global sources IM1281B Electricity Metering Module User Manual
global sources IM1281B Electricity Metering Module

Overview

global sources IM1281B Electricity Metering Module

The IM1281B single-phase AC electricity metering module is developed in order to adapt to various manufacturers to monitor the power consumption of their products; it is also an suitable module for AC charging pile, street lamp, computer room, base station to save energy and monitor. The accuracy is better than the national level 1 standard;

The module uses an industrial-grade dedicated electricity  metering SOC chip, and the voltage and current are fully isolated for sampling. It has the function of Higher integration and better reliability. The module is small in size, easy to integrate and embed into various systems.

Introduction

  • A single module can collect single-phase AC parameters, including voltage, current, power, power factor, frequency, electric energy, temperature etc.
  • It adopts industrial-grade dedicated electricity metering SOC chip with high measurement accuracy.
  • The communication protocol adopts the general standard DL/T 645-2007 and the standard Modbus-RTU protocol (choose one of the two), which has good compatibility and is more convenient for communication and development.
  • Data protection against power failure.
  • The power storage is large. It can be turned over to restart the measurement while it is full.
  • The product has obtained RoHS , CE , and test report of Metrology Institute.
  • It meets the relevant measurement requirements in “JJG1148-2018 Electric Vehicle AC Charging Pile Measurement Verification Regulations”.
  • It meets the relevant measurement requirements in “QZTT2301.4-2018 Base Station Intelligent Motion Monitoring
    Unit (FSU) Technical Requirements Part 4: Micro-Station Type”.

Application

The IM series AC and DC metering modules have been widely used in AC and DC charging piles, smart homes, dynamic environment monitoring FSU, smart security, lighting monitoring, smart parks, digital computer rooms, energy consumption management, battery monitoring etc. And it has been adopted and recognized by benchmarking companies in different industries. It is important supporting modules for entering the Internet of Things era.

Notes

  • Please refer to the corresponding diagram for correct wiring according to product specifications and models. Be sure to disconnect all signal sources before wiring to avoid danger and damage to the device. After checking that the wiring is correct, turn on the power to test.
  • After it is powered, the red LED indicator is always on, and during communication, the red LED indicator flashes
    synchronously during transmission.
  • It is set to the default configuration: address No. 1, baud rate 4800bps, data format “n,8,1”.It can be reset through the IM-S11 software.

Parameter

Parameter

Active Accuracy

1.0
Voltage Range

1-380V ±0.5%F.S

Current Range

10mA-50A ±0.5%F.S
Current Range Expansion

Extensible Range(Customized)

Frequency

AC45~65Hz
Temp.

Chip Temp.

Min. Power Variable

0.0001kW
Power Factor

Measurable

Min. Electric Power Variable

0.001kWh

Co2

National standard formula calculation

Communication

Interface Type

Uart Port TTL
Communication Protocol

DL/T 645-2007 & MODBUS-RTU

Data Format

“n,8,1”(No check、data bits: 8 、stop bit :1) by default
Baud rate

2400bps-19200bps, 4800bps by default

Data refresh interval

≥250ms
Indicator

Power/Communication(Red)

Performance

Typical Power Consumption

≤10mA
Power Supply

DC5.0V

Voltage Level

AC3000Vrms
Overload Capacity

1.2 * Range

Working Environment

Working Temp.

-40~+80℃

Relative humidity

5~95%,No dense(under 40℃)
Altitude

0~3000 m

Working Environment

place which there is no explosion, corrosive gas and conductive dust, no significant vibration and impact

Dimension

Dimension

43.4mmx 25.8mmx 28mm
Installation

2.54 pitch pin installation

Definition of Module Pin

  • Module Pin

Pin

Function

V-

Power Supply Ground
V+

Power Supply Positive

Notes: The Voltage is the power supply voltage for the module, which generally consumes power with the MCU.5V by default.3.3V power supply is available when short-circuiting the K1 point of the module. At this time, the reverse connection protection function is invalid. Ensure correct wiring or it wil directly burn out.

RX

UART TTL receive,for external TX

TX

UART TTL send,for external RX
PF

Pulse output pin,for detecting energy accuracy (can be idle if there is no need)

UL

For fire line
UN

For zero line

Modbus Communication Protocol

Modbus Protocol Electric Parameter Register List(4 bytes per address, high byte first)

Serial No.

Items Address Length Read/Write

Type and explanation

1

Voltage 0048H 4 Read 16 Unsigned numbers Unit 0.0001V

Actual Value= HEX2DEC(Register Value) x Unit

2 Current 0049H 4 Read

16 Unsigned numbers Unit 0.0001A

3

Active 004AH 4 Read 16 Unsigned numbers Unit 0.0001W
4 Active Electric Energy 004BH 4 Read/Write 0

16 Unsigned numbers Unit 0.0001KWh

5

Power Factor 004CH 4 Read 16 Unsigned numbers Unit 0.001
6 Co2 Emission 004DH 4 Read

16 Unsigned numbers Unit 0.0001Kg

7

Temp. 004EH 4 Read 16 Unsigned numbers Unit 0.01℃
8 Frequency 004FH 4 Read

16 Unsigned numbers Unit 0.01Hz

21 Address Baud rates 0004H 2 Read/Write 16 Default Value 0105H:(Address 01H 8,N,1,4800),Default Address 1 High Bytes presents Address,range 1~255 ,0 is Broadcast Address.

