Installation & Wiring Instructions
TLP/1S High Voltage
Emergency Conversion Kit
TLP-1S-K-EM TLP-1S High Voltage Emergency Conversion Kit
PLEASE READ THESE INSTRUCTIONS BEFORE COMMENCING INSTALLATION & LEAVE WITH END-USER
Description:
The Lite plan range of TLP/1S modules is designed to convert a wide range of high-voltage LED types. The TLP/1S will convert most standard LED luminaires and arrays between 55V and 300V. This makes the TLP/1S suitable for linear luminaires, high voltage boards, and even some mains voltage lamps (subject to testing).
The modules are designed to generally be installed by breaking into the low voltage connection between the mains LED driver and the LEDs and allow the LEDs to be operated as normal under mains healthy conditions and operated at the reduced light output in an emergency.
The module automatically adjusts the output LED current to provide the best match between the battery and the load, providing maximum illumination whilst ensuring full battery duration and being compatible with a wide range of lighting.
The unit will recharge the batteries after the test of clause 22.3 of BS EN 61347-2-7:2012.
The battery is fitted with a PCM to protect the supply voltage against reverse polarity.
Specification:
Input Voltage | 230-240 Volts AC 50/60 Hz |
Power Rating (Charging) | 2.5W 15mA λ = 0.70 |
Power Rating (Standby) | 1.3W 9mA λ = 0.60 |
Insulation between supply & battery | Double Reinforced |
Duration | 3 hours |
Ambient Temp. Ta | 0°C to + 50°C |
Max Case Temp. Tc | 70°C |
Max Battery Temperature | 55°C |
Recharge Period | 24 Hours |
Battery Type | 3.2V 4.8Ah LiFePO4 |
Charge Current | 225mA nominal |
Discharge Current | 1000mA nominal |
Charge Voltage Limit | 4.0 Volts |
Discharge Voltage Limit | 2.4 Volts |
Ingress Protection | IP20 |
Recharge Period | 24 Hours |
Module Size (L x W x H) | 213mm x 30mm x 22.5mm |
Module Fixing Centers | 207mm |
Module Weight | 0.085Kg |
Battery Details (mm) Stick 230mm x 24mm x 22mm FC = 220mm |
|
Remote 220mm x 32mm x 34mm | |
Battery Weight Cable Entry Size |
0.14Kg 0.5mm – 1.5mm |
Fixing Centres 207mm
TLP/1S
Prated – 3W to 80W
Irated – 38-7mA
Voltage Range 55 – 300 Volts
Open Circuit Voltage (U-OUT) = 340 Volts
Warning
Avoid running the LED mains driver and emergency pack without the load connected. Failure to do so may result in damage to the LED array
Important
It is recommended that the module is installed by a competent person ensuring the installation complies with the necessary standards. Lite plan accepts no responsibility for injury, damage, or loss, which may arise as a result of incorrect installation, operation, or maintenance.
The conversion requires an unswitched supply for charging the battery and a switched supply if the unit is being used for maintained operation.
ISOLATE BOTH MAINS SUPPLIES AND DISCONNECT THE BATTERY BEFORE INSTALLATION OR MAINTENANCE.
Installation
When converting a luminaire observe the following points:
- Ensure that the module and battery pack will operate within their temperature ratings at their chosen location.
- Wire the module & battery into the luminaire as per the wiring diagram on Pg2.
- Ensure that the Permanent Live & Switched Live feeds are connected correctly.
- Arrange the wiring to avoid running the 240 Volt AC cables next to the module’s output to the LED to obtain the best EMC results.
- Requirements for ‘F’ markings must be observed.
- Identify clearly the NEW Un-switched supply.
- Ensure the LED Charge Indicator is clearly visible in everyday use.
- If fitted within a metal enclosure, connect the earth terminal to a metal gear tray for improved EMC.
- This module is not intended for use in luminaires for high-risk task area lighting.
- This module is protected against battery polarity reversal.
- Do not connect the battery until an assured permanent supply is present.
Typical
Conversion
Wiring Diagram
Testing/Commissioning:
- Ensure the load is connected.
- Connect the battery.
- Switch on the Unswitched Supply – Check the Charge LED illuminates.
- Switch on the Maintained Supply – Check the LED illuminates as normal.
- Switch off the Maintained Supply.
- Switch off the Unswitched Supply – Check the Charge LED extinguishes and the load LED illuminates at a reduced output.
- Enter the commissioning date on the Battery Pack. Switch on the Unswitched Supply
Luminaire Ref/Location …………….. |
In Case of difficulty, contact the Installation Engineers:- Tel: ……………… |
|||||||||||
Full Recharge Time 24 Hours | Duration 3 Hours | I Lamp Type – LED | ||||||||||
ROUTINE TEST RECORD | ||||||||||||
Year 1 | Year 2 | Year 3 | Year 4 | Year 5 | ||||||||
Monthly Test | Signed | Date | Signed | Date | Signed | Date | Signed | Date | Signed | Date | ||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Functional | ||||||||||||
Three Hour |
Tel +44 (0)1708 372223
www.liteplan.com
customerservice@liteplan.com
RM3 0AP. UK
Lite plan reserve the right to change color,
price or specification without prior notice
ISS 242202