komfovent logoBACNET CONNECTION C5
INSTALLATION AND
SERVICE MANUAL

BACNET CONNECTION AND SETTINGS

BACnet is a standard communication protocol for Building Automation and Control (BAC) networks that can be used to monitor and control Komfovent air handling units with C5 controller. The supported Data Link Layer is BACnet / IP.
BACnet protocol works via Ethernet interface, connection is provided to RJ-45 socket (Pic.1) on the C5 controller (CAT5 cable is recommended):komfovent C5.1 Air Handling Unit with Controller - Picture 1Below is default network settings of the C5 controller. These can be changed according to the building network software requirements. To do so, it is needed to connect a laptop to the integrated webserver of C5 controller:komfovent C5.1 Air Handling Unit with Controller - Picture 2C5 controller IP can also be viewed and changed on the control panel – from Main menu go to Settings>Air handling unit->Connectivity:komfovent C5.1 Air Handling Unit with Controller - Picture 3BACnet Interoperability Building Blocks Supported:

Data Sharing DS-RP-B Data Sharing-Read Property-B
DS-RPM-B Data Sharing-Read Property Multiple-B
DS-WP-B Data Sharing-Write Property-B
Device Management DM-DDB-B Device Management-Dynamic Device Binding-B
DM-DOB-B Device Management-Dynamic Object Binding-B

Standard Object Types Supported:

Analog Input Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, Units, Description, Reliability,
Analog Output Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, Units, Priority_Array, Relinquish_Default,
Analog Value Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, Units,Description, Priority_Array, Relinquish_Default, Max_Pres_Value, Min_Pres_Value, Resolution,
Binary Input Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, Polarity,Description
Binary Output Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, Polarity,Priority_Array, Relinquish_Default, Active_Text, Inactive_Text,
Binary Value Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_Service, Priority_Array, Relinquish_Default,
Device Object_Identifier, Object_Name, Object_Type, System_Status, Vendor_Name, Vendor_Identifier, Model_Name, Firmware_Revision, Application_Software_Version, Protocol_Version, Protocol_Revision, Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_APDU_Length_Accepted, Segmentation_Supported, APDU_Timeout, Number_Of_APDU_Retries, Device_Address_Binding, Database_Revision, Description,Location,

Analog input

Name Object Instance Range Unit Access Description
Monitoring data
Supply air temperature 0 -50.0..+120.0 °C R
Extract air temperature 1 -50.0..+120.0 °C R
Outdoor air temperature 2 -50.0..+120.0 °C R
Exhaust air temperature 3 -50.0..+120.0 °C R
Water temperature 4 -50.0..+120.0 °C R
Air quality 5 0..100 % R
Supply air humidity 6 0..100 %RH R
Supply air flow 7 0..1000000 variable1 R
Exhaust air flow 8 0..1000000 variable1 R
Outdoor air filter pressure 9 0..5500 Pa R
Extract air filter pressure 10 0..5500 Pa R
Zone 1 supply air temperature 11 -50.0..+120.0 °C R
Zone 1 water temperature 12 -30.0..+120.0 °C R
Zone 2 supply air temperature 13 -50.0..+120.0 °C R
Zone 2 water temperature 14 -30.0..+120.0 °C R
Internal supply air temperature 15 -50.0..+120.0 °C R
Zone 1 air quality 16 0..100 % R
Zone 1 heater temperature 17 0..+120.0 °C R
Zone 2 air quality 18 0..100 % R
Zone 2 heater temperature 19 0..+120.0 °C R
Supply temperature set-point 20 +5..+45 °C R
Supply air absolute humidity 21 0..40.0 g/m3 or g/kg R
Supply air pressure 22 0..5500 Pa R
Extract air pressure 23 0..5500 Pa R

Analog output

Name Object Instance Range Unit Access Description
Output signals
Water heater level 0 0..100 % R
Water cooler level 1 0..100 % R
Humidifier level 2 0..100 % R
Heat exchanger level 3 0..100 % R
Recirculation level 4 0..100 % R
Supply fan level 5 0..100 % R
Exhaust fan level 6 0..100 % R
Outdoor air damper level 7 0..100 % R
8 0..100 % R
Output signals
El. Heater level 9 0..100 % R
DX level 10 -100..+100 % R
Heat pump level 11 -100..+100 % R
Zone 1 level/heater level 12 -100..+100 % R
Zone 2 level/heater level 13 -100..+100 % R
Zone 1 cooler level 14 0..100 % R
Zone 2 cooler level 15 0..100 % R
Zone 1 temperature setpoint/ error 16 +5..+40 /
0..100
°C or % R
Zone 2 temperature setpoint/ error 17 +5..+40 /
0..100
°C or % R

