RP-2002(E) Agent Release Control Panel

Conventional Releasing Panels
General
The RP-2002 is a six-zone FACP for single and dual hazard agent releasing applications. The RP-2002 provides reliable fire detection, signaling and protection for commercial, indus-trial and institutional buildings requiring agent-based releasing. The RP-2002 is compatible with System Sensor’s i3 detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 45°F (7.22°C). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Notifier Device Compatibility Document for a com-plete listing of compatible devices. Four outputs are programmable as NACs (Notification Appli-ance Circuits) or releasing circuits. Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and non-resettable power outputs are also included on the main circuit board. The RP-2002 supervises all wiring, AC voltage, battery charger and battery level. Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm infor-mation on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function. The RP-2002E offers the same features as the RP-2002 but allows connection to 220/240 VAC. Unless otherwise speci-fied, the information in this data sheet applies to both the 110/ 120 VAC and 220/240 VAC versions of the panels.

Features

  • Listed to UL Standard 864, 9th edition.
  • FM Approved.
  • Designed for agent releasing standards NFPA 12, 12A, 12B, and 2001.
  • Meets International Building Code (IBC) seismic require-ments.
  • Disable/Enable control per input zone and output zone.
  • Extensive transient protection.
  • Dual hazard operation.
  • Adjustable pre-discharge, discharge and waterflow delay timers.
  • Cross-zone (double-interlock) capability.
  • Six programmable Style B (Class B) IDCs (Initiating Device Circuit).
  • System Sensor i3 series detector compatible.
  • Four programmable Style Y (Class B) output circuits – (spe-cial application power).
  • Strobe synchronization:
    • System Sensor
    • Wheelock
    • Gentex
    • Faraday
    • Amseco
  • Three programmable Form-C relays.
  • 7.0 amps total 24 VDC output current.
  • Resettable and non-resettable output power.
  • Built-in Programmer.
  • ANN-BUS connector for communication with optional devices (up to 8 total of any of the following):
    • N-ANN-80 Remote LCD Annunciator
    • N-ANN-I/O LED Driver
    • N-ANN-S/PG Printer Modules
    • N-ANN-RLY Relay Module
    • N-ANN-LED Annunciator Module
  • 80-character LCD display (backlit).
  • Real-time clock/calendar with daylight savings time control.
  • History log with 256 event storage.
  • Piezo sounder for alarm, trouble and supervisory.
  • 24 volt operation.
  • Low AC voltage sense.
  • Outputs Programmable for:
    • Releasing Circuits or NACS
  • NACs programmable for:
    • Silence Inhibit
    • Auto-Silence
    • Strobe Synchronization
    • Selective Silence (horn-strobe mute)
    • Temporal or Steady Signal
    • Silenceable or Non-silenceable
    • Release Stage Sounder
  • Automatic battery charger with charger supervision.
  • Optional Dress Panel DP-51050 (red).
  • Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet.
  • Optional N-CAC-5X Class A Converter Module for Outputs and IDCs.
  • Optional 4XTM Municipal Box Transmitter Module.
  • Optional Digital Alarm Communicators (411, 411UD, 411UDAC).
  • Optional ANN-SEC card for a secondary ANN-BUS.

PROGRAMMING AND SOFTWARE:

  • Custom English labels (per point) may be manually entered or selected from an internal library file.
  • Programmable Abort operation.
  • Three programmable Form-C relay outputs.
  • Pre-programmed and custom application templates.
  • Continuous fire protection during online programming at the front panel.
  • Program Check automatically catches common errors not linked to any zone or input point.

USER INTERFACE:

  • Integral 80-character LCD display with backlighting.
  • Real-time clock/calendar with automatic daylight savings adjustments.
  • ANN-Bus for connection to remote annunciators.
  • Audible or silent walk test capabilities.
  • Piezo sounder for alarm, trouble, and supervisory.

