Danfoss-LOGO

Danfoss PLUS+1 Compliant EMD Speed Sensor QUAD Function Block

Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-PRODIUCT

Specifications

  • Product: PLUS+1 Compliant EMD Speed Sensor Quadrature Function Block
  • Revision: Rev AA (May 2015)
  • Manufacturer: Danfoss

Product Information

The EMD_SPD_QUAD Function Block outputs an RPM signal and a DIR signal based on inputs from an EMD Speed Sensor. It receives inputs such as Phase A, Phase B, Voltage, and Config signals to calculate RPM output.

FAQ

Q: What is the purpose of the EMD_SPD_QUAD Function Block?

A: The EMD_SPD_QUAD Function Block outputs an RPM signal and a DIR signal based on inputs from an EMD Speed Sensor.

DIMENSIONS

Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-FIG-1

www.powersolutions.danfoss.com

Revision History

Revision Date Comment
Rev AA May 2015

©2015 Danfoss Power Solutions (US) Company. All rights reserved.
All trademarks in this material are properties of their respective owners.
PLUS+1, GUIDE, and Sauer-Danfoss are trademarks of Danfoss Power Solutions (US) Company. The Danfoss, PLUS+1 GUIDE, PLUS+1 Compliant, and Sauer-Danfoss logotypes are trademarks of Danfoss Power Solutions (US) Company.

Overview

Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-PRODIUCT

This function block outputs an RPM signal and a DIR signal based on inputs from an EMD Speed Sensor.
On an MC and SC controller, this function block receives its:

  • Phase A input through an MFIn.
  • Phase B input through an MFIn.

Inputs

EMD_SPD_QUAD Function Block Inputs

Input Type Range Description
Param —— —— Input for a user-defined Pulse/Rev value that defines the number of pulses equal to one revolution.

Optionally, an input for a DirLockHz value to replace this function block’s internal default fault direction-lock frequency value.

Phase A Bus —— Inputs speed and direction signals from the speed sensor.
Per U32 1,250 to

10,000,000

The measured period output by the Speed Sensor.

The function block uses the Per signal, Count signal, and Puls/Rev parameter value to calculate its

RPM output.

10,000 = 1,000 μs.

L1429531 · Rev AA · May 2015

EMD_SPD_QUAD Function Block Inputs

Input Type Range Description
Count U16 0 to 65,535 The measured count per program loop output by the Speed Sensor.

The function block uses the Per signal, Count signal, and Puls/Rev parameter value to calculate its

RPM output. 1,000 = 1,000.

QuadCount S16 -32768 to

32767

The measured direction and number of counts based on phase shifted pulse waves from Phase A

and Phase B.

1,000 = 1,000.

Volt/Voltage U16 0 to 5,250 The measured voltage of the input signal that the Speed Sensor outputs, which the block uses for fault detection.
Config Sub-bus —— Contains the signals that configure this input.
Phase B Bus —— Inputs speed signals from the speed sensor.
Per U32 1,250 to

10,000,000

The measured period output by the Speed Sensor.

The function block uses the Per signal, Count signal, and Puls/Rev parameter value to calculate its

RPM output. 10,000 = 1,000 μs.

Count U16 0 to 65,535 The measured count per program loop output by the Speed Sensor.

The function block uses the Per signal, Count signal, and Puls/Rev parameter value to calculate its

RPM output. 1,000 = 1,000.

Volt/Voltage U16 0 to 5,250 The measured voltage of the input signal that the Speed Sensor outputs, which the block uses for fault detection.
Config Sub-bus —— Contains the signals that configure this input.

Outputs

EMD_SPD_QUAD Function Block Outputs

Output Type Range Description
Status U16 —— Reports the function block’s status.

This function block uses a non-standard bitwise scheme to report its status and faults.

·          0x0000 = Block is OK.

·          0x0008 = Puls/Rev or DirLockHz parameter value is out of range.

Fault U16 —— Reports the function block’s faults.

This function block uses a non-standard bitwise scheme to report its status and faults.

·          0x0000 = Block is OK.

·          0x0001 = Per signal in the function block’s Phase A input is too low.

·          0x0002 = Volt/Voltage signal in the function block’s Phase A input is out of range.

·          0x0004 = Per signal in the function block’s Phase B input is too low.

·          0x0008 = Volt/Voltage signal in the function block’s Phase B input is out of range.

·          0x0010 =The difference in frequencies reported by the function block’s Phase A and

Phase B inputs is greater than 5%.

