LEVITON-Inform-App-LOGO

LEVITON Inform AppEVITON-Inform-App-PRODUCT

INSTALLATION INSTRUCTIONS

ELECTRICAL SERVICE
For instructions on the installation and connection of the switch to the electrical service, refer to the installation instructions included in the box. Instruction sheets can also be found on www.leviton.com.

Cabling
RS-485 is a three-wire bus. One twisted pair is required for the two data signal wires, plus an additional wire for a common reference, which does not need to be twisted. A cable with two twisted pairs may also be used, where one or both conductors of the second pair is/are used for the common.

Shielding
A shield may not be needed for short networks, but is recommended and required for long networks or networks in an electrically noisy environment. The shield must be connected to a ground point at ONE side only. Although the shield can be used for the common reference, it is preferable to use a separate wire for the common.

Termination
RS-485 (EIA-485) networks typically require a termination resistor of 120Ω. Depending on the bus, a termination resistor may be needed. Additional bias resistors may also be needed.

Topology
Utilize a daisy-chain bus configuration for connecting up to 32 devices.

Connection
The terminal block on the Modbus communication PCBA can accommodate 24 – 16 AWG cable. Connect the communication cable to the terminal block on the Modbus PCBA.

MODBUS CONFIGURATION

The following describes the Modbus commands and messages. The basic instructions should be adequate for Modbus host programming. The Modbus Interface requires about 150 ms to read sensor elements and respond. The default configuration is:

  •  Modbus address: 02
  •  Baud Rate: 19200
  •  Data Length: 8-bit
  •  Parity: Even
  •  Stop Bits: 1

NOTE:
To reset the communication parameters (including device address) to the factory default  settings, press and hold the reset button (SW1) on the Display PCBA for 5 to 7 seconds)

SUPPORTED FUNCTIONS

Function Code [dec] Function Code [hex] Action Relevant Table
03 03 Read Holding Registers
04 04 Read Input Registers
06 10 Write Holding Registers

CONFIGURATION REGISTERS

The following registers represent the Modbus network communication parameters:

  Register Address Data Address [Dec] Data Address [Hex] Data Type Value Range Default Value  
Name Min Max Description
Address 40001 0 0 UINT16 1 247 2 Value between 1 and 247
Baud Rate  

40002

 

1

 

1

 

UINT16

 

96

 

1152

 

192

Modbus Baud rate value/ 100; 96: 9600, 192: 19200,

384: 38400, 576: 57600

Parity 40003 2 2 UINT16 0 2 2 0: No parity, 2: Even Parity,

1: Odd Parity

Stop Bits 40004 3 3 UINT16 1 2 1  
Data Length 40005 4 4 UINT16 8 8 8 The Only acceptable value is 8 for RTU mode

MEASUREMENT REGISTERS
The following registers represent the sensor and alarm outputs available:

 

Name

 

Register Address

Modbus Data Address [Dec] Modbus Data Address [Hex] Number of Modbus Registers  

Data Type

 

Description

Line 1 Voltage 30001 0 0 1 INT16 Line 1 RMS Voltage (V)
Line 2 Voltage 30002 1 1 1 INT16 Line 2 RMS Voltage (V)
Line 3 Voltage 30003 2 2 1 INT16 Line 3 RMS Voltage (V)
Load 1 Voltage 30004 3 3 1 INT16 Load 1 RMS Voltage (V)
Load 2 Voltage 30005 4 4 1 INT16 Load 2 RMS Voltage (V)
Load 3 Voltage 30006 5 5 1 INT16 Load 3 RMS Voltage (V)
Ground Status 30007 6 6 1 UINT16 1: GND/Earth Present,

