ModMAG-LOGO

ModMAG M2000 BACnet MS/TP Communication Protocol Electromagnetic Flow Meters

ModMAG-M2000-BACnet-MS-TP-Communication-Protocol-Electromagnetic-Flow-Meters-PRODUCT

ABOUT THIS MANUAL

Definitions

BACnet Building Automation and Control Networks
DB Daughterboard
MS/TP Master-Slave/Token-Passing
PTP Point-to-Point
SPS Alternate abbreviation for PLC (Programmable Logic Controller)
User Units Defined by configuration of the meter’s volume unit or flow unit

Scope
This document discusses the supported features of serial BACnet MS/TP, how these features are related to the M2000, and the special considerations and type of data that is accessible over BACnet MS/TP. This document assumes general understanding of the BACnet MS/TP protocol by the reader. For further information regarding the BACnet Protocol, refer to www.bacnet.org. The M2000 BACnet MS/TP daughterboard supports BACnet MS/TP protocol, Revision 19. The BACnet MS/TP daughterboard acts as a BACnet MS/TP master node (Data Link Layer) with the device profile of BACnet-Smart Actuator (B-SA). It interfaces directly to MS/TP based systems.

INTRODUCTION

BACnet is a Data Communication Protocol for Building Automation and Control Networks. Developed under the auspices of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), BACnet is an American national standard, a European standard, a national standard in more than 30 countries, and an ISO global standard. The protocol is supported and maintained by ASHRAE Standing Standard Project Committee 135.

ModMAG-M2000-BACnet-MS-TP-Communication-Protocol-Electromagnetic-Flow-Meters-FIG-1

INSTALLATION

Pre-Installed Daughterboard
Most daughterboard installations will be completed in the factory and shipped pre-installed into the main board. Follow these steps to set up your M2000 BACnet MS/TP device.

  1. Power on the M2000.
  2. Allow time for the daughterboard to properly power up and be recognized by the M2000 before navigating the menus.This time is typically 3 seconds or less. If the BACnet MS/TP daughterboard is not recognized, cycle the M2000 power.
  3. Navigate in the menu to Main Menu > Communications > Daughterbrd Config.
  4. Configure the settings in the table below to what is required for the BACnet MS/TP network.
    Parameter Default Value Comments
    BACnet MS/TP Baud 9600 Baud Rate of the BACnet MS/TP network . Common settings are 9600, 19200, 38400

    and 76800 .

    BACnet MS/TP MAC ID 1 Sets BACNET MS/TP Device ID of module/meter . Max value = 127
    BACnet Max Master 127 Sets the max master variable for the device . Max value = 127
    BACnet Instance 10001 Sets the BACnet Instance number . The instance number is an unsigned decimal number that can range from 0 to 4,194,302 . Every device on a BACnet network gets

    an instance number, and two devices must not have the same number .

  5. After configuration of all parameters, exit the menu system back to the M2000 Home screen.
  6. Cycle power to the M2000 meter for any daughterboard configuration changes to take place.
Wiring the RS-485 Connections

NOTE:
Power off the M2000 before making the RS-485 wiring connections. Use the following information to wire signals to the 6-pin customer connector. See Figure 2.

Terminal Number Pin Description Comments
71 RS-485 B+ RS-485 Non-Inverting I/O 15kV HBM ESD Protected RS-485 level
72 RS-485 A- RS-485 Inverting I/O15kV HBM ESD Protected RS-485 level
73 Analog GND 0/4…20 mA (Terminal 15-)
74 Analog Output 0/4…20 mA (Terminal 16+)
75 24V DC Ext 24V DC Output
76 GND Isolated Ground (GND)
   

ModMAG-M2000-BACnet-MS-TP-Communication-Protocol-Electromagnetic-Flow-Meters-FIG-2

In-Field Upgrade

Prerequisites

  • Installing a BACnet MS/TP daughterboard into an M2000 requires firmware revision v1.22 or later.
  • The main board (revision 2 or later) must have a 12-pin connector for this interface.

Installing the Daughterboard
The BACnet MS/TP daughterboard connects to the 12-pin connector labeled COMMUNICATION on the main board.