Digital input

Name Object Instance Range Unit Access Description
External contacts
OVR 0 0..1 R 0-open, 1- closed
External stop 1 0..1 R 0-open, 1- closed
Zone 1 electric heater TK100 2 0..1 R 0-open, 1- closed
Zone 1 electric heater TK60 3 0..1 R 0-open, 1- closed
Zone 1 electric heater TK70 4 0..1 R 0-open, 1- closed
Zone 1 low water temperature 5 0..1 R 0-open, 1- closed
Zone 1 combined coil 6 0..1 R 0-open, 1- closed
Zone 1 external stop 7 0..1 R 0-open, 1- closed
Zone 2 electric heater TK100 8 0..1 R 0-open, 1- closed
Zone 2 electric heater TK60 9 0..1 R 0-open, 1- closed
Zone 2 electric heater TK70 10 0..1 R 0-open, 1- closed
Zone 2 low water temperature 11 0..1 R 0-open, 1- closed
Zone 2 combined coil 12 0..1 R 0-open, 1- closed
Zone 2 external stop 13 0..1 R 0-open, 1- closed
Outdoor air filter 14 0..1 R 0-open, 1- closed
Extract air filter 15 0..1 R 0-open, 1- closed
C5 Control 16 0..1 R 0-open, 1-closed

Digital output

Name Object Instance Range Unit Access Description
Water pumps
Water heating pump 0 0..1 R 0-stop, 1- run
Water cooling pump 1 0..1 R 0-stop, 1- run
Zone 1
Zone 1 stage 1 2 0..1 R 0-stop, 1- run
Zone 1 stage 2 3 0..1 R 0-stop, 1- run
Zone 1 stage 3 4 0..1 R 0-stop, 1- run
Zone 1 stage 4 5 0..1 R 0-stop, 1- run
Zone 1 heating water pump 6 0..1 R 0-stop, 1- run
Zone 1 cooling water pump 7 0..1 R 0-stop, 1- run
Zone 1 DX level unit reverse 8 0..1 R 0-stop, 1- run
Zone 1 DX modulated unit operation 9 0..1 R 0-stop, 1- run
Zone 1 DX modulated unit cooling 10 0..1 R 0-stop, 1- run
Zone 1 DX modulated unit heating 11 0..1 R 0-stop, 1- run
Zone 2
Zone 2 stage 1 12 0..1 R 0-stop, 1- run
Zone 2 stage 2 13 0..1 R 0-stop, 1- run
Zone 2 stage 3 14 0..1 R 0-stop, 1- run
Zone 2 stage 4 15 0..1 R 0-stop, 1- run
Zone 2 heating water pump 16 0..1 R 0-stop, 1- run
Zone 2 cooling water pump 17 0..1 R 0-stop, 1- run
Zone 2 DX level unit reverse 18 0..1 R 0-stop, 1- run
Zone 2 DX modulated unit operation 19 0..1 R 0-stop, 1- run
Zone 2 DX modulated unit cooling 20 0..1 R 0-stop, 1- run
Zone 2 DX modulated unit heating 21 0..1 R 0-stop, 1- run
Alarm output
Alarm DOUT 22 0..1 R 0-no alarm, 1-alarm
Active functions
AQC active 23 0..1 R 0-stop, 1- run
OCV active 24 0..1 R 0-stop, 1- run
MTC active 25 0..1 R 0-stop, 1- run
OVR active 26 0..1 R 0-stop, 1- run
SNC active 27 0..1 R 0-stop, 1- run
OOD active 28 0..1 R 0-stop, 1- run
REC active 29 0..1 R 0-stop, 1- run
HUM active 30 0..1 R 0-stop, 1- run