Low Bytes:High 2 bits data format

(00: 10 bits data “8,N,1″) No check 1 end bit

(01: 11 bits data “8,E,1″) Even Parity Check 1 end bit (10: 11 bits data “8,O,1″) Odd Parity Check 1 end bit Low Bytes:Low 4 bits present Baud rates

(3 : 1200bps 4 : 2400bps) (5 :4800bps 6 : 9600bps) (7 : 19200bps)

Modbus Communication Protocol

This instrument provides Uart TTL communication interface, which adopts standard Modbus-RTU protocol. All kinds of data information can be transmitted on the communication line. Each network instrument can set its communication address. And the communication connection should use shielded twisted-pair wire with copper net, whose diameter is no less than 0.5mm2. When wiring, keep the communication line away from strong electric cables or other strong electric field Environment.

Modbus protocol response data flow
Data Flow

The Modbus protocol uses a master-slave response communication connection method on a communication line. First, the signal of the host computer is addressed to a terminal device (slave) with a unique Address, and then the response signal sent by the terminal device is transmitted to the host in the opposite direction, that is: All communication data streams are transmitted in the opposite two directions along a communication line (half-duplex Working mode). The Modbus protocol only allows communication between the host (PC, PLC, etc.) and terminal devices, and does not allow data exchange between independent terminal devices, so that each terminal device will not occupy the communication line when they are initialized, but is limited to response Inquiry signal to the machine.

Host device query: The query message frame includes the device address, function code, data information code, and check code. The address code indicates the slave device to be selected; the function code tells the selected slave device what function to be performed, for example, the function code 03 or 04 requires the slave device to Read registers and return their contents; the data segment contains the slave device’s requirements for any additional information of the execution function, the check code is used to check the correctness of a frame of information. The slave device provides a method to verify whether the message content is correct. It uses the CRC16 calibration rule.

Slave device response: If the slave device generates a normal response, the response message contains the address code, function code, data information code and CRC16 check code. The data information code includes the data collected from the device: such as register value or status. If an error occurs, we agree that the slave device will not respond.

We stipulate the communication data format used in this instrument: the bits of each byte (1 start bit, 8 data bits, Odd Parity Check or Even Parity Check or No check, 1 or 2 stop bits).

The structure of the data frame, that is, the message format:

Address

Function code Data segment CRC16 check code
1 byte 1 byte N bytes

2 bytes(Low Byte first)

Device Address: Consists of one byte. The Address of each terminal device must be unique, and only the addressed
terminal will respond to the corresponding query.

Function code: tells what function the addressed terminal performs. The following table lists the function codes supported by this series of instruments and their functions.

Function Code

Function

03H

Read one or more register value
10H

Write one or more register value

Data segment: Contains the data required by the terminal to perform a specific function or the data collected when the
terminal responds to a query. The content of these data may be numerical values, reference addresses, or set values.

Check code: CRC16 occupies two bytes and contains a 16-bit binary value. The CRC value is calculated by the transmitting device and then appended to the data frame. The receiving device recalculates the CRC value when receiving the data, and then compares it with the value in the received CRC field. If the two values are not equal, mistake will happens Process of generating a CRC16:

  1. Preset a 16-bit register as 0FFFFH (all 1s), which is called CRC register.
  2. XOR the 8 bits of the first byte in the data frame with the low byte in the CRC register, and store the result back to the
    CRC register.
  3. Shift the CRC register one bit to the right, fill the highest bit with 0, and shift the lowest bit out and check.
  4. If the lowest bit is 0: repeat the third step (the next shift); if the lowest bit is 1: XOR the CRC register with a preset fixed
    value (0A001H).
  5. Repeat the third and fourth steps until 8 shifts. A complete eight bits have been processed in this way.
  6. Repeat steps 2 to 5 to process the next eight bits until all bytes are processed.
  7. The final value of the CRC register is the value of CRC16.

