LENNOX V0CTRL95P-3 Mini Split BACnet Gateway

LENNOX-V0CTRL95P-3-Mini-Split-BACnet-Gateway-PRODUCT

Specifications
  • Function: Input Supply Power
  • BACnet Connection: 24VAC
  • I/O: 25% ~ 90%
  • Operating Temperature Range: 10-1/2 in. X 10 in. X 2-3/8 in. (26 cm X 25 cm X 6 cm)

Product Usage Instructions

Network Setting

Connect the device to a network port using an Ethernet interface (Eth0). The factory-set device address is 192.168.1.8.

Security

  • Default Admin User Name: admin
  • Default Admin Password: 123456

System Connections

  • The BACnet gateway can monitor and control up to 320 VRB & VPB VRF systems with up to 960 VRF outdoor units and 2560 VRF indoor units.
  • Ensure proper connection based on the BACnet address, which identifies the BACnet gateway bus, unit type, and unit’s address.

Setup Instructions

  1. Directly connect a PC network port to the gateway Ethernet connection.
  2. Configure the PC network port with the proper settings.
  3. Open a web browser and enter the IP address 192.168.1.8.
  4. You will be prompted to enter the default admin name and password.
  5. Once connected, follow the on-screen instructions to set up the Gateway on your BACnet network.

Equipment List

Package 1 of 1 consists of:

  • 1 – BACnet gateway
  • 1 – DIN rail
  • 1 – Instruction and Application Guide

General Safety

  • The Lennox VRF, Mini-VRF, and Mini-Split BACnet Gateway allows connection of those systems to a building management system (BMS) using BACnet protocols.
  • Setup can be accomplished through the use of a web browser and a PC with a network port.
  • LENNOX-V0CTRL95P-3-Mini-Split-BACnet-Gateway-FIG-1WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life.
  • Installation and service must be performed by a licensed professional HVAC installer or equivalent, a service agency, or the gas supplier.
  • LENNOX-V0CTRL95P-3-Mini-Split-BACnet-Gateway-FIG-1WARNING: Do not operate the device with wet hands.
  • LENNOX-V0CTRL95P-3-Mini-Split-BACnet-Gateway-FIG-1CAUTION: Before attempting to perform any service or maintenance, turn the electrical power to the unit OFF at the disconnect switch.
  • LENNOX-V0CTRL95P-3-Mini-Split-BACnet-Gateway-FIG-1CAUTION: Do not install the device in areas where heavy oil, vapor, or gases containing sulfur may exist, or the controller may be damaged.
  • LENNOX-V0CTRL95P-3-Mini-Split-BACnet-Gateway-FIG-1CAUTION: Clean device using a clean, damp cloth. Do not spray cleanser on or around the device.
  • LENNOX-V0CTRL95P-3-Mini-Split-BACnet-Gateway-FIG-1IMPORTANT: These instructions are intended as a general guide and do not supersede local codes in any way.
  • Consult the authorities having jurisdiction before installation. Read all of the information in this manual before operating this equipment.

Network Setting

  • There is an Ethernet interface in the device (Eth0). The factory-set device address is 192.168.1.8.

Security

  • Default Admin User Name: admin
  • Default Admin Password: 123456

Specifications

Function Description
Input Supply Power 24VAC
BACnet Connection BACnet/IP
I/O 4-port 485 interface
Operating Temperature Range 32°F ~ 104°F (0°C ~ 40°C)
Operating Humidity Range (Rh) 25% ~ 90%
Dimensions 10-1/2 in. X 10 in. X 2-3/8 in. (26 cm X 25 cm X 6 cm)
DIN Mounted
  • The V0CTRL95P-3 Lennox BACnet gateway can monitor and control up to 320 VRB & VPB VRF sys-tems with up to 960 VRF outdoor units and 2560 VRF indoor units.
  • See Appendix A. All Lennox VRF P3 outdoor and indoor units can be connected to the V0CTRL95P-3 Lennox BACnet gateway. See the LVM and BACnet Gateway installation man-ual (507897) for instructions for detailed connection information.

System Connections

The BACnet address is a four-digit number that identifies the BACnet gateway bus (port), the type of unit (indoor unit or outdoor unit), and the unit’s address. Device ID = XXXX

X X X X
BACnet Bus (Port) Number Unit Type Unit Address
(0-3) 0 Indoor Unit (Indoor Unit 0-63)

(Outdoor Unit 0-31)

1 Outdoor Unit
  • Example – 0001 indicates BACnet device number 0, indoor unit type, and indoor unit number 01.
  • Direct connect with PC from PC network port to the gateway Ethernet connection – Configure PC network port with the proper settings and use a web browser to connect – enter the IP address 192.168.1.8 and you will be prompted to enter name/password.
  • Once connected, you will see the options for setting up the Gateway to reside on your bacnet network.
  • Once connected, you will see the options for setting up the Gateway to reside on your bacnet network.
  • User name = admin
  • User Password = 123456LENNOX-V0CTRL95P-3-Mini-Split-BACnet-Gateway-FIG-2
Object Type Abbreviation
Analog Input AI
Analog Output AO
Analog Value AV
Binary Input BI
Binary Output BO
Binary Value BV
Multi-state Input MI
Multi-state Output MO
Multi-state Value MV

BACnet Object Points List

Indoor Units Points List

Object ID Object Name Value R/W Description
BV 1 On/Off Setting “0-OFF

1-ON”

R/W Indoor unit ON/OFF setting
MV 1 Mode Setting “1-OFF

2-Fan

3-Cooling 4-Heating 5-Auto

6-Dry”

