Autonics - logoADIO-EI Remote I/O Boxes (EtherNet/IP)
User ManualAutonics ADIO-EI Remote I O Boxes (EtherNet IP)

For your safety, read and follow the considerations written in the instruction manual, other manuals and Au tonics website.
The specifications, dimensions, etc. are subject to change without notice for product improvement. Some models may be discontinued without notice.

Features

  • The upper level communication protocol: Ethernet/IP
  • The lower level communication protocol: IO-Link ver. 1.1 (port class: Class A)
  • Housing material: Zinc Die casting
  •  Protection rating: IP67
  • The daisy chain allows the power supply using the connection technology in a standardized 7/8” connector
  • The maximum output current of power supply: 2 A per port
  • I/O port settings and status monitoring (cable short / disconnection, connection status, etc.)
  • Supports digital input filter

Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
  • Warning icon  symbol indicates caution due to special circumstances in which hazards may occur.

Warning icon Warning Failure to follow instructions may result in serious injury or dealt.

  1.  Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
    Failure to follow this instruction may result in personal injury, economic loss or fire.
  2. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present. Failure to follow this instruction may result in explosion or fire.
  3. Do not connect, repair, or inspect the unit while connected to a power source.
    Failure to follow this instruction may result in fire.
  4. Check ‘Connections’ before wiring.
    Failure to follow this instruction may result in fire.
  5. Do not disassemble or modify the unit.
    Failure to follow this instruction may result in fire.
  6. Do not touch the product during operation or for a certain period of time after stopping.
    Failure to follow this instruction may result in burn.

Warning icon Caution Failure to follow instructions may result in injury or product damage.

  1. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or shortening the life cycle of the product.
  2. Use a dry cloth to clean the unit, and do not use water or organic solvent. Failure to follow this instruction may result in fire.
  3. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
    Failure to follow this instruction may result in fire or product damage.
  4. Connect the cable correctly and prevent poor contact.
    Failure to follow this instruction may result in fire or product damage.
  5. Do not connect or cut off the wire of the cable while operating the unit.
    Failure to follow this instruction may result in fire or product damage.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
  • The UA power (actuator power) and US power (sensor power) should be insulated by the individually isolated power device.
  • Power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
  • Use the rated standard cables and connectors. Do not apply excessive power when connecting or disconnecting the connectors of the product.
  • Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power line and input signal line closely, use line filter or varactor at power line and shielded wire at input signal line. For stable operation, use shield wire and ferrite core, when wiring communication wire, power wire, or signal wire.
  • Do not use near the equipment which generates strong magnetic force or high frequency noise.
  • Do not connect, or remove this unit while connected to a power source.
  • This unit may be used in the following environments.
    – Indoors (in the environment condition rated in ‘Specifications’)
    – Altitude max. 2,000 m
    – Pollution degree 2
    – Installation category II

Configuration of ADIO-EI

The figure below shows the EtherNet/IP network and the devices that compose it.
For proper use of the product, refer to the manuals and be sure to follow the safety considerations in the manuals. Download the manuals from the Au tonics website.Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - configuration

STEP Reference manual
Hardware installation Install and ground the ADIO ADIO-EI Product Manual
Connect the ports of ADIO
Supply power to the ADIO
O-Link device settings Set parameters and functions of IO-Link device atIOLink User Manual
EtherNet/IP Master

ADIO-EI
Integrate the ADIO-EI to EtherNet/IP project ADIO-EI (Studio 5000 Logix Designer Guide) 01)
Set the ports of ADIO-EI
Checking the operation Check the indicators ADIO-EI Product Manual

01) The project planning software of the upper level communication system may be different depending on the user’s environment. For more information, refer to the manufacturer’s manual.
The configuration instance and class

Operation mode Fault State 01) Validation Data Storage Input Filter 01) Vendor ID Device ID Cycle Time
Digital Input
Digital Output
IO-Link Input
IO-Link Output
IO-Link Input/Output

Ordering Information
This is only for reference, the actual product does not support all combinations. For selecting the specified model, follow the Autonics websiteAutonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 1

1 I/O specification
N: NPN
P: PNP
Product Components

  • Product (+ Protective cover for the rotary switches)
  • Name plates × 20
  • M4×10 screw with washer × 1
  • Instruction manual × 1
  • Waterproof cover × 4

Sold Separately

  • Name plates
  • Waterproof cover

Software
Download the installation file and the manuals from the Autonics website.
airlink
airlink with purposes for setting, diagnosis, initialization and maintenance of IO-Link device via IODD file is provided as the dedicated Port and Device Configuration Tool (PDCT).