Modbus-RTU Communication Protocol cases

Function code 0x03:Read multi-port register

E.g:The host device needs to read Address as 01, and start sending data from the 2 slave registers with Address as 0048H:

1 3 00 48 00 02 CRC
Address Function Code Start Address Length CRC Code
Slave device responds: 1 3 8 HH HH HH HH CRC
Address Function Code Return Bytes No. Register Data 1 Register Data 2 CRC Code

Function code 0x10:Write multi-port Register

E.g:The host device need save 0000,0000 to the slave Register whose Address is 000C,000D (the address code of the slave is 0x01)

Host Device send 01: 10 00 0C 00 02 4 00 00 00 00 F3 FA
Address Function code Start Address Write Register Number Bytes numbers Data 1 Data 2 CRC code
Slave Device responds 01: 10 00 0C 00 02 81 CB
Address Function code Start Address Write Register Number CRC code

Notes: When setting parameters, do not write illegal data (that is, the data value that exceeds the limit of the data range);

Communication Messages Case

  1. Read Data Register (Function code 03H):Read 8 Register value which starts with 48H, Host device Read Data
    frame:01 03 00 48 00 08 C4
    Address Command Start Address (High bytes first) Register value (High bytes first) Check code (Low bytes first)
    01H 03H 00H,48H 00H,08H C4H,1AH

    Instrument responds Data frame:01 03 20 00 21 8D D8 00 01 38 75 01 0C 63 08 00 00 00 5A 00 00 03 E8 00 00 00 59 00 00 0C CB 00 00 13 88 1B C2
    It is:
    Address 01
    Voltage 219.9000V
    Current 7.9989A
    Power 1758.9000W
    Electric Energy 0.0090kWh
    Power Factor 1.000 Co2
    0.0089Kg
    Frequency 50.00Hz
    E.g:Voltage actual value= HEX2DEC(00 21 8D D8) Hexadecimal to Decimal x 0.0001V Unit = 219.9000V

    Address

    Command Data Length Data (4 bytes/32 bytes),hexadecimal

    Check code

    01H 03H 20H 00 21 8D D8 00 01 38 75 01 0C 63 08 00 00 005A
    00 00 03 E8 00 00 00 59 00 00 0C CB 00 00 1388
    1BH,C2H
  2. Write Data Register (Function code 10H):
    Clear Host device Write Data frame:01 10 00 4B 00 02

    Address

    Command Start Address Register Value Bytes Data

    Check code

    01H 10H 00H,4BH 00H,02H 04H 00H,00H,00H,00H B6H,2CH

    Instrument responds Data frame:01 10 00 4B 00 02 2B F0

    Address Command Start Address Register value Check code
    01H 10H 00H,4BH 00H,02H 2BH,F0H

DL/T 645-2007 electricity meter Communication Protocol

The DL/T645 protocol is an industry communication protocol for meter communication. If you are not familiar with it, it is not recommended.

645 protocol electric parameter Register List

Serial No. Definition Register Address Length Read/Write

Data Type and explanation

1 Voltage 02010100 2 Read XXX.X Unit 0.1V
2 Current 02020100 3 Read XXX.XXX Unit 0.001A
3 Active Power 02030000 3 Read XX.XXXX Unit 0.0001kW
4 Active Total Power 00000000 4 Read/Write 0 XXXXXX.XX Unit 0.01KWh
5 Extended total power 80800001 4 Read/Write 0 16 Unsigned numbers Unit 0.001KWh
6 Power Factor 02060000 2 Read X.XXX Unit 0.001
7 Temp. 02800007 2 Read XXX.X Unit 0.1℃
8 Frequency 02800002 2 Read XX.XX Unit 0.01Hz
9 Address 04000401 6 Read/Write NNNNNNNNNNNN Default 111111111111
10 Baud rates 04000703 1 Read/Write 16 Unsigned numbers(04: 1200bps              08:

2400bps) (10:4800bps

20:

          9600bps) (40:19200bps)

Dimension

Dimensions Diagram

Wiring diagram

  • IM1281B Standard wiring diagram
    wiring diagram
  • IM1281B Schematic diagram of pulse detection interface wiring
    Pulse Output detection Circuit
    Schematic diagram
  • IM1281B Three-phase measurement application diagram
    application diagram
  • IM1281B Typical Communication exception instructions and short-circuit point K1 indication diagram
    instructions
    If the connection is correct, the communication indicator flashes, but the data does not return, please short-circuit this current-limiting resistor and then communicate.
    Notes:
    The reason for this exception is caused by the matching difference between different USB to TTL tools. If the actual use is direct communication between the module and the MCU, this situation does not exist.

Process requirements

  • When welding this product, the highest welding Temp.<350℃, and the welding time ≤5 seconds
  • This product contains quartz crystal, so ultrasonic cleaning is strictly prohibited.
  • The surface of this product is sprayed with three-proof paint for protection, and it is strictly forbidden to clean the surface of the product

Precautions

  • Please refer to the diagram for correct wiring according to the product specifications and models. Be sure to disconnect all signal sources and power before wiring to avoid danger and damage to the equipment. After checking that the wiring is correct, turn on the power to test.
  • The voltage circuit or the secondary circuit of the PT cannot be short-circuited.
  • When there is Current on the primary side of the CT, it is strictly forbidden to open the secondary circuit of the CT; it is strictly forbidden to connect live wires or unplug the terminals.
  • When the product is used in an environment with strong electromagnetic interference, please pay attention to the
    shielding of the input and output signal lines.
  • For centralized installation, the Min. installation interval should not be less than 10mm.
  • There is no lightning protection circuit in this series of products. When the input and output feeders of the module are exposed to the harsh outdoor environment, lightning protection is a must.

 