R/W Indoor unit mode setting
MV 2 Fan Speed Setting “1/2-Low 3/4-Medium 5/6/7-High 8-Auto

9-OFF”

R/W Indoor unit fan speed setting
AV 1 Temperature Setting 62~86F(17~30C) R/W Indoor unit setpoint for cooling, heating, and dry mode
AV 2 Dual Point (Cooling) Setting 62~86F(17~30C) R/W Indoor unit auto mode cooling setpoint setting
AV 3 Dual Point (Heating) Setting 62~86F(17~30C) R/W Indoor unit auto mode heating setpoint setting
AV 4 Cool Temperature Limit Setting 62~86F(17~30C) R/W Indoor unit low limit of cooling, auto cooling, and dry setpoint
AV 5 Heat Temperature Limit Setting 62~86F(17~30C) R/W Indoor unit up limit of heating and auto heating setpoint
MV 3 Mode Limit Setting “0-Unlock

1-Locked in cooling mode 2-Locked in heating mode”

R/W Indoor unit mode lock/ unlock setting
MV 5 Fan Lock/Unlock Setting “1/2-Locked in low speed

3/4-Locked in medium speed 5/6/7-Locked in high speed

8-Unlock”

R/W Indoor unit fan speed lock/unlock setting
BV 4 Remote Control Lock Setting “0-Unlock

1-Wireless control locked”

R/W Wireless controller lock/unlock setting
BV 5 Controller Lock Setting “0-Unlock

1-Wired control locked”

R/W Wired controller lock/ unlock setting
AI 1 Room Temperature Actual value R Indoor unit room temperature sensor value
BI 2 Alarm Indication “0-No malfunction code 1-Malfunction code” R If there is an error code for the indoor unit
AI 9 EXV Opening Actual value R Indoor unit EEV opening
AI 10 Software Version Actual value R Indoor unit software version
AI 11 Indoor type “1-(V33B)Four-way cassette 2-(VWMB)Wall mounted

3-(VMDB)Medium static pressure duct

5-(VVCB)Vertical air handler

6-(VHIB)High static pressure duct 7-(V22B)Compact four-way cassette

8-(VCFB)Ceiling/Floor

11-(VOSB)Dedicated outside air duct

14-(VOWA)One way cassette

21-AHU control kit”

R Indoor unit series name
AI 12 Indoor Capacity “8-7Kbtu/h 10-9Kbtu/h 12-12Kbtu/h 17-15Kbtu/h 20-18Kbtu/h 25-24Kbtu/h 32-30Kbtu/h 40-36Kbtu/h 50-48Kbtu/h 60-54Kbtu/h 65-60Kbtu/h 80-72Kbtu/h

100-96Kbtu/h”

R Indoor unit capacity

Outdoor Units Points List

Object ID Object Name Value R/W Description
MI 1 Mode Status “1-OFF

2-Reserved 3-Cooling

4-Heating

5-Cooling test 6-Mix Cooling 7-Mix Heating 8-Heating test”

R Outdoor unit operation mode status.
BI 1 On/Off Status “0-OFF

1-ON”

R Outdoor unit ON/OFF status
AI 1 Ambient Temperature Actual value R Outdoor unit ambient temperature
AI 2 Compressor 1 Freq. Actual value R Outdoor unit main compressor frequency(Hz)
AI 3 Compressor 2 Freq. Actual value R Outdoor unit sub-compressor frequency(Hz)
AI 4 Compressor 1 Discharge Temp. Actual value R Outdoor unit main compressor discharge temperature
AI 5 Compressor 2 Discharge Temp. Actual value R Outdoor unit sub-compressor discharge temperature
AI 6 High Pressure Actual value R Outdoor unit discharge pressure (psi)
AI 7 Low Pressure Actual value R Outdoor unit suction pressure (psi)
AI 9 Fan 1 Speed Actual value R Outdoor unit Fan-1 speed step, not the actual RPM
AI 10 Fan 2 Speed Actual value R Outdoor unit Fan-2 speed step, not the actual RPM
BI 2 Alarm Indication “0-No malfunction code

1-Malfunciton code”

R If there is an error code for the outdoor unit.
AI 11 T3 Actual temperature R Outdoor left condenser temperature
AI 12 T3B Actual temperature R Outdoor right condenser temperature
BI 4 SV2 “0-OFF

1-ON”

R Outdoor SV2(Solenoid valve) status
BI 6 SV4 “0-OFF

1-ON”

R Outdoor SV4(Solenoid valve) status
BI 11 ST1 “0-Not energized 1-Energized” R Outdoor ST1(Reverse valve) status
BI 12 ST2 “0-Not energized 1-Energized” R Outdoor ST2(Reverse valve) status
AI 13 Version Actual value R Outdoor unit main PCB software version
AI 14 Outdoor type “0-Mini VRF 1-VRF” R Outdoor unit type
AI 15 Outdoor horses Actual value R Outdoor unit capacity (Ton)
AI 16 Exv1 opening Actual value R Outdoor EEV A opening (pulse)
AI 17 Exv2 opening Actual value R Outdoor EEV B opening (pulse)
BV 1 Emergency Stop “0-None

1-Energy stop command”

W Emergency stop command

Technical Support

FAQ

  • Q: Can I clean the device with any type of cleanser?
    • A: No, clean the device using a clean, damp cloth. Do not spray cleanser on or around the device.
  • Q: How many VRF systems can the BACnet gateway monitor and control?
    • A: The BACnet gateway can monitor and control up to 320 VRB & VPB VRF systems with up to 960 VRF outdoor units and 2560 VRF indoor units.
  • Q: What is the default admin password for the device?
    • A: The default admin password is 123456.