iSMACONTROLLI SfAR-S-16RO Expansion Module – 16 Relay Outputs

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-product-image

Introduction

Thank you for choosing our product.
This manual will help you with proper handling and operating of the device.
The information included in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law. This information does not discharge you from the liability of your own judgement and verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations concluded therein.

WARNING!
Failure to follow instructions can result in equipment damage or impede the use of the hardware or software.

Revision History
Rev. Date Description
3.2 25 May 2022 Rebranded

Safety Rules

  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.
  • Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock.
  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.
  • Do not disassemble the product. Doing so might cause an electric shock or faulty operation.
  • Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to  do so might cause a fire or faulty operation.
  • Firmly tighten the wires to the terminal. Failure to do so might cause a fire.
  • Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an
  • uncontrolled interference, resulting in an instable operation of the product.
  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can  cause interferences in monitored and control signals.
  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC
  • transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from  other transformers and loads.
  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.
  • Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single
  • power source causes a risk of introducing disturbances from the loads to the control devices.
  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects,  which are dangerous for devices.
  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external  communication. It is recommended to use galvanic separators.
  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.
  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it  is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.
  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do  not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Module Features

Purpose and Description of the Module

The SfAR-S-16RO module is an innovative device that provides a simple and cost effective extension of the number of lines of output with high current-carrying capacity. The module has 16 relay outputs.

The module is connected to the RS485 bus with a twisted-pair wire. Communication is via Modbus RTU or Modbus ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200.

The module is designed for mounting on a DIN rail in accordance with DIN EN 5002.
The module is equipped with a set of LEDs to indicate the status of inputs and outputs, power supply, and communication, which is useful for diagnostic purposes and helping to find errors.

Module configuration is done via USB by using a dedicated computer program. It also allows for changing the parameters using the Modbus protocol or set the Modbus address using the DIP switches under the front panel.

Technical SpecificationInterfaceRS485
Power Supply Voltage 10-38 V DC; 10-28 V AC
Power consumption (with active Modbus transmission and high state on all outputs) 4.8 W at 24 V DC
7 VA at 24 V AC
Relay Outputs No. of outputs 16
Maximum current and voltage (resistive load) 3 A 230 V AC
3 A 30 V DC
Temperature Work -10°C to +50°C (14°F to 122°F)
Storage -40°C to +85°C (-40°F to 185°F)
Connectors Power supply 2 pins
Communication 3 pins
Outputs 10 pins
Configuration mini USB
Size Height 119.1 mm (4.689 in)
Length 110.9 mm (4.366 in)
Width 22.7 mm (0.894 in)
Up to 128 devices

Table 2. Technical specification

Dimensions

The appearance and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard. Power connectors, communication and IOs are at the bottom and top of the module. USB connector configuration and indicators are located on the front of the module.

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-01Figure 1. Dimensions

Communication

Grounding and Shielding

In most cases, I/O modules will be installed in an enclosure along with the other devices, which generate electromagnetic radiation. Relays, contactors, transformers, motor invertors, etc., are examples of such devices. Radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module. Whether or not the SfAR modules are immune to such effects, the interferences must be suppressed at their source if possible to ensure the proper functioning of the entire system. Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. It is recommended to at least follow the rules below:

  • line power cables must be routed with spatial separation from signal and data transmission cables; analog and digital signal cables should also be separated;
  • it is recommended to use shielded cables for analog signals, cable shields should not be interrupted by intermediate terminals; the shielding should be earthed directly after the cable enters the cabinet.

It is recommended to install interference suppressors when switching inductive loads (e.g., coils of contactors, relays, solenoid valves). RC snubbers or varactors are suitable for AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must be connected as close to the coil as possible.

Network Termination

Transmission line effects often present problems for data communication networks. These problems include reflections and signal attenuation.
To eliminate the presence of reflections of signal from the end of the cable, the cable must be terminated at both ends with a resistor across the line adequate to its characteristic impedance. Both ends must be terminated since the propagation is bidirectional. In case of an RS485 twisted pair cable, this termination is typically 120 Ω.

Setting Module Address in RS485 Modbus Network

The following table shows how to set DIP switches to determine the address of the module. The module address is set with the switches in the range of 0 to 127. Addresses from 128 to 255 can be set via RS485 or USB and using dedicated software tool.