0: GND/Earth Fault

Switch Status 30008 7 7 1 UINT16 1: Switch Open, 0: Switch Closed
Temperature 30009 8 8 1 INT16 Temperature (°C); Multiply by 0.1
Humidity 30010 9 9 1 UINT16 Relative Humidity (%); 0-100
Liquid Accumulation 30011 10 A 1 UINT16 1: Liquid Accumulation Detected, 0: Absence of Liquid
Line 1 Avg Voltage 30012 11 B 1 INT16 Not yet implemented
Line 2 Avg Voltage 30013 12 C 1 INT16 Not yet implemented
Line 3 Avg Voltage 30014 13 D 1 INT16 Not yet implemented
 

Line 1 LED

 

30015

 

14

 

E

 

1

 

UINT16

Line 1 Voltage State 0: Off (Normal), 2: Energized (Normal), 4: Improper Voltage
 

Line 2 LED

 

30016

 

15

 

F

 

1

 

UINT16

Line 2 Voltage State 0: Off (Normal), 2: Energized (Normal), 4: Improper Voltage
 

Line 3 LED

 

30017

 

16

 

10

 

1

 

UINT16

Line 3 Voltage State 0: Off (Normal), 2: Energized (Normal), 4: Improper Voltage
 

Load 1 LED

 

30018

 

17

 

11

 

1

 

UINT16

Load 1 Voltage State 0: Off (Normal), 2: Energized (Normal), 4: Improper Voltage
 

Load 2 LED

 

30019

 

18

 

12

 

1

 

UINT16

Load 2 Voltage State 0: Off (Normal), 2: Energized (Normal), 4: Improper Voltage
 

Load 3 LED

 

30020

 

19

 

13

 

1

 

UINT16

Load 3 Voltage State 0: Off (Normal), 2: Energized (Normal), 4: Improper Voltage
GND LED 30021 20 14 1 UINT16 Ground Continuity State 2: Normal, 4: Fault
 

Fault LED

 

30022

 

21

 

15

 

1

 

UINT16

General warning error states

2: Normal, 6: Fault. Includes liquid accumulation sensor and internal communication state

Load 1 Current 30023 22 16 2 INT32 Load 1 current in mA
Load 2 Current 30025 24 18 2 INT32 Load 2 current in mA
Load 3 Current 30027 26 1A 2 INT32 Load 3 current in mA
Load 1 Avg Current 30029 28 1C 2 INT32 Not yet implemented
Load 2 Avg Current 30031 30 1E 2 INT32 Not yet implemented
Load 3 Avg Current 30033 32 20 2 INT32 Not yet implemented

DEVICE INFORMATION REGISTERS
The following registers represent the device information available:

 

Name

 

Register Address

Modbus Data Address [Dec] Modbus Data Address [Hex] Number of Modbus Registers  

Data Type

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring Config

 

 

 

 

 

 

 

 

 

 

 

 

 

31001

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

3E8

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

String*

3-7 characters,

plus null terminator:

1P+N+E = Single Phase, Neutral,

Ground

2P+E = Single (split) Phase, Ground

2P+N+E = Single (split) Phase,

Neutral, Ground 3P+E = Three-phase, Ground

3P+N+E = Three-phase, Neutral,

Ground

3PB+E = 4-wire Delta B leg high

 

3PB+N+E = 5-wire Delta B leg high

3PB+E = 4-wire Delta B leg high 3PB+N+E = 5-wire Delta B leg

high

3PC+E = 4-wire Delta C leg high 3PC+N+E = 5-wire Delta leg

high C

3PC+E = 4-wire Delta C leg high 3PC+N+E = 5-wire Delta C leg

high

 

Voltage Config

 

31007

 

1006

 

3EE

 

2

 

uint16

DIP switch-based

user-configured nominal voltage

 

Reserved

31013-

31100

     

87

   
 

Model Number

 

31101

 

1100

 

44C

 

32

 

String*

Device model number; 1-63 characters, plus null terminator
 

Serial Number

 

31133

 

1132

 

46C

 

16

 

String*

Device serial number; 1-31 characters, plus null terminator
 

Display PCBA FW Version

 

31149

 

1148

 

47C

 

6

 

String*

Display PCBA firmware version; 5-11 characters plus null terminator
Power Sense PCBA FW Version  

31155

 

1154

 

482

 

6

 

String*

Power Sense PCBA firmware version number; 5-11 characters
Modbus PCBA FW Version  

31161

 

1160

 

488

 

6

 

String*

Modbus board firmware version number; 5-11 characters

SENSOR DATA FORMAT
Sensor data as delivered as signed and unsigned integers and strings. Consequently, numeric conversion may be required to display in preferred conventional units.

