LENNOX V0CTRL95P-3 Mini Split BACnet Gateway
- Function: Input Supply Power
- BACnet Connection: 24VAC
- I/O: 25% ~ 90%
- Operating Temperature Range: 10-1/2 in. X 10 in. X 2-3/8 in. (26 cm X 25 cm X 6 cm)
Product Usage Instructions
Network Setting
Connect the device to a network port using an Ethernet interface (Eth0). The factory-set device address is 192.168.1.8.
Security
- Default Admin User Name: admin
- Default Admin Password: 123456
System Connections
- The BACnet gateway can monitor and control up to 320 VRB & VPB VRF systems with up to 960 VRF outdoor units and 2560 VRF indoor units.
- Ensure proper connection based on the BACnet address, which identifies the BACnet gateway bus, unit type, and unit’s address.
Setup Instructions
- Directly connect a PC network port to the gateway Ethernet connection.
- Configure the PC network port with the proper settings.
- Open a web browser and enter the IP address 192.168.1.8.
- You will be prompted to enter the default admin name and password.
- Once connected, follow the on-screen instructions to set up the Gateway on your BACnet network.
Equipment List
Package 1 of 1 consists of:
- 1 – BACnet gateway
- 1 – DIN rail
- 1 – Instruction and Application Guide
General Safety
- The Lennox VRF, Mini-VRF, and Mini-Split BACnet Gateway allows connection of those systems to a building management system (BMS) using BACnet protocols.
- Setup can be accomplished through the use of a web browser and a PC with a network port.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life.
- Installation and service must be performed by a licensed professional HVAC installer or equivalent, a service agency, or the gas supplier.
WARNING: Do not operate the device with wet hands.
CAUTION: Before attempting to perform any service or maintenance, turn the electrical power to the unit OFF at the disconnect switch.
CAUTION: Do not install the device in areas where heavy oil, vapor, or gases containing sulfur may exist, or the controller may be damaged.
CAUTION: Clean device using a clean, damp cloth. Do not spray cleanser on or around the device.
IMPORTANT: These instructions are intended as a general guide and do not supersede local codes in any way.
- Consult the authorities having jurisdiction before installation. Read all of the information in this manual before operating this equipment.
Network Setting
- There is an Ethernet interface in the device (Eth0). The factory-set device address is 192.168.1.8.
Security
- Default Admin User Name: admin
- Default Admin Password: 123456
Specifications
Function | Description |
Input Supply Power | 24VAC |
BACnet Connection | BACnet/IP |
I/O | 4-port 485 interface |
Operating Temperature Range | 32°F ~ 104°F (0°C ~ 40°C) |
Operating Humidity Range (Rh) | 25% ~ 90% |
Dimensions | 10-1/2 in. X 10 in. X 2-3/8 in. (26 cm X 25 cm X 6 cm) |
DIN Mounted |
- The V0CTRL95P-3 Lennox BACnet gateway can monitor and control up to 320 VRB & VPB VRF sys-tems with up to 960 VRF outdoor units and 2560 VRF indoor units.
- See Appendix A. All Lennox VRF P3 outdoor and indoor units can be connected to the V0CTRL95P-3 Lennox BACnet gateway. See the LVM and BACnet Gateway installation man-ual (507897) for instructions for detailed connection information.
System Connections
The BACnet address is a four-digit number that identifies the BACnet gateway bus (port), the type of unit (indoor unit or outdoor unit), and the unit’s address. Device ID = XXXX
X | X | X | X | |
BACnet Bus (Port) Number | Unit Type | Unit Address | ||
(0-3) | 0 | Indoor Unit | (Indoor Unit 0-63)
(Outdoor Unit 0-31) |
|
1 | Outdoor Unit |
- Example – 0001 indicates BACnet device number 0, indoor unit type, and indoor unit number 01.
- Direct connect with PC from PC network port to the gateway Ethernet connection – Configure PC network port with the proper settings and use a web browser to connect – enter the IP address 192.168.1.8 and you will be prompted to enter name/password.
- Once connected, you will see the options for setting up the Gateway to reside on your bacnet network.
- Once connected, you will see the options for setting up the Gateway to reside on your bacnet network.