Addr SW1 SW2 SW3 SW4 SW5
0 OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF
2 OFF ON OFF OFF OFF
3 ON ON OFF OFF OFF
4 OFF OFF ON OFF OFF
5 ON OFF ON OFF OFF
6 OFF ON ON OFF OFF
7 ON ON ON OFF OFF
8 OFF OFF OFF ON OFF
9 ON OFF OFF ON OFF
10 OFF ON OFF ON OFF
11 ON ON OFF ON OFF
12 OFF OFF ON ON OFF
13 ON OFF ON ON OFF
14 OFF ON ON ON OFF
15 ON ON ON ON OFF
16 OFF OFF OFF OFF ON
17 ON OFF OFF OFF ON
18 OFF ON OFF OFF ON
19 ON ON OFF OFF ON
20 OFF OFF ON OFF ON
21 ON OFF ON OFF ON
22 OFF ON ON OFF ON
23 ON ON ON OFF ON
24 OFF OFF OFF ON ON
25 ON OFF OFF ON ON
26 OFF ON OFF ON ON
27 ON ON OFF ON ON
28 OFF OFF ON ON ON
29 ON OFF ON ON ON
30 OFF ON ON ON ON
31 ON ON ON ON ON

Table 3. Setting module address in RS485 Modbus network, using DIP switch

Types of Modbus Functions
There are 4 types of Modbus functions supported by the SfAR modules

Type Beginning Address Variable Access Modbus Command
1 00001 Digital Outputs Bit Read/write 1, 5, 15
2 10001 Digital Inputs Bit Read 2
3 30001 Input Registers Registered Read 3
4 40001 Output Registers Registered Read/write 4, 6, 16

Table 4. Types of Modbus functions supported by the module

Communication Settings

The data stored in the module’s memory is given in the 16-bit registers. The access to registers is via Modbus RTU or Modbus ASCII.

Default Settings

The default configuration can be restored with the DIP switch, SW6.

Baud Rate 19200
Parity No
Data Bits 8
Stop Bits 1
Reply Delay [ms] 0
Modbus Type RTU
Restoring Default Configuration

To restore the default configuration, follow the steps below:

  • Turn the power off;
  • Turn the DIP switch SW6 on;
  • Turn the power on;
  • When power and the communication led are lit, turn the switch SW6 off.

WARNING! After restoring the default configuration, all values stored in the registers are cleared as well.

Configuration Registers
Modbus Address Decimal Address Hex Address Name Values
40003 2 0x02 Baud Rate 0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005 4 0x04 Parity 0 – none
1 – odd
2 – even
3 – always 0
4 – always 1
40004 3 0x03 Stop Bits 1 – one stop bit
2 – two stop bit
40004 3 0x03 Data Bits 7 – 7 data bits
8 – 8 data bits
40006 5 0x05 Response Delay Time in ms
40007 6 0x06 Modbus Mode 0 – RTU
1 – ASCII

Table 6. Configuration registers

Watchdog

This 16-bit register specifies the time in milliseconds to watchdog reset. If the module does not receive any valid message within this time, all digital and analog outputs will be set to default state.
This feature is useful if there is an interruption in data transmission and for security reasons. Output states must be set to the appropriate state in order to reassure the safety of persons or property.
The default value is 0 milliseconds which means the watchdog function is disabled.

Indicators

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-02Figure 2. Indicators

Indicator Description
Power Supply The LED indicates that the module is correctly powered
Communication The LED lights up when the unit receives the correct packet and sends the answer
Outputs State The LED indicates that the output is on

Table 7. Description of indicators

Connections

Block Diagram

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-03

Power Supply Connection

DC Power Connection

 

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-04Figure 4. DC power connection

AC Power Connection

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-05Figure 5. AC power connection

Communication Bus Connection

 

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-06Figure 6. Communication bus connection

Connection of Relay Outputs

Connection of Resistive Load

 

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-07Figure 7. Connection of resistive load

 

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-08Figure 8. Connection of electrovalve

Quick Connector

The Quick Connector is a unique feature of modules that allows for quickly connecting a group of devices with a flat ribbon cable. Thanks to this solution, it is enough to connect power and RS485 communication to one of the devices in the group, and the others will be powered and communicated with ribbon cable. The Quick Connector is sufficient to connect up to 10 devices next to each other. It is important that the various types of modules in the SfAR-S family can be connected with the ribbon cable.