Connections

 Ethernet port

M12 (Socket-Female), D-coded Pin Function Description
Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 2 1 TX + Transmit Data +
2 RX + Receive Data +
3 TX – Transmit Data –
4 RX – Receive Data –

Power supply port

OUT (7/8”, Socket- Female) IN (7/8”, Plug-Male) Pin  Function Description
Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 3 Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 4 1, 2 0 V Sensor and actuator
supply
3 F.G. Frame ground
4 +24 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3  Sensor supply
5 +24 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3  Actuator supply

PDCT port

M12 (Socket-Female), A-coded Pin Function
Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 5 1 Not Connected (N.C.)
2 Data –
3 0 V
4 Not Connected (N.C.)
5 Data +

I/O port

M12 (Socket-Female), A-coded Pin Function
Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 6 1 +24 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3
2 I/Q: Digital Input
3 0 V
4 C/Q: IO-Link, Digital Input/output
5 Not Connected (N.C.)

Dimensions

  • Unit: mm, For the detailed dimensions of the product, follow the Autonics website.

Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - dimensionsUnit DescriptionsAutonics ADIO-EI Remote I O Boxes (EtherNet IP) - remote control

  1. Grounding hole
  2. Mounting hole
  3. Insertion part for the name plate
  4. Ethernet port
  5. Power supply port
  6. PDCT port
  7. I/O port
  8. Rotary switches
  9. Status indicator
  10. I/O port indicator

Installation

Mounting

  1. Prepare a flat or metal panel in the enclosure.
  2. Drill a hole to mount and ground the product on the surface.
  3. Turn off all power.
  4. Fix the product using M4 screws in the mounting holes. Tightening torque: 1.5 N m

Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - mountingGrounding
Warning icon Be sure to use a cable with low impedance and as short as possible for connecting the housing to the product.

  1. Connect the grounding strap and M4×10 screw with washer.
  2. Fix the screw in the grounding hole. Tightening torque: 1.2 N m

Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - groundingIP Address Settings
To connect to the Ethernet/IP network, configure the Ethernet/IP interface. The IP address can be assigned using the following methods.
Rotary switches
Warning icon  Be sure to place the seal of the protective cover firmly on the rotary switches after completing the settings.
The protection rating is not guaranteed when the protective cover is open.Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 7

  1. Rotate the rotary switches to set the mode and IP address. The green LED of the US indicator flashes.
    Setting mode Rotary switches Description Value
    Default IP Address 000 This IP address is stored in the ADIO-EI’s EEPROM. Applying the IP address set on the atIOLink software. Factory settings: 192.168.2.3
    Static IP Address 001 to 255 The IP address of the Ethernet port. Set the last octet of the IP address. 192.168.2.□□□
    BOOTP 800 to 899 The IP address is assigned by the Bootstrap Protocol (BOOTP)-server. IP Address, Subnet Mask., etc
    DHCP 900 to 999 The IP address is assigned by the DHCP-server. IP Address, Subnet Mask., etc
  2. Turn on the ADIO-EI again.
  3. Check that green LED of the US indicator is ON.
  4. The IP address has been changed.
  5. Put the protective cover on the rotary switches.

airlink
The address assigned by the airlink software is stored in the ADIO-EI’s EEPROM. For more information, refer to the atIOLink User Manua

Address Description Factory settings
Static IP Address The default IP address of the ADIO-EI 192.168.2.3
Subnet Mask The subnet mask of the IP network 255.255.255.0
Gateway Address The IP address of the gateway 192.168.2.1

Port Connections
 Port specifications

  • Be sure to check the port specifications below before connecting the device. Prepare a cable that complies with the protection rating IP67
Ethernet port I/O port PDCT port Power supply port
Type M12 (Socket-Female), 4-pin, D-coded M12 (Socket-Female), 5-pin, A-coded M12 (Socket-Female), 5-pin, A-coded Input: 7/8” (Plug-Male), 5-pin Output: 7/8” (Socket-Female), 5-pin
Push-Pull YES YES YES N.A
Number of ports 2 8 1 2
Tightening torque 0.6 N m 0.6 N m 0.6 N m 1.5 N m
Supported function Daisy chain USB serial communication Daisy chain
Connector 1 Connector 2 Wiring
Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 8 Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 9 Connector 1 Pin no. Connector 1 Function Connector 2 Pinno. Connector 2 Function
1 N.C.
2 Data – 3 Data-
3 0 V 1 0 V
4 N.C. 4 + 5 VDC=
5 Data + 2 Data +