Voltage Format
The voltage value displayed for Line 1, Line 2, Line 3, Load 1, Load 2, and Load 3 is the measured RMS phase voltage measured at their respective switch terminals. Line 1 Avg, Line 2 Avg, and Line 3 Avg are calculated values. Volts (V) = ModbusData.

Current Format
The current value displayed for Line 1 Current, Line 2 Current, and Line 3 Current is the measured RMS current in milliamps. Line 1 Avg Current, Line 2 Avg Current, and Line 2 Avg Current are calculated values. Amps (A) = (ModbusData) /1000

Temperature Format
The measured temperature range is -40.0°C to 125.0°C. The Modbus data range is -400 to 1250. Temperature (°C) = (ModbusData) /10.

Humidity Format
The measured relative humidity range is 0% to 100%. The Modbus data range is 0 to 100. Relative Humidity (%) = ModbusData.

Ground Continuity
The ground continuity sensor has a two-state output: present or fault. The Modbus data is 0 (fault) or 1 (present).

Liquid Accumulation
The liquid accumulation sensor has a two-state output: liquid absent or present. The Modbus data is 0 (absent) or 1 (present).

Switch Position
The switch position sensor has a two-state output: switch open or closed. The Modbus data is 0 (closed) or 1 (open).

ERROR DETECTION
The Inform technology firmware processes the sensor outputs to determine if they are normal for the specified operating conditions. There are a series of status registers that can be used for alerting abnormal operating conditions. These registers control the LED display on the device and are also available to external devices.

Voltage alarms
The voltage sensor outputs, switch position indicator output, and device configuration settings are analyzed to determine if the voltage level present on each switch terminal is normal. These registers are Line 1 LED, Line 2 LED, Line 3 LED, Load 1 LED, Load 2 LED, and Load 3 LED.

  •  Unused terminals yield a “normal – OFF” output.
  •  Load side terminals that are de-energized with the switch turned to the off position also yield an “OFF – normal” output.
  •  An RMS voltage of ≤ 50 V is classified as “de-energized”.
  •  Applicable line side terminals and corresponding load side terminals that are energized when the switch handle is turned to the ON position yield an “Energized – normal” output.
  •  Terminals with voltage present when there should not be, or improper voltage level, yield an output of “improper voltage level.”
  •  The Modbus data is 0 (Off – Normal), 2 (Energized – Normal), or 4 (Improper voltage level).

Ground Continuity Alarm
This alarm is a redundant register for indicating the ground continuity sensor’s status, either normal or fault. The Modbus data is 2 (Normal) or 4 (Fault).

General Fault Alarm
This register is a “catch-all” for a variety of error conditions. If the device experiences any internal communication failures between the sensor and processing electronics or the liquid accumulation sensor detects liquid, an alarm will be generated. The Modbus data is 2 (normal) or 6 (error detected).

Situation Error Response Modbus Error Code
Query is not an allowable action for the server (slave) Invalid Function Error 0x01
Writing to an undefined holding register Invalid Address Error 0x02
Writing invalid data to a holding register Invalid Data Error 0x03
Reading undefined holding register Invalid Address Error 0x02
Reading undefined input register Invalid Address Error 0x02
Incorrect CRC None N/A
Incorrect Parity None N/A
Incomplete Modbus Message None N/A
Incorrect interbyte timing None N/A

Documents / Resources

LEVITON Inform App [pdf] User Guide
Inform App, Inform, App

References

Leave a comment

Your email address will not be published. Required fields are marked *