ModMAG-M2000-BACnet-MS-TP-Communication-Protocol-Electromagnetic-Flow-Meters-FIG-3

Follow these steps to install the daughterboard hardware.

  1. Prior to installing the daughterboard, verify or configure the M2000 Communication Port B Settings. The Port B Settings are located at Main Menu > Communications > Port B Settings.
    Parameter Value
    Port Address 1
    Ext . Port Address 126
    Baud Rate 9600
    Data Bits 8 bits
    Parity Even
    Stop Bits 1 bit
  2. Exit the communications menu back to the M2000 Home screen.
  3. Power off the M2000.
    CAUTION
    DISCONNECT THE INPUT POWER BEFORE ACCESSING THE EQUIPMENT. This step is important for the M2000 to properly recognize the BACnet MS/TP daughterboard.
  4. Prior to inserting the daughterboard, install the foam insulation pad as shown in Figure 4 on page 6. Be sure to align the groove with the two screws attaching the detector or wall mount bracket to the enclosure. The primary purpose of this pad is to ensure the daughterboard is insulated from the enclosure wall. It is important to install this pad flush with the top of the enclosure wall. ModMAG-M2000-BACnet-MS-TP-Communication-Protocol-Electromagnetic-Flow-Meters-FIG-4
  5. Insert the 12-pin daughterboard into the 12 pin-connector.
  6. Power on the M2000.
  7. Allow time for the daughterboard to properly power up and be recognized by the M2000 before navigating the menus. This time is typically 3 seconds. If the BACnet MS/TP daughterboard is not recognized, cycle the M2000 power. 8. Verify recognition of the BACnet MS/TP daughterboard. Navigate to Main Menu > Info/Help. The Daughterboard Info field
    indicates the Daughterboard Type is BACnet MS/TP (Bn_mstp).
  8. From this point, follow the typical installation procedure.

SYSTEM CONFIGURATION

BACnet Protocol Implementation Conformance Statement

  • Date: March 4, 2022
  • Vendor Name: Badger Meter (Vendor 306)
  • Product Name: M2000 Mag Meter
  • Product Model Number: M2000
  • Application Software Version: M-Series v1.22
  • Firmware Revision: v1.02
  • BACnet Protocol Revision: 1.19

Product Description
The ModMAG M2000 Electromagnetic flow meter has a wide selection of liner and electrode materials to help ensure maximum compatibility and minimum maintenance over a long operating period.

BACnet Standardized Device Profiles Supported (Annex L)
BACnet Smart Actuator (B-SA)

BACnet Interoperability Building Blocks Supported (Annex K)

  • Data Sharing-ReadProperty-B (DS-RP-B)
  • Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
  • Data Sharing-WriteProperty-B (DS-WP-B)
  • Device Management-Dynamic Device Binding-B (DM-DDB-B)
  • Device Management-Dynamic Object Binding-B (DM-DOB-B)
  • Device Management-ReinitializeDevice-B (DM-RD-B)

Standard Object Types Supported

Object-Type Dynamically

Createable

Dynamically

Deleteable

Optional Properties Supported Writable Properties
Device No No Description,

Max Master, Max Info Frames

Max Master,

Max Info Frames

Network Port No No Link Speed Link Speeds MAC Address Max Master

Max Info Frames

Link Speed MAC Address Max Master

Max Info Frames

Analog Value No No Present Value
Character String No No Present Value

Range Restrictions for the Device Object

Object-Type Property Range Restriction
Device Max Master

Max Info Frames

1 ~ 127

1 ~ 255

 

Network Port

Link Speed MAC Address Max Master

Max Info Frames

9600, 19200, 38400, 57600, 76800

1 ~ 127

1 ~ 127

1 ~ 255

Data Link Layer Option Supported
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800

Segmentation Capability Supported
None

Character Sets Supported
ISO 10646 (UTF-8)

DATA MANAGEMENT

The BACnet MS/TP interface is based on BACnet Protocol Revision 19 and supports the following objects:

  • One Device Object – contains parameters pertaining to the M2000 device
  • 170 Analog Value Objects – contains parameters pertaining to meter specific parameters
  • 17 Custom String Values – contains device specific string data pertaining to the connected meter
  • One Network Port Object – Contains all BACnet network options and status

Device Object
Every BACnet device must have a Device Object, the Properties of which fully describe the BACnet device to the network. The Object_List Property of the Device Object, for example, provides a list of every Object contained within the BACnet device. The Vendor_Name, Vendor_Identifier and Model_Name Properties provide the manufacturer name and model of the device.