Controls and Indicators

LED INDICATORS

  • FIRE ALARM (red)
  • SUPERVISORY (yellow)
  • TROUBLE (yellow)
  • AC POWER (green)
  • ALARM SILENCED (yellow)
  • DISCHARGED (red)
  • PRE-DISCHARGE (red indicator)
  • ABORT (yellow indicator)

CONTROL BUTTONS

  • ACKNOWLEDGE
  • ALARM SILENCE
  • SYSTEM RESET (lamp test)
  • DRILL

AC Power – TB1

  • RP-2002: 120 VAC, 60 Hz, 3.66 amps.
  • RP-2002E: 240 VAC, 50/60 Hz, 2.085 amps.
  • Wire size: minimum #14 AWG (2.0 mm2) with 600V insula-tion.
  • Supervised, nonpower-limited.

Battery (sealed lead acid only) – J12:

  • Maximum Charging Circuit – Normal Flat Charge: 27.6 VDC @ 1.4 amp. Supervised, nonpower-limited.
  • Maximum Charger Capacity: 26 Amp Hour battery (two 18 Amp Hour batteries can be housed in the FACP cabinet. Larger batteries require separate battery box such as the BB-26 or NFS-LBBR).
  • Minimum Battery Size: 7 Amp Hour.

Initiating Device Circuits – TB4 and TB6

  • Zones 1 – 5 on TB4.
  • Zone 6 on TB6.
  • Supervised and power-limited circuitry.Style B (Class B) wiring with Style D (Class A) option.
  • Normal Operating Voltage: Nominal 20 VDC.
  • Alarm Current: 15 mA minimum.
  • Short Circuit Current: 40 mA max.
  • Maximum Loop Resistance: 100 Ohms.
  • End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
  • Standby Current: 4 mA.

Refer to the Notifier Device Compatibility Document for listed compatible devices.
Notification Appliance and Releasing Circuit(s) – TB5 and TB7

  • Four Output Circuits.
  • Style Y (Class B) or Style Z (Class A) with optional con-verter module.
  • Special Application power.
  • Supervised and power-limited circuitry.
  • Normal Operating Voltage: Nominal 24 VDC.
  • Maximum Signaling Current: 7.0 amps (3.0 amps special application, 300 mA regulated maximum per NAC).
  • End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
  • Max. Wiring Voltage Drop: 2 VDC. Refer to the Notifier Device Compatibility Document for com-patible listed devices.

Form-C Relays – Programmable – TB8

  • Relay 1 (factory default programmed as Alarm Relay)
  • Relay 2 (factory default programmed as fail-safe Trouble Relay)
  • Relay 3 (factory default programmed as Supervisory Relay)
  • Relay Contact Ratings:
    • 2 amps @ 30 VDC (resistive)
    • 0.5 amps @ 30 VAC (resistive)

Auxiliary Trouble Input – J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor external devices for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector cir-cuits.

Special Application Resettable Power – TB9

  • Operating Voltage: Nominal 24 VDC.
  • Maximum Available Current: 500 mA – appropriate for powering 4-wire smoke detectors (see note).
  • Power-limited Circuitry.

Refer to the Notifier Device Compatibility Document for com-patible listed devices.
NOTE: Total current for resettable power, nonresettable power and Output Circuits must not exceed 7.0 amps.
Special Application Resettable or Nonresettable Power -TB9

  • Operating Voltage: Nominal 24 VDC.
  • Maximum Available Current: 500 mA (see note 1).
  • Power-limited Circuitry.
  • Jumper selectable by JP31 for resettable or nonresettable power.

Refer to the Notifier Device Compatibility Document for com-patible listed devices.