Digital value

Name Object Instance Range Unit Access Description
Alarms
Low supply air flow 0 0..1 R
Low extract air flow 1 0..1 R
VAV calibration fail 2 0..1 R
Change outdoor air filter 3 0..1 R
Change extract air filter 4 0..1 R
Electric heater off 5 0..1 R
High pressure on compressor 6 0..1 R
Low pressure on compressor 7 0..1 R
Service time 8 0..1 R
Service mode 9 0..1 R
Supply air temp. sensor failure 10 0..1 R
Extract air temp. sensor failure 11 0..1 R
Outdoor air temp. sensor failure 12 0..1 R
Exhaust air temp. sensor failure 13 0..1 R
Water temp. sensor failure 14 0..1 R
Return water temp low 15 0..1 R
Internal fire alarm 16 0..1 R
External fire alarm 17 0..1 R
External stop 18 0..1 R
Heat exchanger failure 19 0..1 R
Heat exchanger icing 20 0..1 R
Low supply air temperature 21 0..1 R
High supply air temperature 22 0..1 R
Electric heater overheat 23 0..1 R
Evaporator air temp. sensor failure 24 0..1 R
Evaporator coil temp. sensor failure 25 0..1 R
Compressor failure 26 0..1 R
Supply fan drive failure 27 0..1 R
Supply fan drive overload 28 0..1 R
Supply fan motor failure 29 0..1 R
Supply fan motor overload 30 0..1 R
Exhaust drive failure 31 0..1 R
Exhaust fan drive overload 32 0..1 R
Exhaust fan motor failure 33 0..1 R
Exhaust fan motor overload 34 0..1 R
Rotor drive failure 35 0..1 R
Rotor drive overload 36 0..1 R
Rotor motor failure 37 0..1 R
Rotor motor overload 38 0..1 R
Alarms
Communication error 39 0..1 R
Controller failure 40 0..1 R
Compressor off 41 0..1 R
Evaporator icing 42 0..1 R
Zone 1 TK100 alarm 43 0..1 R
Zone 1 TK70 alarm 44 0..1 R
Zone 1 TK60 alarm 45 0..1 R
Zone 1 low water temperature 46 0..1 R
Zone 1 external stop 47 0..1 R
Zone 2 TK100 alarm 48 0..1 R
Zone 2 TK70 alarm 49 0..1 R
Zone 2 TK60 alarm 50 0..1 R
Zone 2 low water temperature 51 0..1 R
Zone 2 external stop 52 0..1 R
Low heat exchanger efficiency 53 0..1 R

Analog value

Name Object Instance Range Unit Access Description
Unit On/Off 0 0..1 R/W 0-Off, 1-On
Ventilation modes
Current mode 1 0..5 R 0-Off/Standby, 1-Comfort1,
2-Comfort2, 3-Economy1, 4-Economy2,
5-Special
Mode selection 2 1..6 R/W 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2,
5-Special, 6-Program
Comfort1 Supply flow 3 0..200000 variable1 R/W
Comfort1 Extract flow 4 0..200000 variable1 R/W
Comfort1 Setpoint 5 +5..+40 °C R/W
Comfort2 Supply flow 6 0..200000 variable1 R/W
Comfort2 Extract flow 7 0..200000 variable1 R/W
Comfort2 Setpoint 8 +5..+40 °C R/W
Economy1 Supply flow 9 0..200000 variable1 R/W
Economy1 Extract flow 10 0..200000 variable1 R/W
Economy1 Setpoint 11 +5..+40 °C R/W
Economy2 Supply flow 12 0..200000 variable1 R/W
Economy2 Extract flow 13 0..200000 variable1 R/W
Economy2 Setpoint 14 +5..+40 °C R/W
Special Supply flow 15 0..200000 variable1 R/W
Special Extract flow 16 0..200000 variable1 R/W
Special Setpoint 17 +5..+40 °C R/W
Special mode Heating 18 0..1 R/W 0-Disable, 1-Enable
Special mode Cooling 19 0..1 R/W 0-Disable, 1-Enable
Special mode Recirculation 20 0..1 R/W 0-Disable, 1-Enable
Special mode Humidifying 21 0..1 R/W 0-Disable, 1-Enable
Special mode Dehumidifying 22 0..1 R/W 0-Disable, 1-Enable
Flow control mode 23 0..2 R/W 0-CAV, 1-VAV, 2-DCV
Temp. control mode 24 0..3 R/W 0-Supply, 1-Extract, 2-Room, 3-Balance

Analog value

Name Object Instance Range Unit Access Description
Functions
AQC Enable 25 0..1 R/W 0-Disable, 1-Enable
AQC Setpoint 1 26 variable1 variable1 R/W 200..1800 ppm, or

10..90 % or 5,0..45,0 °C

AQC Mode 1 27 1..5 R/W 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2, 5-Special
AQC Setpoint 2 28 variable1 variable1 R/W 200..1800 ppm, or
10..90 % or 5,0..45,0 °C
AQC Mode 2 29 1..5 R/W 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2, 5-Special
OCV Enable 30 0..1 R/W 0-Disable, 1-Enable
OCV Winter compensation stop 31 -40.0..+50.0 °C R/W
OCV Winter compensation start 32 -40.0..+50.0 °C R/W
OCV Summer compensation start 33 -40.0..+50.0 °C R/W
OCV Summer compensation stop 34 -40.0..+50.0 °C R/W
MTC Enable 35 0..1 R/W 0-Disable, 1-Enable
MTC Setpoint 36 -40.0..+50.0 °C R/W
OVR Enable 37 0..1 R/W 0-Disable, 1-Enable
OVR Type 38 0..2 R/W 0-Alltime, 1-If on, 2-If off
OVR Mode 39 0..6 R/W 0-Standby, 1-Comfort1, 2-Comfort2,
3-Economy1, 4-Economy2, 5-Special,
6-Program
SNC Enable 40 0..1 R/W 0-Disable, 1-Enable
SNC Start temperature 41 15.0..+50.0 °C R/W
SNC Stop temperature 42 15.0..+50.0 °C R/W
OOD Enable 43 0..1 R/W 0-Disable, 1-Enable
OOD Setpoint 44 variable1 variable1 R/W 200..1800 ppm, or