Diag —— —— Outputs a bus with Freq, FltTmrPhase A, FltTmrPhase B, and FltTmrFreqDiff signals that are available for troubleshooting.
Freq U32 0 to 1,000,

000,000

The measured frequency of the Speed Sensor. 100,000 = 10,000 Hz.
FltTmrPhase A U16 0 to 65,535 When a frequency fault:

·          Occurs, this output counts up the milliseconds until the function block makes a fault declaration.

·          Clears, the output counts down the milliseconds until the function clears the fault declaration.

1,000 = 1,000 ms.

FltTmrPhase B U16 0 to 65,535 When a frequency fault:

·          Occurs, this output counts up the milliseconds until the function block makes a fault declaration.

·          Clears, the output counts down the milliseconds until the function clears the fault declaration.

1,000 = 1,000 ms.

FltTmrFreqDiff U16 0 to 65,535 When a frequency difference fault:

·          Occurs, this output counts up the milliseconds until the function block makes a fault declaration.

·          Clears, the output counts down the milliseconds until the function clears the fault declaration.

1,000 = 1,000 ms.

dRPM U16 0–25,000 Speed sensor revolutions per minute x 10 (deciRPM). The function block clamps this output at 25,000.

1 = 0.1 rpm.

RPM U16 0–2,500 Speed sensor revolutions per minute.

The function block clamps this output at 2,500. 1 = 1 rpm.

EMD_SPD_QUAD Function Block Outputs

Output Type Range Description
Dir S8 -1, 0, +1 The Speed Sensor’s direction of rotation.

·          -1 = Counterclockwise (CCW).

·          0 = Neutral.

·       +1 = Clockwise (CW).

About Function Block Connections

Function Block Connections

Item Description
1. Input for common parameters that can be applied to multiple function blocks.
2. Input for a bus with:

·          The voltage, period, quadcount, and count signals output by the EMD Speed Sensor.

·          A sub-bus with signals that configure the controller input that receives these signals.

3. Input for a bus with:

·          The voltage, period, quadcount, and count signals output by the EMD Speed Sensor.

·          A sub-bus with signals that configure the controller input that receives these signals.

4. Reports the status of the function block.
5. Reports the fault of the function block.
6. Outputs a bus with Freq, FltTmrPhase A, FltTmrPhase B, and FltTmrFreqDiff signals that are available for troubleshooting.
7. Speed sensor revolutions per minute.
8. Speed sensor revolutions per minute x 10 (deciRPM).
9. The Speed Sensor’s direction of rotation.

·          -1 = Counterclockwise (CCW).

·          0 = Neutral.

·       +1 = Clockwise (CW).

Status and Fault Logic

Unlike most other PLUS+1 compliant function blocks, this function block uses non-standard status and fault codes.

Status Logic

Status Hex* Binary Cause Response Correction
A parameter is out of range. 0x0008 1000 Puls/Rev, FaultDetTm, or DirLockHz parameter is out of range. The function block clamps the out-of-range value at either its upper or lower limit. Get the out-of-range parameter back within its range.

* Bit 16 set to 1 identifies a standard Danfoss status or fault code.

Fault Logic

Fault Hex* Binary Cause Response Delay Latch Correction
Per signal in the function block’s Phase A input is too low. 0x0001 00000001 Per signal < 1,250 Hz. The function block outputs its maximum RPM and dRPM

values.

Y N Check for hardware issues, such as electrical noise, that can produce an invalid Per signal

value.

Volt signal in the function block’s Phase

A input is out of range.

0x0002 00000010 2000 V < Volt signal

< 3000 V.

The function block outputs 0 for RPM and dRPM values. Y N Check for hardware issues, such as an open circuit signal wire or missing sensor voltage supply.
Per signal in the function block’s Phase B input is too low. 0x0004 00000100 Per signal < 1,250 Hz. The function block outputs its maximum RPM and dRPM

values.

Y N Check for hardware issues, such as electrical noise, that can produce an invalid Per signal

value.

Volt signal in the function block’s Phase B input is out

of range.

0x0008 00001000 2000 V < Volt signal

< 3000 V.

The function block outputs 0 for RPM and dRPM values. Y N Check for hardware issues, such as an open circuit signal wire or missing sensor voltage supply.
Measured difference between Phase A and Phase B

frequency too big.

0x0010 00010000 |Freq A -Freq B| > 5% of current frequency. No built-in response, output reported as measured by Phase A input. Y N Check for hardware issues, such as electrical noise, that can produce an invalid Per signal value.

