User Guide
UG_ULK-EIP-4A4BP6
(IO-Link MASTER,4A4B,EIP,IP67)
Introduction
1.1 Agreement
The following terms/abbreviations are used synonymously in this document:
IOL: IO-Link.
LSB: least significant bit.
MSB: most significant bit.
This device: equivalent to “this product”, refers to the product model or series described in this manual.
1.2 Purpose
This manual contains all the information required to use the device correctly, including information on necessary functions, performance, usage, etc.
It is suitable both for programmers and test/debugging personnel who debug the system themselves and interface it with other units (automation systems, other programming devices), as well as for service and maintenance personnel who install extensions or perform fault/error analysis.
Please read this manual carefully before installing this equipment and putting it into operation.
This manual contains instructions and notes to help you step-by-step through installation and commissioning. This ensures trouble-free.
use of the product. By familiarizing yourself with this manual, you will gain.
The following benefits:
❖ ensuring safe operation of this device.
❖ take advantage of the full capabilities of this device.
❖ avoid errors and related failures.
❖ reduce maintenance and avoid cost waste.
1.3 Valid Scope
The descriptions in this document apply to the IO-Link device module products of the ULKEIP series.
1.4 Declaration of Conformity
This product has been developed and manufactured in compliance with applicable European standards and guidelines (CE, ROHS).
You can obtain these certificates of conformity from the manufacturer or your local sales representative.
Safety Instructions
2.1 Safety Symbols
Read these instructions carefully and inspect the equipment before attempting to install, operate, repair, or maintain it. The following special messages may appear throughout this document or on the equipment to indicate status information or to warn of potential hazards.
We divide the safety prompt information into four levels: “Danger”, “Warning”, ” Attention”, and “Notice”.
DANGER | indicates a severely hazardous situation which, if not avoided, will result in death or serious injury. |
WARNING | indicates a hazardous situation which, if not avoided, could result in death or serious injury. |
ATTENTION | indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. |
NOTICE | used to prompt information not related to personal injury |
DANGER
This is the DANGER symbol, which indicates an electrical hazard exists which, if instructions are not followed, will result in personal injury.
WARNING
This is a WARNING symbol, which indicates an electrical hazard exists which, if instructions are not followed, could result in personal injury.
Attentio
This is the “Attention” symbol. Used to warn you of a potential personal injury hazard. Observe all safety instructions following this symbol to avoid injury or death.
Notice
This is the “Notice” symbol, which is used to warn the user of possible risks. Failure to observe this regulation may result in faulty of device.
2.2 General Safety
This equipment should only be installed, operated, serviced and maintained by qualified personnel. Qualified person is a person who has skills and knowledge concerning the construction and operation of electrical equipment, and its installation, and has received safety training to recognize and avoid the hazards involved.
There shall be a statement in the instructions that if the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Notice
User modifications and/or repairs are dangerous and will void the warranty and release the manufacturer from any liability.
Attentio
Product maintenance can only be carried out by our personnel. Unauthorized opening and improper servicing of the product can result in extensive equipment damage or possibly personal injury to the user.
In the event of a serious malfunction, discontinue use of the equipment. Prevent accidental operation of the device. If repairs are required, please return the device to your local representative or sales office.
It is the operating company’s responsibility to comply with locally applicable safety regulations.
Store unused equipment in its original packaging. This provides the best protection against impact and moisture for the device. Please ensure that the ambient conditions comply with this relevant regulation.
2.3 Special Safety
WARNING
A process started in an uncontrolled manner may endanger or be exposed to other equipment, therefore, before commissioning, make sure that the use of the equipment does not involve risks that may endanger other equipment or be endangered by other equipment risks of.
Power Supply
This device can only be operated with a current source of limited power, that is, the power supply must have overvoltage and overcurrent protection functions. In order to prevent the power failure of this equipment, affecting the safety of other equipment;
or the failure of external equipment, affecting the safety of this equipment.
Product Overview
The IO-Link master establishes the connection between the IO-Link device and the automation system. As an integral part of the I/O system, the IO-Link master station is either installed in the control cabinet, or directly installed on site as a remote I/O, and
its encapsulation level is IP65/67.