Product Line Information

  • RP-2002: Six-zone, 24 volt Agent Release Control Panel (includes backbox, power supply, technical manual, and a frame & post operating instruction sheet) for single and dual hazard agent releasing applications.
  • RP-2002E: Same as above but allows connection to 220/240 VAC.
  • N-CAC-5X: Class A Converter Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A).
    NOTE: Two Class A Converter modules are required to convert all four Output Circuits and six Initiating Device Circuits.
  • 4XTM: Transmitter Module provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trou-ble LED.
  • N-ANN-80(-W): LCD Annunciator is a remote LCD annuncia-tor that mimics the information displayed on the FACP LCD display. Recommended wire type is un-shielded. (Basic model is black; order -W version for white; see DN-7114.)
  • N-ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. Ships with red or black enclosure (see DN-60242).
  • N-ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. (See DN-60242).
  • N-ANN-RLY: Relay Module, which can be mounted inside or outside the cabinet, provides 10 programmable Form-C relays.(See DN-7107).
  • N-ANN-S/PG: Serial/Parallel Printer Gateway module pro-vides a connection for a serial or parallel printer. (See DN-7103).
  • N-ANN-I/O: LED Driver Module provides connections to a user supplied graphic annunciator. (See DN-7105).
  • ANN-SEC: Optional card for a secondary ANN-BUS. See #53944.
  • NBG-12LR: Agent Release Pull Stations designed for use with Notifier Fire Alarm Control Panels with releasing capabili-ties.
  • DP-51050: Dress panel (red) is available as an option. The dress panel restricts access to the system wiring while allow-ing access to the membrane switch panel.
  • TR-CE: Trim-ring (red) is available as an option. The trim-ring allows semi-flushing mounting of the cabinet.
  • BB-26: Battery box, holds up to two 26 Amp Hour batteries and CHG-75.
  • NFS-LBBR: Battery box, houses two 55 Amp Hour batteries, red.
  • SEISKIT-COMMENC: Seismic mounting kit; required for seis-mic-certified installations.
  • BAT Series Batteries: Refer to DN-6933.
  • PRN-6: UL-listed compatible event printer. Dot-matrix, tractor-fed paper, 120 VAC.
  • PRN-7: UL-listed compatible event printer. Dot-matrix, tractor-fed paper, 120 VAC.
  • PRT-PK-CABLE: Programming cable. Used to update the FACP’s flash firmware. (Also requires an RS485 to RS232 converter).

SYSTEM SPECIFICATIONS

System Capacity

  • Annunciators …………………………………………….. ……………..8

Electrical Specifications

  • RP-2002 (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66 amps
  • RP-2002E (FLPS-7 Power Supply): 240 VAC, 50/60 Hz, 2.085 amps
  • Wire size: minimum 14 AWG (2.0 mm²) with 600 V insula-tion, supervised, nonpower-limited

Cabinet Specifications
Door: 19.26″ (48.92 cm.) high x 16.82″ (42.73 cm.) wide x 0.72″ (1.82 cm.) deep. Backbox: 19.00″ (48.26 cm.) high x 16.65″ (42.29 cm.) wide x 5.25″ (13.34 cm.) deep. Trim Ring (TR- CE): 22.00″ (55.88 cm.) high x 19.65″ (49.91 cm.) wide.

Shipping Specifications
Weight: 24.05 lbs. (10.9 kg)
Dimensions:

  • Height 20.00″ (50.80cm)
  • Width 22.50″ (57.15cm)
  • Depth 8.50″ (21.59cm)

Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme tempera- ture ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.

NFPA Standards
The RP-2002(E) complies with the following NFPA 72 Fire Alarm Systems requirements:

  • NFPA 12 CO2 Extinguishing Systems
  • NFPA 12A Halon 1301 Extinguishing Systems
  • NFPA 12B Halon 1211 Extinguishing Systems
  • NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)
  • NFPA 2001 Clean Agent Fire Extinguishing Systems

Agency Listings and Approvals

The listings and approvals below apply to the basic RP-2002(E) control panels. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL: S635
  • FM approved
  • CSFM: 7165-0028:0245
  • MEA: 333-07-E
  • Seismic Listing: Reference certificiate of compliance VMA – 45894-01 by the VMC Group

NOTE: For ULC-listed model, see DN-60444.
NOTIFIER® and System Sensor® are registered trademarks of Honeywell International Inc.
©2017 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.NOTIFIER-RP-2002-E-Agent-Release-Control-Panel-fig-1This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: 203-484-7161, FAX: 203-484-7118.
www.notifier.comNOTIFIER-RP-2002-E-Agent-Release-Control-Panel-fig-2firealarmresources.com

Documents / Resources

NOTIFIER RP-2002-E Agent Release Control Panel [pdf] Owner's Manual
RP-2002-E, RP-2002-E Agent Release Control Panel, Agent Release Control Panel, Release Control Panel, Control Panel

References

Leave a comment

Your email address will not be published. Required fields are marked *