Connect to the EtherNet/IPAutonics ADIO-EI Remote I O Boxes (EtherNet IP) - enther net

  1. Connect the M12 connector to the Ethernet port. See the connections below.Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 10
    1 TX + Transmit Data +
    2 RX + Receive Data +
    3 TX – Transmit Data –
    4 RX – Receive Data –

     

  2. Connect the connector to the Ethernet/IP network.
    • Network device: PLC or Ethernet/IP device supporting Ethernet/IP protocol
  3. Put the waterproof cover on the unused port.

Connect the IO-Link devices
Warning icon
The maximum output current is 2 A at each I/O port. Configure the device so that the total current of the I/O ports does not exceed 9 A.
Warning icon Check the wiring information in the manual of the IO-Link device to be connected.Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - Link device

  1. Connect the M12 connector to the I/O port. See the connections below.Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 11
    1 +24 VDC ART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3
    2 I/Q: Digital Input
    3 0 V
    4 C/Q: IO-Link, Digital Input/output
    5 Not Connected (N.C.)

     

  2. Put the waterproof cover on the unused port.

Port Connections

Connect with the airlink
Warning icon Do not use the PDCT port and the Ethernet port at the same time.Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - at olink

  1. Connect the M12 connector to the PDCT port. See the connections below.
    Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 1 2
    1 Not Connected (N.C.)
    2 Data –
    3 0 V
    4 Not Connected (N.C.)
    5 Data +

     

  2.  Connect the connector to the network device.
    • Network device: PC/laptop that airlink software is installed
  3.  Put the waterproof cover on the unused port.

Connect the power supply to ADIO
Warning icon Be sure not to exceed 9 A of the maximum supplying current to the sensor (US).Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - power sapply

  1. Turn off all power.
  2. Connect the 7/8″ connector to the power supply port. See the connections below.

Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 13

1, 2 0 V Sensor and actuator supply
3 F.G. Frame ground
4 +24 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3 Sensor supply
5 +24 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3 Actuator supply

Indicators

Status indicatorAutonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 1401. The power supply of sensor

Indicator LED color Status Description
 US  Green ON Applied voltage: normal
Flashing (1 Hz) The settings of the rotary switches is changing.
Red Flashing (1 Hz) Applied voltage: low (< 18 VDCᜡ)

02. The power supply of actuator

Indicator LED color Status Description
 UA Green ON Applied voltage: normal
 Red Flashing (1 Hz) Applied voltage: low (< 18 VDCᜡ), Error in the rotary switches
ON Applied voltage: none (< 10 VDCᜡ)

03. Error status

Indicator LED color Status Description
 US, UA  Green Flashing (1 Hz) Error in the rotary switches (the applied voltage: normal)
Red ON ADIO initialization failure

04. Module status

Indicator LED color Status Description
 MOD  Green / Red OFF No error
Flashing Device self-testing: Power
 Green ON Operating
Flashing Standby: Device is not configured. (no IP address)
 

Red

ON Unrecoverable error (module failed)
Flashing Error in device configuration (invalid configuration)

05. Network status

Indicator LED color Status Description
 NET  

Green / Red

OFF No Power and IP address
Flashing Device self-testing: Power
 Green ON The connection is established.
Flashing No connection
 Red ON IP address conflict: Another device has the same IP address.
Flashing Connection timeout

06. Ethernet connection

Indicator LED color Status Description
 L/A1 L/A2  

Green

OFF No Ethernet connection
ON The Ethernet connection is established.
Yellow Flashing Data transmission

07. Transmission rate of the Ethernet

Indicator LED color Status Description
 100  Green OFF Transmission rate: 10 MPs
ON Transmission rate: 100 MPs

I/O port indicatorAutonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 1501. Pin 4 (C/Q)