❖ Designed for industrial environments, it is a system applied to automated lines.
❖ Compact structure, suitable for usage scenarios with limited installation conditions.
❖ IP67 high protection level, anti-interference design, suitable for demanding application environments.
As a special reminder, IP rating is not part of UL certification.
Technical Parameters
4.1 ULK-EIP-4A4BP6
4.1.1 ULK-EIP-4A4BP6 Specification
The technical specifications of ULK-EIP-4A4BP6 are as follows:
10-Link Master 1P67 U LK- E1P-4A4B P6 4xCLASS A 4xCLASS B |
Ethernet/ IP![]() |
Basic Panuneters | |
liaising Material | Alumna Alloy |
lousing Color | Metallic Silva |
Protection Level | 1P67.epoxy MI potting |
Ihninsiont (Wx11210) | 205reans60mnix34.4mm |
Writ** | 515g |
Operating lemperature | -25T.70T |
Morns Tamicrature | 40t.85•C |
Operating Bunichty | 5%.95% |
Storage 1 tumidity | 5%.95% |
opciating Attnnplicric Presstac | 80KPa..106KPa |
Storage Atmospheric Procure | 801Ch.106KP* |
Mum& | 0..2000m |
Pollution Ikgree | 3 |
Tightening forqu$110) | M12:0.5Nm |
Application Environment | conforms b EN-61131 |
Vitiation Test | conform to IEC60068-2 |
Impact rest | conforms so IFC60068-27 |
Free Drop test | suntans to IEC60068.32 |
EMC | corium. to IEC610004-2.-3.4 |
Certification | Cr…R.11S |
Mounting llole Sin | s4 5mn. 14)5 .5min. 1 |
Data Transfer | |
Connection Type | 24112 Dadc: 4-pin Female |
Physical layer | Ethernet |
Transfer Kate | 10’100 MINK. Full Duplex |
Characteristic | anima to protocol features |
Mann Ftmetion | diagnosis alarm process alarm |
Min Cycle Tune | Ins |
10w-sing lorque(data port) | M12.0.5N5n |
Power Supply | |
Connection Ewe | M12. 5 pins. l.-code. Maki:task |
System voltage Us | 18..30 VIX(type .24VDC) |
Auxiliary voltage lla | 18…30 VDC(typc.24VDC) |
Total (Anent slit | 12A |
Static Working Curicsit1C | <150mA |
Overvoltagg Protection | VCs |
Power Reverie Polarity Protection | Ves |
riebnins Torquopowa supply pan) | M12:0.5Nm |
10-Link Master IP67 ULK-EIP-4A4BP6 4xCLASS A 4xClASS B |
EtherOet/IP![]() |
IO-UNK Parameters | |
Port Number | 8×10-UNK |
IO UNK Connection Type | 0412.Sn-code.femalt |
IO-UNIC Version | 1.1 |
Communication Rate | COM1(4.13flps),COM2(384X8ps),COM1(230.4KBps) |
Poet Voltage | type24VDC (follow US) |
Port Current | 2A (follow US) |
Pon Class | 4 x CLASS& 4 v CLASS 13 |
Port Maximum Data Length | My’, |
Max. Data Transfer Distance | 1100 m |
10-UNK Max Distance | s20 m |
Digital Input/Output | 4N PNP (selfeadaptive) |
Port Parameters (Input) | |
Input Number | up to 4 |
Input Port Position | x1…x4 |
Input Polarity | PNP |
Input Signal 0′ | low level 0.3-SV DC |
Input Signal ‘1’ | high level 12-30V DC |
Port Parameters (Output) | |
Output Number | up to 4 |
Output Port Position | X1…X4 |
Output Polarity | PNP |
Output Current | single channel maximum 2A |
Port Protection | poet power short circuit protection (P1N1. P1N3)/ port overload protection |
Load Type | Resistive. Pilot Duty, Tungsten |
4.1.2 ULK-EIP-4A4BP6 LED Definition
ULK-EIP-4A4BP6 is shown in the below figure.