Bit 16 set to 1 identifies a standard Danfoss status or fault code.
A delayed fault is reported if the detected fault condition persists for a specified delay time. A delayed fault cannot be cleared until the fault condition remains undetected for the delay time.
The function block maintains a latched fault report until the latch releases.

Function Block Parameter Values

Enter the top-level page of the EMD_SPD_QUAD function block to view and change this function block’s parameters.

Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-FIG-3

Function Block Parameters

Input Type Range Description
Puls/Rev U16 20–120, 180 Number of pulses per revolution of the Speed Sensor. Refer to the EMD Speed Sensor Technical Information (Danfoss part L1017287) for the correct value.
FaultDetTm U16 —— Sets the time between when the function block detects a:

·          Fault condition and then makes a fault declaration.

·          Cleared fault condition and then clears the fault declaration. 1,000 = 1,000 ms.

DirLockHz U16 0–8,000 Hz Sets the frequency above which the function block’s Dir output locks. Above this frequency, the function block does not report changes in direction.

1,000 = 1,000 Hz.

MC Controller—Input Configuration

If you have an SC controller

You route the function block’s:

Phase A and Phase B inputs through MFIn.
You must change the MFIn default configurations to accept these inputs.

How to Configure a MFIn

Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-FIG-4

  1. In the GUIDE template, enter the Inputs page.
    Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-FIG-5
  2. Enter the MFIn page that receives the input.
    Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-FIG-6
  3. Make the changes that are shown in the preceding figure.

SC Controller—Input Configuration

If you have an MC controller

You route this function block’s:
Phase A and Phase B inputs through MFIn.
You must change the default configuration of the MFIn to accept this input.

The MFIn that you use must be capable of a Freq input and have configurable Bias, Range, and InputMode values.

How to Configure a MFIn

Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-FIG-7

  1. In the GUIDE template, enter the Inputs page.
    Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-FIG-8
  2. Enter the MFIn page that receives the input.
    Danfoss-PLUS+1-Compliant-EMD-Speed-Sensor-QUAD-Function-Block-FIG-9
  3. Make the changes that are shown in the preceding figure.

Products we offer

  • Bent Axis Motors
  • Closed Circuit Axial Piston
    Pumps and Motors
  • Displays
  • Electrohydraulic Power
    Steering
  • Electrohydraulic
  • Hydraulic Power Steering
  • Integrated Systems
  • Joysticks and Control
    Handles
  • Microcontrollers and
    Software
  • Open Circuit Axial Piston
    Pumps
  • Orbital Motors
  • PLUS+1™ GUIDE
  • Proportional Valves
  • Sensors

Danforss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and electronic components. We specialize in providing state-of-the-art technology and solutions that excel in the harsh operating conditions of the mobile off-highway market. Building on our extensive applications expertise, we work closely with our customers to ensure exceptional performance for a broad range of off-highway vehicles. We help OEMs around the world speed up system development, reduce costs and bring vehicles to market faster. Danfoss—Your Strongest Partner in Mobile Hydraulics.

Go to www.powersolutions.danfoss.com for further product information.

  • Wherever off-highway vehicles are at work, so is Danfoss.
  • We offer expert worldwide support for our customers, ensuring the best possible solutions for outstanding performance. And with an extensive network of Global Service Partners, we also provide comprehensive global service for all of our components.
  • Please contact the Danfoss Power Solution representative nearest you.

Local address:

Danfoss
Power Solutions US Company 2800 East 13th Street
Ames, IA 50010, USA
Phone: +1 515 239-6000

Danfoss
Power Solutions GmbH & Co. OHG Krokamp 35
D-24539 Neumünster, Germany Phone: +49 4321 871 0

Danfoss
Power Solutions ApS Nordborgvej 81
DK-6430 Nordborg, Denmark Phone: +45 7488 4444

Danfoss Ltd.
Power Solutions
B#22, No. 1000 Jin Hai Rd. Shanghai 201206, China Phone: +86 21 3418 5200

Danfoss can accept no responsibility for possible errors in catalogs, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss Power Solutions (US) Company. All rights reserved.

L1429531 · Rev AA · May 2015

www.danfoss.com

©2015 Danfoss Power Solutions (US) Company

Documents / Resources

Danfoss PLUS+1 Compliant EMD Speed Sensor QUAD Function Block [pdf] User Manual
PLUS 1 Compliant EMD Speed Sensor QUAD Function Block, PLUS 1, Compliant EMD Speed Sensor QUAD Function Block, Speed Sensor QUAD Function Block, Sensor QUAD Function Block, QUAD Function Block, Function Block, Block

References

Leave a comment

Your email address will not be published. Required fields are marked *