BACnet Property Value
Apdu Timeout 3000
Application Software Version M-Series v1 .22
Database Revision 0
Description Magnetic Flow Meter
Device Address Binding
Firmware Revision 1 .02
Location
Max Apdu Length Accepted 480
Max Info Frames 1
Max Master 127
Model Name M2000
Number of Apdu Retries 3
Object Identifier OBJECT_DEVICE: 10001
Object Name M2000 Mag Meter
Object Type 8 : Object Device
Property List Object Array
Protocol Object Types Supported 001000001000000000000000000000000000000010000000000000001000
Protocol Revision 19
Protocol Services Supported 00000000000010110100100000000000011000000000
Protocol Version 1
Segmentation Supported 3 : None
System Status 0 : Operational
Vendor Identifier 306
Vendor Name Badger Meter

Analog Value Objects & Character String Objects
This list specifies all the analog values accessible by the BACnet MS/TP network.

Measurements Category

Index Parameter Name Data Type Network Access BACnet Object ID
31 VelocityUnits INTEGER READ_WRITE AV13
32 FlowUnits INTEGER READ_WRITE AV14
33 VolumeUnits INTEGER READ_WRITE AV15
34 UnitMultiplier INTEGER READ_WRITE AV16
35 ZeroScaleFlow FLOAT READ_WRITE AV17
36 FullScalVelocity FLOAT READ_WRITE AV18
37 FullScaleFlow FLOAT READ_WRITE AV19
38 LowFlowCutoff FLOAT READ_WRITE AV20
39 FlowDirection INTEGER READ_WRITE AV21
40 DampingFactor INTEGER READ_WRITE AV22

Product Identification Category

Index Parameter Name Data Type Network Access BACnet Object ID
1 ProductCode INTEGER READ_ONLY AV161
2 ProductName STRING READ_ONLY CSV0
3 FirmwareName STRING READ_ONLY CSV1
4 ApplicationVer STRING READ_WRITE CSV2
5 CompileDate STRING READ_ONLY CSV3
6 CompileTime STRING READ_ONLY CSV4
7 PCBSerialNum STRING READ_WRITE CSV5
8 OTPBootChecksum STRING READ_ONLY CSV6
9 FlashOSChecksum STRING READ_ONLY CSV7
10 BootVer STRING READ_ONLY CSV8
11 OsVer STRING READ_ONLY CSV9
12 ComBoardProdType INTEGER READ_ONLY AV146
13 ComBoardMajorVer INTEGER READ_ONLY AV147
14 ComBoardMinorVer INTEGER READ_ONLY AV148
15 PwrOnSplashLn1 STRING READ_WRITE CSV10
16 PwrOnSplashLn2 STRING READ_WRITE CSV11
17 MeterTagName STRING READ_WRITE CSV12

Meter Calibration Category

Index Parameter Name Data Type Network Access BACnet Object ID
18 DetDiamEnum INTEGER READ_WRITE AV0
19 DetDiamActual INTEGER READ_WRITE AV1
20 DetectorFactor FLOAT READ_WRITE AV2
21 FACT_DetFactor FLOAT READ_ONLY AV3
22 DetectorOffset FLOAT READ_WRITE AV4
23 FACT_DetOffset FLOAT READ_ONLY AV5
24 AmplifierFactor FLOAT READ_WRITE AV6
25 FACT_AmpFactor FLOAT READ_ONLY AV7
26 DetectorCurrent FLOAT READ_WRITE AV8
27 FACT_DetCurrent FLOAT READ_ONLY AV9
28 PowerLineFreq INTEGER READ_WRITE AV10
29 ExcitationFreq INTEGER READ_WRITE AV11
30 ScaleFactor FLOAT READ_WRITE AV12