Module Indicator | ||
Status | Solution | |
PWR | green: normal power supply | |
red:power reversed/UA power not connected/too low/high voltage | check power wiring | |
IO | green: normal channel signal | |
red: port power supply short circuit (2, 3 pins) | check pin 2 and pin 3 | |
LINK | green:normal link but abnormal data | check the network configuration |
yellow flash:normal link and data | ||
off:no link | check cable/network configuration | |
MS | red:module failure | check damage/IO-Link device connected or not |
green flash:module not configured | check configuration in the program and PLC download status | |
NS |
red flash:data interruption | check network cable status |
green flash:data not connected | ||
MS/NS | green:normal status | |
IO-LINK | green:port running status | |
green fast flash:port connecting | ||
green slow flash:port preoperaion status | pre-operational / port configured but no device connected | |
green off:port closed | port not configured | |
red:power supply short circuit (1, 3 pins) | check whether the 1 and 3 pins are short circuited |
Note: When the Link indicator is always off, if there is no abnormality in the cable inspection and replacement of other modules, it indicates that the product is working abnormally.
Please contact the manufacturer for technical consultation.
4.1.3 ULK-EIP-4A4BP6 Dimension
The size of the ULK-EIP-4A4BP6 is 205mm×60mm×34.5mm, including one φ4.5mm and one φ5.5mm mounting hole, the depth of the mounting hole is 20mm, as shown in the figure below:
Product Installation
5.1 Installation Precautions
To prevent product malfunction, malfunction, or negative impact on performance and equipment, please observe the following items.
5.1.1 Installation Site
Notice
Please avoid installing near devices with high heat dissipation (heaters, transformers, large-capacity resistors, etc.)
Notice
Please avoid installing it near equipment with serious electromagnetic interference (large motors, transformers, transceivers, frequency converters, switching power supplies, etc.).
This product uses PN communication.
Radio waves (noise) generated by transceivers, motors, inverters, switching power supplies, etc. may affect the communication between the product and other modules.
When these devices are around, it may affect the communication between the product and the module or damage the internal components of the module.
When using this product near these devices, please confirm the effects before use.
Notice
When multiple modules are installed close to each other, The service life of the modules may be shortened due to the inability to dissipate heat.
Please keep more than 20mm between the modules.
5.1.2 Application
DANGER
Do not use AC power. Otherwise, there is a risk of rupture, seriously affecting the safety of personal and equipment.
Attentio
Please avoid wrong wiring. Otherwise, there is a risk of rupture and burnout. It may affect the safety of personal and equipment.
5.1.3 Usage
Attentio
Do not bend the cable within a radius of 40mm. Otherwise there is a risk of disconnection.
Attentio
If you feel that the product is abnormal, please stop using it immediately and contact the company after cutting off the power.
5.2 Hardware Interface
5.2.1 ULK-EIP-4A4BP6 Interface Definition
Power Port Definition
- ULK-EIP-4A4BP6 Port Definition
The power port uses a 5-pin connector, and the pins are defined as follows:
Port M12 L-code Female &Male Pin Definiti on |
Connection Type | M12, 5 pins, L-code, Male/Female | ![]() |
System Supply Voltage us | 18…30 VDC (type.24VDC) | ||
Auxiliary Supply Voltage ua | 18…30 VDC (type.24VDC) | ||
Total Current Is | 12A | ||
Total Current la | 12A | ||
Static Working Current lc | 150mA | ||
Power Reverse Polarity Protection | Yes | ||
Tightening Torque (power port) | M12:0.5Nm | ||
Note: Us is the system power and input power, and Ua is the output power.
The power supply must be a limiting power source or class 2 power supply.
Data Port Definition
The data port uses a 4-pin connector, and the pins are defined as follows:
Data Port Pin Definition | |||
M12 D-code Female |
Connection Type | 2 × M12 D-code; 4 pins, Female | ![]() 1. TX+ |
Physical Layer | Ethernet | ||
Transfer Speed | 10/100 Mbps, full duplex | ||
Characteristic | conforms to the protocol features | ||
Alarm Function | diagnostic alarm, process alarm | ||
Min. Cycle Time | 1ms | ||
Tightening Torque (data port) | M12:0.5Nm | ||
IO-Link Port Definition
The IO-Link port uses a 5-pin connector, and the pins are defined as follows:
WARNING
Use Copper Conductors Only.