10..90 % or 5,0..45,0 °C

REC Enable 45 0..1 R/W 0-Disable, 1-Enable
REC Setpoint 1 46 variable1 variable1 R/W 200..1800 ppm, or

10..90 % or 5,0..45,0 °C

Name Object Instance Range Unit Access Description
Functions
REC Mode 1 47 1..5 R/W 1-Comfort1, 2-Comfort2, 3-Economy1,
4-Economy2, 5-Special
REC Setpoint 2 48 variable1 variable1 R/W 200..1800 ppm, or

10..90 % or 5,0..45,0 °C

Analog value

Name Object Instance Range Unit Access Description
Functions
REC Mode 2 49 1..5 R/W 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2, 5-Special
REC Min. Fresh Air 1 50 0..100 % R/W
REC Min. Fresh Air 2 51 0..100 % R/W
REC Winter end 52 -40.0..+50.0 °C R/W
REC Winter start 53 -40.0..+50.0 °C R/W
REC Summer start 54 -40.0..+50.0 °C R/W
REC Summer end 55 -40.0..+50.0 °C R/W
REC Default recirculation 56 0..100 % R/W
REC Activated recirculation 57 0..100 % R/W
HUM Enable 77 0..1 R/W 0-Disable, 1-Enable
HUM Setpoint 1 78 10..90 % R/W
HUM Mode 1 79 1..5 R/W 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2, 5-Special
HUM Setpoint 2 80 10..90 % R/W
HUM Mode 2 81 1..5 R/W 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2
CF heatexchanger calibration 84 0..2 R/W 0- No calibration,
1-  Calibrated,
2- Calibrating. Write 1 to start calibration
HUM mode 85 0..2 R/W 0- Supply,
1- Indoor+Supply, 2-Indoor
HUM Type 86 0..1 R/W 0-RH, 1-AH
HUM Units 87 0..1 R/W AH: 0-g/m3, 1-g/kg
OCV Minimum airflow 88 20..100 R/W %
Water heater: Enable/Disable 89 0..1 R/W 0-Disable, 1-Enable
Name Object Instance Range Unit Access Description
Functions
Water cooler: Enable/Disable 90 0..1 R/W 0-Disable, 1-Enable
Alarm reset
Actual alarms reset 58 1 W 1-Reset current alarm
Counters
Air heater operation 59 0..2^32 hours R/W
Supply fan operation 60 0..2^32 hours R/W
Exhaust fan operation 61 0..2^32 hours R/W
Heat exchanger thermal ef- ficiency 62 1..100 % R 255-none
Heat exchanger recovery 63 0..2^32 watt R
Thermal energy saving 64 0..100 % R
Supply SFP 65 0..655 R
Exhaust SFP 66 0..655 R
User settings
Day 67 1..31 days R/W
Month 68 1..12 months R/W
Year 69 2000..2250 years R/W
Hours 70 0..23 hours R/W
Minutes 71 0..59 minutes R/W
Flow units 72 0..3 R/W 0-m3/h, 1-l/s, 2-m3/s, 3-Pa
External room temperature sensor 73 -50.0..+120.0 °C R/W Values outside the range disables override
Zone 1 setpoint 74 -50.0..+40.0 °C R/W
Zone 2 setpoint 75 -50.0..+40.0 °C R/W
Digital input IN4 override 76 -1..2 R/W -1 – disabled,
0 – heating,
1 – cooling,
2 – error
Daylight saving time 82 0..1 R/W 0-Disable, 1-Enable
BACnet Broadcast Management Device 83 0..1 R/W 0-Disable, 1-Enable

SERVICE AND SUPPORT

GERMANY
Komfovent GmbH
Konrad-Zuse-Str. 2a,
42551 Velbert, Deutschland
Phone: +49 0 2051 6051180
info@komfovent.de
www.komfovent.de

UNITED KINGDOM
Komfovent Ltd
Unit C1 The Waterfront
Newburn Riverside
Newcastle upon Tyne NE15 8NZ, UK
Phone: +447983 299 165
steve.mulholland@komfovent.com
www.komfovent.com

komfovent logowww.komfovent.com

Documents / Resources

komfovent C5.1 Air Handling Unit with Controller [pdf] Instruction Manual
C5.1, BACnet-C5_24-04, C5.1 Air Handling Unit with Controller, C5.1, Air Handling Unit with Controller, Handling Unit with Controller, Unit with Controller, Controller