Meter Measurement Settings Category

Index Parameter Name Data Type Network Access BACnet Object ID
101 T1_Tplus_m3 FLOAT READ_ONLY AV82
102 T1_Tplus_User FLOAT READ_ONLY AV83
103 T1_TplusDispStr STRING READ_ONLY CSV14
104 T2_Tminus_m3 FLOAT READ_ONLY AV84
105 T2_Tminus_User FLOAT READ_ONLY AV85
106 T2_TminusDispStr STRING READ_ONLY CSV15
107 T3_TNet_m3 FLOAT READ_ONLY AV86
108 T3_TNet_User FLOAT READ_ONLY AV87
109 T3_TNetDispStr STRING READ_ONLY CSV16
110 T1_TplusRollCtr INTEGER READ_ONLY AV88
111 T2_TminusRollCtr INTEGER READ_ONLY AV89
112 FlowVelocity_MS FLOAT READ_ONLY AV90
113 FlowVelocity_Usr FLOAT READ_ONLY AV91
114 FlowRate_m3 FLOAT READ_ONLY AV92
115 FlowRate_User FLOAT READ_ONLY AV93
116 RelFlowRatePerc FLOAT READ_ONLY AV94
117 PresBatchTot_m3 FLOAT READ_ONLY AV95
118 PresBatchTot_Usr FLOAT READ_ONLY AV96
119 FlowDirection INTEGER READ_ONLY AV97

Digital Input Category

Index Parameter Name Data Type Network Access BACnet Object ID
41 DigInOperation INTEGER READ_WRITE AV23
42 DigInStatus INTEGER READ_ONLY AV24

Output 1 Category

Index Parameter Name Data Type Network Access BACnet Object ID
56 Out1_PPUnit_m3 FLOAT READ_WRITE AV37
57 Out1_PPUnit_user FLOAT READ_WRITE AV38
58 Out1_PulseWidth INTEGER READ_WRITE AV39
59 Out1_FS_Freq INTEGER READ_WRITE AV40
60 Out1_AlarmMin INTEGER READ_WRITE AV41
61 Out1_AlarmMax INTEGER READ_WRITE AV42
62 Out1_Mode INTEGER READ_WRITE AV43
63 Out1_Operation INTEGER READ_WRITE AV44

