Pipe shoe sliding element FMFS
Element for fixing FMPS pipe shoes in case of thermal expansion
Diagram showing the FMFS sliding element mounted on a pipe shoe, designed to accommodate thermal expansion movement.
Illustration of a slide bearing with a pipe shoe attached.
Illustration of a frame construction utilizing channel systems.
Applications
- Fixation of pipelines for thermal expansions.
- For indoor and outdoor application.
Advantages
- The sliding element FMFS can be attached to the pipe shoes FMPS to provide axial guidance and lifting for safe guidance in the moment of pipe expansion.
- The sliding element FMFS fits to all base plates of the pipe shoes FMPS due to the variably applicable distance plates and is easy to install.
Properties
Material: steel S235JR (material no. 1.0038) according to DIN EN 10025-2
Zinc plating: hot-dip galvanised according to DIN EN ISO 1461
FMFS SP: material plastic inlay: PTFE polytetrafluorethylene, colour white
Installation FMFS
Installation diagram detailing dimensions for thermal expansion: X1 (8-9 mm), X (10-12 mm), and spacing (2-5 mm), with a recommended torque of 75 Nm.
Technical Data
Item | Item no. | Length L [mm] | Width B [mm] | Thickness S [mm] | Sales unit [pcs] |
---|---|---|---|---|---|
FMFS SP | 547853 | 113 | 40 | 4.5 | 10 |
FMFS SH | 547854 | 130 | 35 | 4.0 | 10 |
FMFS DP4 | 547855 | 130 | 35 | 4.0 | 20 |
FMFS DP6 | 547856 | 130 | 35 | 6.0 | 20 |
FMFS LL | 547857 | 130 | 60 | 6.0 | 20 |
Technical Information
Diagrams for technical information showing base plate groups (BG 1, BG 2, BG 3) and their associated thickness (S) and required sliding elements for different expansion gaps (X1, X2).
BG 1 and BG 2 are for pipe shoe thickness S and require X1 = 8-9 mm gap, using 1 or 5 or - sliding elements.
BG 3 is for pipe shoe thickness S and requires X2 = 10-12 mm gap, using 2 or 4 sliding elements.
Item | Item no. | Thickness S [mm] | BG 1 [pcs] | BG 2 [pcs] | BG 3 [pcs] |
---|---|---|---|---|---|
FMFS SP | 547853 | 4.5 | 1 | 2 | 2 |
FMFS SH | 547854 | 4 | 1 | 2 | 2 |
FMFS DP4 | 547855 | 4 | 5 | 2 | 2 |
FMFS DP6 | 547856 | 6 | - | 4 | 4 |
FMFS LL | 547857 | 6 | - | 2 | 2 |
Additional note: 2 FMFS UB fixed point brackets are required, size matching the FMP profile. Assembly group details are listed in tables for pipe shoes FMPS.