The maximum input current per port load is 200mA .
The voltage range of the output signal and Ua has always been 18~30Vdc .
5.2.2 ULK-EIP-4A4BP6 Wiring Diagram
- PNP type input signal, that is, the jack is connected to 1 input sensor, which is divided into two-wire sensor and three-wire sensors
- PNP type output signal, that is, the jack is connected to the actuator
- The IO-Link port is connected to the ULK-EIP-4A4BP6 substation. (When the IO-Link device is an input type, the 2 pins allow no wiring.
5.2.3 ULK-EIP-4A4BP6 IO Process Image Area Allocation 8-way IO-Link Interface (4 Class-A, 4 Class-B)
Ether’s: et/P Pro to co 1P rocess 0 ut put Data | |||||||||
Byte | Functipn D escrip tipn | ||||||||
Descrt tiln | BE7 I | BUG 1 | BUS | 1 BU4 | BE3 | 13E2 | BIll | BUO | |
0 | Standard I) 0 utput 0= off 1= on |
em pty | X4P2 | X3P2 | X2P2 | X 1P2 | |||
1 | no | reserve | reserve | reserve | reserve | reserve | reserve | reserve | reserve |
2-33 | port 1 process output data | ||||||||
34-65 | port2 process output data | ||||||||
66`97 | port3 process output data | ||||||||
98%129 | p ort 4 pro cess output data | ||||||||
130-161 | pons process output data | ||||||||
162-193 | port6 process output data | ||||||||
194-225 | port7 process output data | ||||||||
226-257 | p ort 8 process output data |
EtherN et P Proto co 1Pro cess hputData | |||||||||
Byte | Function D escrttion | ||||||||
D e scrip tip n | BEr | I BIM | I BUS | I BII4 | BE3 | 8E2 | B111 | 3E0 | |
0 | Stand ard D hput 0= no signal 1= have signal |
empty | 14P2 | X3P2 | X2P2 | vh.1P2 | |||
1 | C lass B pow ersupply shortcituk 0=Ph 2,5 short c itu it 1= non al |
empty | port5 | port6 | port . | pon8 | |||
2 | Port 1 process com m unicatbn status (0x03 connected, Oxa4 not connected, Ox00 not configured) | ||||||||
3 | Po rt 2 process corn m unicatbn status (0x03 connected, Oxa4 not connected, Ox00 not configured) | ||||||||
4 | Port 3 process corn m unicatbn status (0x03 connected, Oxa4 not connected, Ox00 not configured) | ||||||||
S | Port 4 process corn m unicatbn status (0x03 connected, Oxa4 not connected, Ox00 not configured) | ||||||||
6 | Pons process com in unicatbn status (0x03 connected, Oxa4 not connected, Ox00 not configured) | ||||||||
7 | Po rt 6 process com in unicatbn status (0x03 connected, Oxa4 not connected, Ox00 not configured) | ||||||||
8 | Port 7 process corn m unicatbn status (0x03 connected, Oxa4 not connected, Ox00 not configured) | ||||||||
9 | Port 8 process com in unicatbn stands (0x03 connected, Oxa4 not connected, Ox00 not configured) | ||||||||
10-41 | port]. process hput data | ||||||||
42-.73 | p ort 2 process hput data | ||||||||
74– 105 | port 3 process hput data | ||||||||
106137 | p ort 4 process hput data | ||||||||
138-‘169 | ports process hput data | ||||||||
170– 201 | port6 process hput data |
Note: When the IO-Link master port is connected to a slave station with output function, it is necessary to set the Pin2 output point to ON to provide power for the IO-Link device. Otherwise, the output point of the IO-Link device will light up in red when outputting.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided “as is” without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no
responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R”G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.