Output 2 Category

Index Parameter Name Data Type Network Access BACnet Object ID
64 Out2_PPUnit_m3 FLOAT READ_WRITE AV45
65 Out2_PPUnit_user FLOAT READ_WRITE AV46
66 Out2_PulseWidth INTEGER READ_WRITE AV47
67 Out2_FS_Freq INTEGER READ_WRITE AV48
68 Out2_AlarmMin INTEGER READ_WRITE AV49
69 Out2_AlarmMax INTEGER READ_WRITE AV50
70 Out2_Mode INTEGER READ_WRITE AV51
71 Out2_Operation INTEGER READ_WRITE AV52
Index Parameter Name Data Type Network Access BACnet Object ID
72 Out3_FS_Freq INTEGER READ_WRITE AV53
73 Out3_AlarmMin INTEGER READ_WRITE AV54
74 Out3_AlarmMax INTEGER READ_WRITE AV55
75 Out3_Mode INTEGER READ_WRITE AV56
76 Out3_HW_Select INTEGER READ_WRITE AV57
77 Out3_Operation INTEGER READ_WRITE AV58
Index Parameter Name Data Type Network Access BACnet Object ID
78 Out4_AlarmMin INTEGER READ_WRITE AV59
79 Out4_AlarmMax INTEGER READ_WRITE AV60
80 Out4_Mode INTEGER READ_WRITE AV61
81 Out4_HW_Select INTEGER READ_WRITE AV62
82 Out4_Operation INTEGER READ_WRITE AV63
77 Out3_Operation INTEGER READ_WRITE AV58
Index Parameter Name Data Type Network Access BACnet Object ID
43 AnalogOutRange INTEGER READ_WRITE AV25
44 AnalogOutOffset FLOAT READ_ONLY AV26
45 AnalogOutCalPtA FLOAT READ_WRITE AV27
46 AnalogOutCalPtB FLOAT READ_WRITE AV28
47 FACT_AOutCalPtA FLOAT READ_ONLY AV29
48 FACT_AOutCalPtB FLOAT READ_ONLY AV30
49 AnalogOutSlope FLOAT READ_ONLY AV31
50 AnalogOffset4MA FLOAT READ_WRITE AV32
51 AnalogOffset20MA FLOAT READ_WRITE AV33
52 AnalogOutCurrent FLOAT READ_ONLY AV34
53 AOutCurrentStr STRING READ_ONLY CSV13
54 AlarmMode INTEGER READ_WRITE AV35
55 FixedCurrentMode FLOAT READ_ONLY AV36
Index Parameter Name Data Type Network Access BACnet Object ID
83 A_PacketsProc INTEGER READ_ONLY AV64
84 A_BcastPackets INTEGER READ_ONLY AV65
85 A_CRCErrs INTEGER READ_ONLY AV66
86 A_PacketsRcvd INTEGER READ_ONLY AV67
87 A_PacketsSent INTEGER READ_ONLY AV68
88 A_ParityErrs INTEGER READ_ONLY AV69
89 A_FramingErrs INTEGER READ_ONLY AV70
90 A_OverrunErrs INTEGER READ_ONLY AV71
91 A_BreakDets INTEGER READ_ONLY AV72
Index Parameter Name Data Type Network Access BACnet Object ID
92 B_PacketsProc INTEGER READ_ONLY AV73
93 B_BcastPackets INTEGER READ_ONLY AV74
94 B_CRCErrs INTEGER READ_ONLY AV75
95 B_PacketsRcvd INTEGER READ_ONLY AV76
96 B_PacketsSent INTEGER READ_ONLY AV77
97 B_ParityErrs INTEGER READ_ONLY AV78
98 B_FramingErrs INTEGER READ_ONLY AV79
99 B_OverrunErrs INTEGER READ_ONLY AV80
100 B_BreakDets INTEGER READ_ONLY AV81
Index Parameter Name Data Type Network Access BACnet Object ID
174 BacnetMSTPBaud LONG READ_WRITE AV155
175 BacnetMSTPMacId INTEGER READ_WRITE AV156
176 BacnetMaxMaster INTEGER READ_WRITE AV157
177 BacnetInstance LONG READ_WRITE AV158
182 BacnetMaxInfoFrm INTEGER READ_WRITE AV164
Index Parameter Name Data Type Network Access BACnet Object ID
137 PowerLossTot_s LONG READ_ONLY AV115