- User name = admin
- User Password = 123456
Object Type | Abbreviation |
Analog Input | AI |
Analog Output | AO |
Analog Value | AV |
Binary Input | BI |
Binary Output | BO |
Binary Value | BV |
Multi-state Input | MI |
Multi-state Output | MO |
Multi-state Value | MV |
BACnet Object Points List
Indoor Units Points List
Object ID | Object Name | Value | R/W | Description |
BV 1 | On/Off Setting | “0-OFF
1-ON” |
R/W | Indoor unit ON/OFF setting |
MV 1 | Mode Setting | “1-OFF
2-Fan 3-Cooling 4-Heating 5-Auto 6-Dry” |
R/W | Indoor unit mode setting |
MV 2 | Fan Speed Setting | “1/2-Low 3/4-Medium 5/6/7-High 8-Auto
9-OFF” |
R/W | Indoor unit fan speed setting |
AV 1 | Temperature Setting | 62~86F(17~30C) | R/W | Indoor unit setpoint for cooling, heating, and dry mode |
AV 2 | Dual Point (Cooling) Setting | 62~86F(17~30C) | R/W | Indoor unit auto mode cooling setpoint setting |
AV 3 | Dual Point (Heating) Setting | 62~86F(17~30C) | R/W | Indoor unit auto mode heating setpoint setting |
AV 4 | Cool Temperature Limit Setting | 62~86F(17~30C) | R/W | Indoor unit low limit of cooling, auto cooling, and dry setpoint |
AV 5 | Heat Temperature Limit Setting | 62~86F(17~30C) | R/W | Indoor unit up limit of heating and auto heating setpoint |
MV 3 | Mode Limit Setting | “0-Unlock
1-Locked in cooling mode 2-Locked in heating mode” |
R/W | Indoor unit mode lock/ unlock setting |
MV 5 | Fan Lock/Unlock Setting | “1/2-Locked in low speed
3/4-Locked in medium speed 5/6/7-Locked in high speed 8-Unlock” |
R/W | Indoor unit fan speed lock/unlock setting |
BV 4 | Remote Control Lock Setting | “0-Unlock
1-Wireless control locked” |
R/W | Wireless controller lock/unlock setting |
BV 5 | Controller Lock Setting | “0-Unlock
1-Wired control locked” |
R/W | Wired controller lock/ unlock setting |
AI 1 | Room Temperature | Actual value | R | Indoor unit room temperature sensor value |
BI 2 | Alarm Indication | “0-No malfunction code 1-Malfunction code” | R | If there is an error code for the indoor unit |
AI 9 | EXV Opening | Actual value | R | Indoor unit EEV opening |
AI 10 | Software Version | Actual value | R | Indoor unit software version |
AI 11 | Indoor type | “1-(V33B)Four-way cassette 2-(VWMB)Wall mounted
3-(VMDB)Medium static pressure duct 5-(VVCB)Vertical air handler 6-(VHIB)High static pressure duct 7-(V22B)Compact four-way cassette 8-(VCFB)Ceiling/Floor 11-(VOSB)Dedicated outside air duct 14-(VOWA)One way cassette 21-AHU control kit” |
R | Indoor unit series name |
AI 12 | Indoor Capacity | “8-7Kbtu/h 10-9Kbtu/h 12-12Kbtu/h 17-15Kbtu/h 20-18Kbtu/h 25-24Kbtu/h 32-30Kbtu/h 40-36Kbtu/h 50-48Kbtu/h 60-54Kbtu/h 65-60Kbtu/h 80-72Kbtu/h
100-96Kbtu/h” |
R | Indoor unit capacity |
Outdoor Units Points List
Object ID | Object Name | Value | R/W | Description |
MI 1 | Mode Status | “1-OFF
2-Reserved 3-Cooling 4-Heating 5-Cooling test 6-Mix Cooling 7-Mix Heating 8-Heating test” |
R | Outdoor unit operation mode status. |
BI 1 | On/Off Status | “0-OFF
1-ON” |
R | Outdoor unit ON/OFF status |
AI 1 | Ambient Temperature | Actual value | R | Outdoor unit ambient temperature |
AI 2 | Compressor 1 Freq. | Actual value | R | Outdoor unit main compressor frequency(Hz) |
AI 3 | Compressor 2 Freq. | Actual value | R | Outdoor unit sub-compressor frequency(Hz) |
AI 4 | Compressor 1 Discharge Temp. | Actual value | R | Outdoor unit main compressor discharge temperature |
AI 5 | Compressor 2 Discharge Temp. | Actual value | R | Outdoor unit sub-compressor discharge temperature |
AI 6 | High Pressure | Actual value | R | Outdoor unit discharge pressure (psi) |
AI 7 | Low Pressure | Actual value | R | Outdoor unit suction pressure (psi) |
AI 9 | Fan 1 Speed | Actual value | R | Outdoor unit Fan-1 speed step, not the actual RPM |
AI 10 | Fan 2 Speed | Actual value | R | Outdoor unit Fan-2 speed step, not the actual RPM |
BI 2 | Alarm Indication | “0-No malfunction code
1-Malfunciton code” |
R | If there is an error code for the outdoor unit. |
AI 11 | T3 | Actual temperature | R | Outdoor left condenser temperature |
AI 12 | T3B | Actual temperature | R | Outdoor right condenser temperature |
BI 4 | SV2 | “0-OFF
1-ON” |
R | Outdoor SV2(Solenoid valve) status |
BI 6 | SV4 | “0-OFF
1-ON” |
R | Outdoor SV4(Solenoid valve) status |
BI 11 | ST1 | “0-Not energized 1-Energized” | R | Outdoor ST1(Reverse valve) status |
BI 12 | ST2 | “0-Not energized 1-Energized” | R | Outdoor ST2(Reverse valve) status |
AI 13 | Version | Actual value | R | Outdoor unit main PCB software version |
AI 14 | Outdoor type | “0-Mini VRF 1-VRF” | R | Outdoor unit type |
AI 15 | Outdoor horses | Actual value | R | Outdoor unit capacity (Ton) |
AI 16 | Exv1 opening | Actual value | R | Outdoor EEV A opening (pulse) |
AI 17 | Exv2 opening | Actual value | R | Outdoor EEV B opening (pulse) |
BV 1 | Emergency Stop | “0-None
1-Energy stop command” |
W | Emergency stop command |
Technical Support
- 18004LENNOX
- 18004536669
- technicalsupport@lennoxind.com
- LennoxCommercial.com
- Download the VRF and Mini-Split app from the Apple App Store or the Google Play Store.
FAQ
- Q: Can I clean the device with any type of cleanser?
- A: No, clean the device using a clean, damp cloth. Do not spray cleanser on or around the device.
- Q: How many VRF systems can the BACnet gateway monitor and control?
- A: The BACnet gateway can monitor and control up to 320 VRB & VPB VRF systems with up to 960 VRF outdoor units and 2560 VRF indoor units.
- Q: What is the default admin password for the device?
- A: The default admin password is 123456.