FAS IOL-104-S01-M08 IP67 Module

FAS-IOL-104-S01-M08-IP67-Module-PRODUCT

Security

Expected use
This manual describes as decentralized input and output modules for connecting to an industrial network.

Installation and start-up

Precautions!
Installation and start-up may only be performed by trained personnel. A qualified individual is one who is familiar with the installation and operation of the product and has the necessary qualifications to perform such operations. Any damage caused by unauthorized operation or illegal and improper use is not covered by the manufacturer’s warranty. The equipment operator is responsible for ensuring that appropriate safety and accident prevention regulations are observed.

Corrosion resistance

Precautions!
FNI modules generally have good chemical and oil resistance.When used in corrosive media (e.g. high concentrations of chemicals, oils, lubricants, coolants and other material media (i.e. very low water content), these media must be checked before the corresponding application material compatibility.If a module fails or is damaged due to this corrosive medium, a defect claim cannot be made.

Dangerous voltage
Precautions!
Disconnect all power before using the device!

General security

Debugging and inspection Trouble Owner/operator obligations Expected use
      Before debugging, read the user manual carefully. If the defect or equipment failure cannot be corrected, the operation of the equipment must be stopped to avoid damage that may be caused by unauthorized use.      This equipment is an EMC Class A compliant product. This device produces RF noise.              The warranty and limited liability statement provided by the manufacturer does not cover damage caused by:
  • Unauthorized tampering
  • Improper use operation
  • The instructions provided in the user manual explain the use, installation and handling of discrepancies
  This system cannot be used in an environment where the safety of personnel depends on the functionality of the equipment.       Only after the housing is fully installed can the intended use be assured. The owner/operator must take appropriate precautions to use this equipment.
This device can only use the power supply that matches this device, and can only connect cables approved for application.

Getting started guide

Module overview

  1. FAS-IOL-104-S01-M08-IP67-Module- (1)IO-Link interface
  2. Fixing holes
  3. Label
  4. Standard output port 1
  5. Standard output port 3
  6. Standard output port  5
  7. Standard output port 7
  8. Fixing holes
  9. Port LED: Standard input port 7, Pin 4
  10. Standard Output Port 6
  11. Standard output port 4
  12. Standard output port 2
  13. Standard output port 0
  14. Status LED: Communication/Module
Indicator light State Describe
Port LED Yellow LED indicator Input status is normal
State LED Green, pulse Communication is normal
Red indicator Communication abnormality

Mechanical connection
The modules are connected using 2 M4 bolts and 2 washers. Isolation pads are available as accessories.

Electrical connections

IO-Link interface(A-coded)

M12,A-Coded,Male

FAS-IOL-104-S01-M08-IP67-Module- (2)

Standard input interface

FAS-IOL-104-S01-M08-IP67-Module- (3)Note:
Unused I/O port sockets must be covered with dust caps to meet IP67 protection rating FAS-IOL-104-S01-M08-IP67-Module- (4)

Technical data

 Size FAS-IOL-104-S01-M08-IP67-Module- (4) FAS-IOL-104-S01-M08-IP67-Module- (6)Mechanical data

Shell material Plastic
Housing rating according to IEC 60529 IP67 (only in plug-in or plug type)
IO-Link interface A-Coded
Input port M8(8*Female)
Size(W*H*D) 30mm*131mm*25.8mm
Installation type 2-Through hole mounting
Weight About 107 g

Operating conditions

 

Operating temperature

 

-5°C

 

~

 

70°C

Storage temperature -25°C ~ 70°C

 Electrical data

Voltage 18~30V DC,conform to EN61131-2
Voltage fluctuation <1%
Maximum load current, sensor/channel 100mA
Total current <800mA

IO-Link data

As shown in Table 1-1. Surface 1-1

Data transmission baud rate COM2 (38.4kbit/s)
Minimum cycle time 3ms
Process data cycle time 3ms,corresponds to the minimum cycle

time

Process data length 2

 Process data/output data
No output data is defined.

Process data/input data
As shown in Figure 4.

Byte 0 1
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Describe PORT7 PIN4 PORT6 PIN4 PORT5 PIN4 PORT4 PIN4 PORT3 PIN4 PORT2 PIN4 PORT1 PIN4 PORT0 PIN4 PORT7 PIN2 PORT6 PIN2 PORT5 PIN2 PORT4 PIN2 PORT3 PIN2 PORT2 PIN2 PORT1 PIN2 PORT0 PIN2

Figure 4

 Parameter data/request data

As shown in Figure 5.

DPP SPDU Object name length Scope Defaults
Index Index Subindex
Identification data Supplier ID 2 0x0454
Device ID 3 0x0994E3
0x10 0 Supplier name 18 Read only FAS(Fujian)Co.,LTD
0x11 0 Supplier text 16 www.fas-elec.com
0x12 0 Product name 20 FNIIOL-104-000-M08
0x13 0 Product ID 6 00B311
0x14 0 Product text 12 IO-Link M8 PNP 16DI
0x16 0 Hardware version 3 20201011
0x17 0 Firmware version 3 2.02
Parameter data Ox40 0 Bit reversal 2 0000-FFFF 0x0000

Figure 5

Note:
The 0x40 setting bit is reversed: 0-bit is not reversed, 1-bit is reversed. For example, the external input is 0x0000. When 0x40 is 0x0000, the value is 0x0000 (not reversed). When 0x40 is 0xFFFF, the value is 0xFFFF ( reverse).

Error
As shown in Figure 6.

FAS-IOL-104-S01-M08-IP67-Module- (3)Event
As shown in Figure 7.FAS-IOL-104-S01-M08-IP67-Module- (3)Figure 7

High quality products • Sincere serviceFAS-IOL-104-S01-M08-IP67-Module- (7)

  • Telephone : 0591-22991876
  • Technical support : +86 13306936805
  • Official website: www.faselec.com
  • Business support : +86 19905006938
  • Address: Room 009, A1, Building 1, National University Science and Technology

Park Science and Technology Innovation Center, No. 6 Qiuyang East Road, Shangjie Town, Minhou County, Fujian Province.

FAQ

  • Q: What should I do if the module fails due to exposure to corrosive media?
    A: If a module fails or is damaged due to corrosive media, a defect claim cannot be made. It is important to ensure compatibility with the media before usage.
  • Q: Can the module be used in environments where personnel safety depends on its functionality?
    A: This system cannot be used in environments where personnel safety relies on the equipment’s functionality. Safety precautions must be taken accordingly.