138 DispBklightMode INTEGER READ_WRITE AV116
139 PreBatchAmt FLOAT READ_WRITE AV117
140 MenuResetAllowed INTEGER READ_WRITE AV118
141 MenuLangSetting INTEGER READ_WRITE AV119
142 FileSysNumRecsRd INTEGER READ_WRITE AV120
143 ConfigStatus INTEGER READ_ONLY AV121
144 PortBExtAddr INTEGER READ_ONLY AV122
157 SoftwreMedianFlt INTEGER READ_WRITE AV135
158 IIRCoefActualVal FLOAT READ_ONLY AV136
159 IIRActualState INTEGER READ_WRITE AV137
160 IIRCoefMin FLOAT READ_WRITE AV138
161 IIRCoefMax FLOAT READ_WRITE AV139
162 IIRHysteresis FLOAT READ_WRITE AV140
163 IIRSensitivity FLOAT READ_WRITE AV141
164 ZFlowStabSize FLOAT READ_WRITE AV142
165 ZFlowStabExp INTEGER READ_WRITE AV143
166 ZFlowStabAcc FLOAT READ_ONLY AV144
167 ZFlowStabTimer INTEGER READ_ONLY AV145
Index Parameter Name Data Type Network Access BACnet Object ID
145 AnalogInMeasVal FLOAT READ_ONLY AV123
146 AnalogInMeasCtr INTEGER READ_WRITE AV124
147 EmptyPipeActRes FLOAT READ_ONLY AV125
Index Parameter Name Data Type Network Access BACnet Object ID
148 EmptyPipeCal_V FLOAT READ_WRITE AV126
149 EmptyPipeMeasVal FLOAT READ_ONLY AV127
150 FullPipeCal_V FLOAT READ_WRITE AV128
151 EmptyPipeMode INTEGER READ_WRITE AV129
Index Parameter Name Data Type Network Access BACnet Object ID
152 CmdActionReq INTEGER READ_WRITE AV130
153 FlowSimulation SIGNED INTEGER READ_WRITE AV131
Index Parameter Name Data Type Network Access BACnet Object ID
154 SecurityStatus INTEGER READ_ONLY AV132
155 RandomVal LONG READ_ONLY AV133
156 RemoteLogin LONG WRITE_ONLY AV134
Index Parameter Name Data Type Network Access BACnet Object ID
157 SoftwreMedianFlt INTEGER READ_WRITE AV135
158 IIRCoefActualVal FLOAT READ_ONLY AV136
159 IIRActualState INTEGER READ_WRITE AV137
160 IIRCoefMin FLOAT READ_WRITE AV138
161 IIRCoefMax FLOAT READ_WRITE AV139
162 IIRHysteresis FLOAT READ_WRITE AV140
163 IIRSensitivity FLOAT READ_WRITE AV141
164 ZFlowStabSize FLOAT READ_WRITE AV142
165 ZFlowStabExp INTEGER READ_WRITE AV143
166 ZFlowStabAcc FLOAT READ_ONLY AV144
167 ZFlowStabTimer INTEGER READ_ONLY AV145
Index Parameter Name Data Type Network Access BACnet Object ID
168 RESERVED RESERVED RESERVED AV149
169 RESERVED RESERVED RESERVED AV150
170 RESERVED RESERVED RESERVED AV151
171 RESERVED RESERVED RESERVED AV152
172 RESERVED RESERVED RESERVED AV153
173 RESERVED RESERVED RESERVED AV154
174 BacnetMSTPBaud INTEGER READ_WRITE AV155
175 BacnetMSTPMacId INTEGER READ_WRITE AV156
176 BacnetMaxMaster INTEGER READ_WRITE AV157
177 BacnetInstance INTEGER READ_WRITE AV158
178 RESERVED RESERVED RESERVED AV159
179 RESERVED RESERVED RESERVED AV160
180 RESERVED RESERVED RESERVED AV162
181 RESERVED RESERVED RESERVED AV163
182 RESERVED RESERVED RESERVED AV164
183 RESERVED RESERVED RESERVED AV165
184 RESERVED RESERVED RESERVED AV166
185 RESERVED RESERVED RESERVED AV167
186 RESERVED RESERVED RESERVED AV168
187 RESERVED RESERVED RESERVED AV169

