: PL & ES Series Product Catalog
Explore the Siemens SPEEDFAX™ 2017 catalog section detailing PL and ES Series Load Centers, WireGuide™ Load Centers, and Circuit Breakers. Find product features, specifications, and cataloging information for electrical distribution solutions.
Preview Siemens US2:ECQTH3 Miniature Circuit Breaker Data Sheet
Data sheet for the Siemens US2:ECQTH3, a 2-pole, low voltage residential miniature thermal magnetic circuit breaker designed for electrical distribution applications, compliant with UL 489 standards.
Preview Siemens Loadcentre Product Catalogue
Comprehensive guide to Siemens loadcentres, including single-phase and three-phase options, main lug and main breaker configurations, and various accessories and replacement parts. Details product features, selection criteria, and technical specifications for residential and commercial applications.
Preview Siemens WL Circuit Breakers: Selection and Application Guide
Comprehensive guide to Siemens WL Low Voltage Circuit Breakers, covering selection, application, features, specifications, and accessories for UL489 and UL1066 listed products.
Preview Siemens SENTRON 5SY4603-5 Miniature Circuit Breaker Datasheet
Technical datasheet for the Siemens SENTRON 5SY4603-5 miniature circuit breaker. Features include 4 poles (3P+N), AC operation, 400V, 10kA breaking capacity, IP20 protection, and various environmental and connection specifications.
Preview Siemens US2:B235 Low Voltage Molded Case Circuit Breaker - 35A, 2-Pole
Datasheet for the Siemens US2:B235, a 2-pole, 35A low voltage molded case circuit breaker designed for electrical distribution applications. Features UL 489 standard compliance and thermal-magnetic trip range.
Preview Siemens Loadcentres, Circuit Breakers, and Surge Protection Catalog
Comprehensive catalog detailing Siemens Loadcentres, including single-phase and three-phase models (EQL, SNC, SEQ, EQ3, EQ4, EQG), circuit breakers (Type Q, BQ, Blue Line, AFCI/GFCI), surge protective devices (BoltShield™, FSPD), and accessories. Provides selection guides, specifications, and ordering information for residential and commercial electrical distribution applications.
Preview Siemens SENTRON 5SY4610-5 Miniature Circuit Breaker Datasheet
Technical datasheet for the Siemens SENTRON 5SY4610-5 miniature circuit breaker, detailing specifications, approvals, and dimensions. Features 4 poles, 10A rating, 10kA/20kA breaking capacity, and IP20 protection for industrial and infrastructure applications.