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-09Figure 9. Quick Connector

DIP Switch

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-10

Switch Function Description
1 Module address +1 Setting module address from 0 to 31
2 Module address +2
3 Module address +4
4 Module address +8
5 Module address +16
6 Restoring default settings Restoring default settings

Table 8. Description of switches

Module Registers

Registered Access
Modbus Address Decimal Address Hex Address Register Name Access Description
30001 0 0x00 Version/Type Read Version and type of the device
30002 1 0x01 Switches Read Switches state
40003 2 0x02 Baud Rate Read/write RS485 baud rate
40004 3 0x03 Stop Bits & Data Bits Read/write No. of stop bits & data bits
40005 4 0x04 Parity Read/write Parity bit
40006 5 0x05 Response Delay Read/write Response delay in ms
40007 6 0x06 Modbus Mode Read/write Modbus mode (ASCII or RTU)
40009 8 0x08 Watchdog Read/write Watchdog
40013 12 0x0C Default Output State Read/write Default output state (after power on or watchdog reset)
40033 32 0x20 Received Packets LSR (Least Significant Register) Read/write No. of received packets
40034 33 0x21 Received Packets MSR (Most Significant Register) Read/write
40035 34 0x22 Incorrect Packets LSR Read/write No. of received packets with error
40036 35 0x23 Incorrect Packets MSR Read/write
40037 36 0x24 Sent Packets LSR Read/write No. of sent packets
40038 37 0x25 Sent Packets MSR Read/write
40052 51 0x33 Outputs Read/write Output state
Bit Access
Modbus Address Dec Address Hex Address Register Name Access Description
193 192 0x0C0 Default State of

Output 1

Read/write Default state of output 1
194 193 0x0C1 Default State of

Output 2

Read/write Default state of output 2
195 194 0x0C2 Default State of

Output 3

Read/write Default state of output 3
196 195 0x0C3 Default State of

Output 4

Read/write Default state of output 4
197 196 0x0C4 Default State of

Output 5

Read/write Default state of output 5
198 197 0x0C5 Default State of

Output 6

Read/write Default state of output 6
199 198 0x0C6 Default State of

Output 7

Read/write Default state of output 7
200 199 0x0C7 Default State of

Output 8

Read/write Default state of output 8
201 200 0x0C8 Default State of

Output 9

Read/write Default state of output 9
202 201 0x0C9 Default State of

Output 10

Read/write Default state of output 10
203 202 0x0CA Default State of

Output 11

Read/write Default state of output 11
204 203 0x0CB Default State of

Output 12

Read/write Default state of output 12
205 204 0x0CC Default State of

Output 13

Read/write Default state of output 13
206 205 0x0CD Default State of

Output 14

Read/write Default state of output 14
207 206 0x0CE Default State of

Output 15

Read/write Default state of output 15
208 207 0x0CF Default State of Output 16 Read/write Default state of output 16
817 816 0x330 Output 1 Read/write Output 1 state
818 817 0x331 Output 2 Read/write Output 2 state
819 818 0x332 Output 3 Read/write Output 3 state
820 819 0x333 Output 4 Read/write Output 4 state
821 820 0x334 Output 5 Read/write Output 5 state
822 821 0x335 Output 6 Read/write Output 6 state
823 822 0x336 Output 7 Read/write Output 7 state
824 823 0x337 Output 8 Read/write Output 8 state
825 824 0x338 Output 9 Read/write Output 9 state
826 825 0x339 Output 10 Read/write Output 10 state
827 826 0x33A Output 11 Read/write Output 11 state
828 827 0x33B Output 12 Read/write Output 12 state
829 828 0x33C Output 13 Read/write Output 13 state
830 829 0x33D Output 14 Read/write Output 14 state
831 830 0x33E Output 15 Read/write Output 15 state
832 831 0x33F Output 16 Read/write Output 16 state

Configuration Software

The SfAR Configurator is a software, which is designed to set the communication module registers over Modbus network as well as to read and write the current value of other registers of the module. It is a convenient way to test the system as well as to observe real-time changes in the registers.

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-11Figure 11. PC connection

Communication with the module is done via a USB cable. The module does not require any drivers.
The SfAR Configurator is a universal software, where it is possible to configure all available modules.

iSMACONTROLLI-SfAR-S-16RO-Expansion-Module-16 Relay-Outputs-12Figure 12. The SfAR Configurator