TROUBLESHOOTING

Symptoms Possible Causes Recommended Actions
No communication Transmit and receive are

wired incorrectly .

Check the network wiring from the meter .
Baud rate does not match master . Check the baud rate of the master and ensure the baud rate of the meter matches the master . If it does not match, change

the Baud Rate setting in the Communication menu .

Check LED behavior on the daughterboard . There should be a “fast” blink (4 flashes per second) . If LED is solid green or is a slow blink (1 flash per second) the daughterboard is not communicating to the main M2000 board . Check that the daughterboard is properly installed and fully plugged into the terminal on the M2000 board .

If there is still a slow blink on the daughterboard LED, remove the daughterboard, cycle power to the meter, and navigate to the communications menu on the M2000 . Configure Port B to the following settings:

Port Address: 1 Data Bits: 8 bits Parity: Even Stop Bits: 1 bit

The remaining port B settings are not factored into the discovery of the daughterboard and can be left as default values . Exit the menu system back to the M2000 main screen . Power off the meter, plug back in the daughterboard, and

again power up the meter .

MAC address is not unique . Another device is on the network with the

same address .

Check the addresses of the other devices on the network . Check that the MAC address is not 1 .
Cable is not terminated properly . For BACnet MS/TP on EIA-485 network, devices can be daisy chained together . The two devices on the end of the chain need to have terminated resistors to reduce reflections .

Terminating resistors (typically 120 Ohm) must be applied externally across the A- and B+ terminals . In point-to-point, or point-to-multipoint (single driver on bus) networks, the main cable should be terminated in its characteristic impedance (typically 120 Ohms) at the end furthest from the driver . In multi-receiver applications, stubs connecting receivers to the main cable should be kept as short as possible . Multipoint (multi-driver) systems require that the main cable be terminated in its characteristic impedance at both ends . Stubs connecting a transceiver to the main cable should be kept as

short as possible .

Cable or chain longer than 100 ft . RS-485 is intended for network lengths up to 4000 ft, but the maximum system data rate decreases as the transmission length increases . Devices (like this one) operating at 20 Mbps

are limited to lengths less than 100 ft .

Symptoms Possible Causes Recommended Actions
Intermittent communication Cable is not properly shielded . Communication cables must have shielding to protect the quality of the communication signals from electromagnetic interference (EMI) . Check that the cable has a shield . Typically, one end of the shield drain is connected to a clean ground to dissipate EMI and prevent ground loops . However, depending on the ground quality, cable length and type of interference, other methods can be employed . Twisted pair is the cable of choice for RS-485 networks . Twisted pair cables tend to pick up noise and other electromagnetically induced voltages as common mode signals, which are effectively rejected by the

differential receivers used in this application .

Cable routed near power cables such a variable frequency drives . Cables carrying high currents cause a high degree of electromagnetic interference that can interfere with the quality of the communication signals . Route signal cables

away from power cables .

Cable is not terminated properly . For BACnet MS/TP on EIA-485 network, devices can be daisy chained together . The two devices on the end of the chain need to have terminated resistors to reduce reflections .

Terminating resistors (typically 120 Ohm) must be applied externally across the A- and B+ terminals . In point-to-point, or point-to-multipoint (single driver on bus) networks, the main cable should be terminated in its characteristic impedance (typically 120 Ohms) at the end furthest from the driver . In multi-receiver applications, stubs connecting receivers to the main cable should be kept as short as possible . Multipoint (multi-driver) systems require that the main cable be terminated in its characteristic impedance at both ends . Stubs connecting a transceiver to the main cable should be kept as

short as possible .

Cable or chain longer than 4000 ft . RS-485 is intended for network lengths up to 4000 ft, but the maximum system data rate decreases as the transmission length increases . Devices (like this one) operating at 20Mbps

are limited to lengths less than 100 ft .

Unable to write specific parameters Meter is set up with security that prevents changes to certain

write-able values .

Enter the correct PIN to unlock the device . Refer to the M2000 user manual for more information on the different levels

of security .

BTL CERTIFICATION

For more information regarding this listing, go to the BTL website. WSPCert attests the conformmance of the following BACnet implementation to the BACnet standard Iso 16484-5 protocol revision 1.19. The attested conformance refers to the BACnet Interoperability Buiding Blocks (BIBBs) listed on the BTL Listing bearing the above-mentioned BTL-number.The BACnet implementation has fulfilled the requirements acoording to the test standard IS0 16484-6, the BTL Test Plan 20.0 and the BTL Testing Policies, see Test Report number BACO1018 of TUV SUD Industrie Service GmbH.

Control. Manage. Optimize.
ModMAG is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists. © 2022 Badger Meter, Inc. All rights reserved. www.badgermeter.com

Documents / Resources

ModMAG M2000 BACnet MS/TP Communication Protocol Electromagnetic Flow Meters [pdf] User Manual
M2000 BACnet MS TP Communication Protocol Electromagnetic Flow Meters, M2000 BACnet MS TP, Communication Protocol Electromagnetic Flow Meters, M2000, BACnet MS TP Communication Protocol Electromagnetic Flow Meters, Flow Meters

References

Leave a comment

Your email address will not be published. Required fields are marked *