Indicator LED color Status Description
0  Yellow OFF DI/DO: pin 4 OFF
ON DI/DO: pin 4 ON
 Green ON Port configuration: IO-Link
Flashing (1 Hz) Port configuration: IO-Link, No IO-Link device found
 Red Flashing (2 Hz) IO-Link configuration error
•  Validation failed, Invalid data length, Data Storage error
  ON •  NPN: Short circuit occurred on the output of pin 4 and pin1
•  PNP: Short circuit occurred on the output ofpin 4 and pin 3

02. Pin 2 (I/Q)

Indicator LED color Status Description
 1  Yellow OFF DI: pin 2 OFF
ON DI: pin 2 ON

03. The power supply of the I/O port

Indicator LED color Status Description
 0,1  Red Flashing (1 Hz) Short circuit occurred in the I/O supply power (pin 1, 3)

Specifications

Electrical/Mechanical specifications

Supply voltage 18 – 30 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3 
Rated voltage 24 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3 
Current consumption 2.4 W ( ≤ 216 W)
Supplying current per port ≤ 2 A/Port
Sensor current (US) ≤ 9 A
Dimensions W 66 × H 215 × D 38 mm
Material Zinc Die casting
 Ethernet port M12 (Socket-Female), 4-pin, D-coded, Push-Pull Number of ports: 2 (IN/OUT)
Supported function: daisy chain
 Power supply port Input: 7/8” (Plug-Male), 5-pin Output: 7/8” (Socket-Female), 5-pin Number of ports: 2 (IN/OUT) Supported function: daisy chain
 PDCT port M12 (Socket-Female), 5-pin, A-coded, Push-Pull Number of ports: 1 Connection method: USB serial communication
 I/O port M12 (Socket-Female), 5-pin, A-coded, Push-Pull Number of ports: 8
Mounting method Mounting hole: fixed with M4 screw
Grounding method Grounding hole: fixed with M4 screw
Unit weight (packaged) ≈ 700 g (≈ 900 g)

Mode specifications

Mode Digital Input
Number of channels 16-CH (I/Q: 8-CH, C/Q:8-CH)
I/O common NPN / PNP
Input current 5 mA
 ON voltage/current Voltage: ≥ 15 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3 Current: ≥ 5 mA
OFF voltage ≤ 5 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3
Mode Digital Output
Number of channels 8-CH (C/Q)
I/O common NPN / PNP
Power supply 24 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3 (18 – 30 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3), Max. 300 mA
Leakage current ≤ 0.1 mA
Residual voltage ≤ 1.5 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3
Short circuit protection YES
Mode IO-Link
Input current 2 mA
 ON voltage/current Voltage: ≥ 15 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3 Current: ≥ 2 mA
OFF voltage ≤ 5 VDCART SOUND ARBT76 Prisma Cube LED Wireless Speaker - icon 3

Environmental conditions

Ambient temperature 01) -5 to 70 °C, Storage: -25 to 70 °C (no freezing or condensation)
Ambient humidity 35 to 75%RH (no freezing or condensation)
Protection rating IP67 (IEC standard)

01) UL approved ambient temperature: 45 ℃
Approvals

Approval Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon 16
Association approval Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon

Communication Interface

Ethernet

Ethernet standard 100BASE-TX
Cable spec. STP (Shielded Twisted Pair) Ethernet cable over Cat 5
Transmission rate 10 / 100 Mbps
Cable length ≤ 100 m
Protocol EtherNet/IP
Address settings Rotary switches, DHCP, BOOTP, airlink
 Factory settings •  IP Address: 192.168.2.3
•  Subnet Mask: 255.255.255.0
•  Gateway Address: 192.168.2.1
EDS file Download the EDS file at the Au tonics website.

IO-Link

Version 1.1
Transmission rate COM1 : 4.8 kbps / COM2 : 38.4 kbps / COM3 : 230.4 kbps
Port class Class A
 Standard IO-Link Interface and System Specification Version 1.1.2 IO-Link Test Specification Version 1.1.2

Autonics - logo18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002
www.autonics.com
+82-2-2048-1577
sales@autonics.com
Autonics ADIO-EI Remote I O Boxes (EtherNet IP) - icon

Documents / Resources

Autonics ADIO-EI Remote I/O Boxes (EtherNet/IP) [pdf] User Manual
ADIO-EI Remote I O Boxes EtherNet IP, ADIO-EI, Remote I O Boxes, EtherNet IP

References

Leave a comment

Your email address will not be published. Required fields are marked *