Teletek SensoIRIS WSST IS Fire Alarm Sounder And Strobe With Built-In Isolator Module
Installation Instruction
ATTENTION: Read carefully this installation Instructions before installing the device! This manual is subject to change without notice! SensoIRIS WSST IS is аn addressable Wall Mount Sounder and Strobe with built-in isolator module designed for installing in addressable fire alarm systems supporting TTE communication protocol. The device is powered on from the panel and can be controlled via the communication protocol.
The sounder SensoIRIS WSST IS is compatible with fire bases B124 for ceiling or wall mounting and WSB IP65 for wall mounting (refer to manual 18020861 for details).
54-23 VAD (Visual Alarm Device)
Note: The coverage volume diagram and characteristics of the sounder are described in document “SensoIRIS WSST IS Coverage volume, RevB, 04/2018”.
Installation Instructions
Attention: Power off the loop circuit before installing the SensoIRIS WSST IS addressable sounder!
- Choose the proper place for installation of the device.
- Set the device address using SensoIRIS Programmer or directly from addressable fire panel. The address must be in the range from 1 to 250.
- Mount the fire base on the ceiling or on the wall of the protected premises using fixings according the mounting surface.
- Connect the base to the fire panel using the wiring diagram.
- Insert the device into the base and rotate clockwise until it drops into place
- the short mark on the base fits with that on the sounder body. Continue to rotate the sounder until its mark coincides with the long mark on the base – a click is heard.
- Program the device parameters. Choose in consecutiveness from the control panel: System – Programming – Devices – Loop. Find the installed sounder, as enter address, loop and zone number – the panel automatically will recognize the type of the device. Choose the button MORE to enter in the additional settings menu.
- Test the sounder for proper operation.
Warranty
All devices carry on a warranty valid from the date of manufacture. The date of manufacture can be checked by the code marking on the back of the device. The date is printed numbers – YY MM. The first two numbers represent the year and the last two – the month. For example: The date code “20 07”, means the device is manufactured in July, 2020.
To return goods for warranty service, please contact with your local distributer for details.
Technical Specifications
Isolator Module Technical Specifications
When used with base B124
A-weighted sound level diagram
54-23 VAD (Visual Alarm Device)
Installation
Base B124/ Sockel B124
Address programming
Note: You may also program the address directly from the fire panel.
Mounting Base B124Mounting the sounder
Wiring Diagram
Tone types and description

Note: Approved to EN54-3 only.
Essential characteristics
Teletek Electronics JSC
Address: 14A Srebarna Str, 1407 Sofia, Bulgaria
- EN 54-3:2001
- EN 54-3:2001/A1:2002
- EN 54-3:2001/A2:2006
- EN 54-17:2005
- EN 54-17:2005/AC:2007
- EN 54-23:2010
- Fire alarm devices – Visual alarm device (VAD) intended for use in and around buildings
- Sounder Type: A
- Coverage volume: Open class